MIB Viewer

AISLCANALOG-MIB

52 objects
MIB module for SLCs with analog input points.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.539Nodeaii
1.3.6.1.4.1.539.28IdentityaiSLCAnalogMIB module for SLCs with analog input points.
1.3.6.1.4.1.539.28.1TableaiSLCAnalogInputTablenot-accessiblecurrentTable of analog inputs points indexed by point number. Includes description, configuration and status information.
1.3.6.1.4.1.539.28.1.1RowaiSLCAnalogInputEntrynot-accessiblecurrentEntry of aiSLCAnalogInputTable.
1.3.6.1.4.1.539.28.1.1.1ColumnaislcainPointNumberread-onlycurrentInput point number to which this table row applies.
1.3.6.1.4.1.539.28.1.1.2ColumnaislcainScanningEnabledread-writecurrentEnable or disable scanning of the input.
1.3.6.1.4.1.539.28.1.1.3ColumnaislcainDescriptionread-writecurrentTextual description of the point. Maximum length is 80 characters.
1.3.6.1.4.1.539.28.1.1.4ColumnaislcainTrapEnableread-writecurrentEnable or disable alarm traps.
1.3.6.1.4.1.539.28.1.1.5ColumnaislcainNormalStateTrapread-writecurrentIf enabled, transitions from an alarm state to the normal state will generate an SNMP trap or TL1 message.
1.3.6.1.4.1.539.28.1.1.6ColumnaislcainHighAlarmSeverityread-writecurrentSeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
1.3.6.1.4.1.539.28.1.1.7ColumnaislcainHighAlarmStateTextread-writecurrentTextual description of the point's alarm state. Maximum length is 80 characters.
1.3.6.1.4.1.539.28.1.1.8ColumnaislcainLowAlarmSeverityread-writecurrentSeverity of the point's alarm state, or notReported(5) if the point does not generate an alarm.
1.3.6.1.4.1.539.28.1.1.9ColumnaislcainLowAlarmStateTextread-writecurrentTextual description of the point's alarm state. Maximum length is 80 characters.
1.3.6.1.4.1.539.28.1.1.10ColumnaislcainNormalStateTextread-writecurrentTextual description of the point's normal state. Maximum length is 80 characters.
1.3.6.1.4.1.539.28.1.1.11ColumnaislcainUserUnitsread-writecurrentThe user-defined units for this input (e.g. degC, degF, etc.).
1.3.6.1.4.1.539.28.1.1.12ColumnaislcainMinInputmAread-writecurrentThe current in mA corresponding to the minimum input in user-defined units.
1.3.6.1.4.1.539.28.1.1.13ColumnaislcainMinInputuuread-writecurrentThe minimum value in user-defined units corresponding to the minimum input in mA.
1.3.6.1.4.1.539.28.1.1.14ColumnaislcainMaxInputmAread-writecurrentThe current in mA corresponding to the maximum input in user-defined units.
1.3.6.1.4.1.539.28.1.1.15ColumnaislcainMaxInputuuread-writecurrentThe maximum value in user-defined units corresponding to the maximum input in mA.
1.3.6.1.4.1.539.28.1.1.16ColumnaislcainHighLimitScanread-writecurrentIf enabled, the high limit threshold will be checked when the input is scanned.
1.3.6.1.4.1.539.28.1.1.17ColumnaislcainHighAlarmThresholduuread-writecurrentThe high alarm level in user-defined units.
1.3.6.1.4.1.539.28.1.1.18ColumnaislcainHighAlarmThresholdIntervaluuread-writecurrentThe high alarm level threshold interval in user-defined units. When the high alarm is active, each time the input rises another interval higher, a new alarm is…
1.3.6.1.4.1.539.28.1.1.19ColumnaislcainHighAlarmMinPeriodread-writecurrentThe minimum number of seconds the input(s) should be energized when the input exceeds the high alarm threshold.
1.3.6.1.4.1.539.28.1.1.20ColumnaislcainHighAlarmHysteresisuuread-writecurrentThe amount by which the input must drop below the High Alarm Threshold before the High Alarm will be cleared.
1.3.6.1.4.1.539.28.1.1.21ColumnaislcainLowLimitScanread-writecurrentIf enabled, the low limit threshold will be checked when the input is scanned.
1.3.6.1.4.1.539.28.1.1.22ColumnaislcainLowAlarmThresholduuread-writecurrentThe low alarm level in user-defined units.
1.3.6.1.4.1.539.28.1.1.23ColumnaislcainLowAlarmThresholdIntervaluuread-writecurrentThe low alarm level threshold interval in user-defined units. When the low alarm is active, each time the input drops another interval lower, a new alarm is se…
1.3.6.1.4.1.539.28.1.1.24ColumnaislcainLowAlarmMinPeriodread-writecurrentThe minimum number of seconds the input(s) should be energized when the input falls below the low alarm threshold.
1.3.6.1.4.1.539.28.1.1.25ColumnaislcainLowAlarmHysteresisuuread-writecurrentThe amount by which the input must rise above the Low Alarm Threshold before the Low Alarm will be cleared.
1.3.6.1.4.1.539.28.1.1.26ColumnaislcainCurrentValueuuread-onlycurrentThe current input value in user-defined units.
1.3.6.1.4.1.539.28.1.1.27ColumnaislcainCurrentValuemAread-onlycurrentThe current input value in mA.
1.3.6.1.4.1.539.28.1.1.28ColumnaislcainLastChangeTimeread-onlycurrentTextural representation of the time of the most recent output change. 24-hour format YYYY-MM-DD HH:MM:SS.
1.3.6.1.4.1.539.28.1.1.29Columnaislcaintl1AccessIDread-writecurrentUnique TL1 access identifier for this point. Maximum length is 22 characters.
1.3.6.1.4.1.539.28.1.1.30Columnaislcaintl1Provisionedread-writecurrentEnable TL1 management of this point.
1.3.6.1.4.1.539.28.1.1.31Columnaislcaintl1AccessIDTyperead-writecurrentIdentifies the point as either an equipment(1) alarm condition or an environmental(2) alarm.
1.3.6.1.4.1.539.28.1.1.32Columnaislcaintl1HighAlarmTyperead-writecurrentString indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.
1.3.6.1.4.1.539.28.1.1.33Columnaislcaintl1HighAlarmMessageread-writecurrentTextual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.
1.3.6.1.4.1.539.28.1.1.34Columnaislcaintl1LowAlarmTyperead-writecurrentString indicating the type of alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 10 characters.
1.3.6.1.4.1.539.28.1.1.35Columnaislcaintl1LowAlarmMessageread-writecurrentTextual description of the alarm, used only when aislcaintl1AccessIDType is environmental(2). Maximum length is 40 characters.
1.3.6.1.4.1.539.28.1.1.36Columnaislcaintl1HighAlarmNotificationCoderead-writecurrentSeverity of the point's alarm state.
1.3.6.1.4.1.539.28.1.1.37Columnaislcaintl1HighAlarmServiceAffectingread-writecurrentIndicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).
1.3.6.1.4.1.539.28.1.1.38Columnaislcaintl1HighAlarmConditionTyperead-writecurrentString indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.
1.3.6.1.4.1.539.28.1.1.39Columnaislcaintl1HighAlarmConditionDescread-writecurrentTextual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.
1.3.6.1.4.1.539.28.1.1.40Columnaislcaintl1LowAlarmNotificationCoderead-writecurrentSeverity of the point's alarm state.
1.3.6.1.4.1.539.28.1.1.41Columnaislcaintl1LowAlarmServiceAffectingread-writecurrentIndicates whether or not the alarm affects the functioning of the equipment. This is only meaningful when aislcaintl1AccessIDType is equipment(1).
1.3.6.1.4.1.539.28.1.1.42Columnaislcaintl1LowAlarmConditionTyperead-writecurrentString indicating the type of alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 20 characters.
1.3.6.1.4.1.539.28.1.1.43Columnaislcaintl1LowAlarmConditionDescread-writecurrentTextual description of the alarm condition, used only when aislcaintl1AccessIDType is equipment(1). Maximum length is 64 characters.
1.3.6.1.4.1.539.28.1.1.44ColumnaislcainAnalogStatusread-onlycurrentThe current alarm status of the analog input.
1.3.6.1.4.1.539.28.1.1.45ColumnaislcainCurrentStateTextread-onlycurrentTextual description of the point's current state. This is either aislcainNormalStateText or aislcainAlarmStateText.
1.3.6.1.4.1.539.28.1.1.46ColumnaislcainAnalogAlarmStateread-onlycurrentThe point's current alarm state, or normal(5).
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerINTEGER (0..2147483647)
PositiveIntegerINTEGER (1..2147483647)