CAREL-RITTAL-LCP-3311-MIB

63 objects
Custom MIB for Rittal LCP 3311 chillers connected to a pco web card
Imported Objects
SNMPv2-CONFOBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
SNMPv2-TCTEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.9839IdentitycarelCustom MIB for Rittal LCP 3311 chillers connected to a pco web card
1.3.6.1.4.1.9839.2606Noderittal
1.3.6.1.4.1.9839.2606.2NoderittalLCP3311
1.3.6.1.4.1.9839.2606.2.1Nodesensors
1.3.6.1.4.1.9839.2606.2.1.1Nodedigital
1.3.6.1.4.1.9839.2606.2.1.1.2ScalarcompressorOverloadAlarmread-onlycurrentCompressor overload alarm ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.3ScalarhighPressureAlarmread-onlycurrentHigh pressure alarm ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.8ScalarremoteOnOffread-onlycurrentRemote On/Off off (0), on (1)
1.3.6.1.4.1.9839.2606.2.1.1.11ScalarinverterAlarmread-onlycurrentInverter alarm ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.12ScalardriveAlarmread-onlycurrentPower+ drive off-line alarm ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.17ScalarinverterOnOffread-onlycurrentInverter On/Off off (0), on (1)
1.3.6.1.4.1.9839.2606.2.1.1.23ScalargeneralAlarmread-onlycurrentGeneral alarm alarm (0), ok (1)
1.3.6.1.4.1.9839.2606.2.1.1.29ScalarresetAllAlarmsread-writecurrentReset all alarms no (0), yes (1)
1.3.6.1.4.1.9839.2606.2.1.1.30ScalarcompressorEnvelopeAlarmread-onlycurrentCompressor forced off working out envelope ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.31ScalarcompressorStartupFailureAlarmread-onlycurrentCompressor startup failure alarm, reached max retries ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.33ScalarmaxDischargeTemperatureAlarmread-onlycurrentMaximum discharge temperature has been reached ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.35ScalarcompressorDeltaPressureAlarmread-onlycurrentDelta pressure too big to startup compressor ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.36ScalaroilReturnAlarmread-onlycurrentOil return alarm for when the compressor is running. Lubrication issue. ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.38ScalaroutputTemperatureTopProbeAlarmread-onlycurrentTop output temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.39ScalaroutputTemperatureMidProbeAlarmread-onlycurrentMid output temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.40ScalaroutputTemperatureBottomProbeAlarmread-onlycurrentBottom output temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.42ScalarinputTemperatureTopProbeAlarmread-onlycurrentTop input temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.43ScalarinputTemperatureMidProbeAlarmread-onlycurrentMid input temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.44ScalarinputTemperatureBottomProbeAlarmread-onlycurrentBottom input temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.45ScalarcompressorDischargeTemperatureProbeAlarmread-onlycurrentCompressor discharge temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.46ScalarcompressorSuctionTemperatureProbeAlarmread-onlycurrentCompressor suction temperature probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.47ScalarcompressorDischargePressureProbeAlarmread-onlycurrentCompressor discharge pressure probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.48ScalarcompressorSuctionPressureProbeAlarmread-onlycurrentCompressor suction pressure probe broken ok (0), alarm (1)
1.3.6.1.4.1.9839.2606.2.1.1.100Scalarrebootread-writecurrentReboot the system no (0), yes (1)
1.3.6.1.4.1.9839.2606.2.1.2Nodeanalog
1.3.6.1.4.1.9839.2606.2.1.2.2ScalaroutputTemperatureTopSensorread-onlycurrentTop sensor output temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.3ScalaroutputTemperatureMidSensorread-onlycurrentMid sensor output temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.4ScalaroutputTemperatureBottomSensorread-onlycurrentBottom sensor output temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.6ScalarinputTemperatureTopSensorread-onlycurrentTop sensor input temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.7ScalarinputTemperatureMidSensorread-onlycurrentMid sensor input temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.8ScalarinputTemperatureBottomSensorread-onlycurrentBottom sensor input temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.9ScalarcompressorDischargeTemperatureread-onlycurrentCompressor discharge temperature
1.3.6.1.4.1.9839.2606.2.1.2.10ScalarcompressorSuctionTemperatureread-onlycurrentCompressor suction temperature
1.3.6.1.4.1.9839.2606.2.1.2.11ScalarcompressorDischargePressureread-onlycurrentCompressor discharge pressure
1.3.6.1.4.1.9839.2606.2.1.2.12ScalarcompressorSuctionPressureread-onlycurrentCompressor suction pressure
1.3.6.1.4.1.9839.2606.2.1.2.13ScalarevaporatorTemperatureread-onlycurrentEvaporator temperature from Low pressure conversion
1.3.6.1.4.1.9839.2606.2.1.2.14ScalarcondensingTemperatureread-onlycurrentCondensing temperature from High pressure conversion
1.3.6.1.4.1.9839.2606.2.1.2.21ScalarinputTemperatureAverageread-onlycurrentAverage input temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.22ScalaroutputTemperatureAverageread-onlycurrentAverage output temperature in Celcius
1.3.6.1.4.1.9839.2606.2.1.2.45ScalarcompressorRotorSpeedread-onlycurrentCompressor rotor speed
1.3.6.1.4.1.9839.2606.2.1.2.46ScalarcompressorMotorCurrentread-onlycurrentCompressor motor current
1.3.6.1.4.1.9839.2606.2.1.2.48ScalarlcpSetpointread-writecurrentMain LCP setpoint
1.3.6.1.4.1.9839.2606.2.1.3Nodeinteger
1.3.6.1.4.1.9839.2606.2.1.3.1ScalarcompressorRotorSpeedHzread-onlycurrentCompressor rotor speed in Hz
1.3.6.1.4.1.9839.2606.2.1.3.2ScalardriverPowerStatusread-onlycurrentDriver power status stop (1), run (2), alarm (3)
1.3.6.1.4.1.9839.2606.2.1.3.3ScalarcurrentErrorCoderead-onlycurrentCurrent error code
1.3.6.1.4.1.9839.2606.2.1.3.4ScalardriverTemperatureread-onlycurrentDriver Power+ Temperature
1.3.6.1.4.1.9839.2606.2.1.3.5ScalardcBusVoltageread-onlycurrentPower+ DC Voltage
1.3.6.1.4.1.9839.2606.2.1.3.6ScalarmotorVoltageread-onlycurrentMotor Voltage
1.3.6.1.4.1.9839.2606.2.1.3.7ScalarpowerRequestread-onlycurrentRequest of power for inverter after envelop
1.3.6.1.4.1.9839.2606.2.1.3.13ScalarunitOnOffread-writecurrentUnit on/off state off (0), on (1), energy-save (2), auto (3)
1.3.6.1.4.1.9839.2606.2.1.3.14ScalarenvelopeZoneread-onlycurrentenvelope zone ok (0), maximum compression ratio (1), maximum discharge power (2), current limit (3), maximum suction power(4), minimum compression ratio (5), m…
1.3.6.1.4.1.9839.2606.2.1.3.16ScalarcoolingCapacityread-onlycurrentActual EVD valve cooling capacity
1.3.6.1.4.1.9839.2606.2.1.3.17ScalarevdValveStepsread-onlycurrentEVD valve steps position
1.3.6.1.4.1.9839.2606.2.1.3.28ScalarfanSpeedPercentread-onlycurrentThe fan speed percentage
1.3.6.1.4.1.9839.2606.2.1.3.29ScalarfanSpeedRpmread-onlycurrentThe fan speed rpm
1.3.6.1.4.1.9839.2606.2.1.3.30ScalarevdValveOpeningread-onlycurrentActual EVD valve opening
Type Definitions
NameSyntaxStatusDescription
DivBy10Integer32currentFixed point, one decimal