CAREL-aria-MIB
140 objects
This is the MIB module for the aria device.
Imported Objects
| SNMPv2-CONF | OBJECT-GROUP |
| SNMPv2-MIB | sysContact sysLocation sysName |
| SNMPv2-SMI | enterprises MODULE-IDENTITY |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.9839 | Nodecarel | |||
| 1.3.6.1.4.1.9839.1 | Nodesystm | |||
| 1.3.6.1.4.1.9839.1.1 | ScalaragentRelease | read-only | current | Release of the Agent. |
| 1.3.6.1.4.1.9839.1.2 | ScalaragentCode | read-only | current | Code of the Agent. 1=WebGate |
| 1.3.6.1.4.1.9839.2 | Nodeinstruments | |||
| 1.3.6.1.4.1.9839.2.0 | NodewebGateInfo | |||
| 1.3.6.1.4.1.9839.2.0.1 | NodeagentParameters | |||
| 1.3.6.1.4.1.9839.2.0.1.1 | ScalarnetSize | read-write | current | Network size. It corresponds to the number of units connected to the WebGate. |
| 1.3.6.1.4.1.9839.2.0.1.2 | ScalarbaudRate | read-write | current | Baudrate of the Carel network. |
| 1.3.6.1.4.1.9839.2.0.2 | NodeunitTypeGroup | |||
| 1.3.6.1.4.1.9839.2.0.2.1 | Scalarunit1-Type | read-only | current | Type of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.3 | NodeunitCodeGroup | |||
| 1.3.6.1.4.1.9839.2.0.3.1 | Scalarunit1-Code | read-only | current | Code of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.4 | NodeunitSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.4.1 | Scalarunit1-SoftwareRelease | read-only | current | Software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.5 | NodeunitMinSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.5.1 | Scalarunit1-MinSoftwareRelease | read-only | current | Minimum software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.6 | NodeunitMaxSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.6.1 | Scalarunit1-MaxSoftwareRelease | read-only | current | Maximum software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.7 | NodeunitNoAnswerCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.7.1 | Scalarunit1-NoAnswerCounter | read-only | current | No answer counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.8 | NodeunitErrorChecksumCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.8.1 | Scalarunit1-ErrorChecksumCounter | read-only | current | Error checksum counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.9 | NodeunitTimeoutCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.9.1 | Scalarunit1-TimeoutCounter | read-only | current | Timeout counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.10 | NodeunitOnLineStatusGroup | |||
| 1.3.6.1.4.1.9839.2.0.10.1 | Scalarunit1-OnLineStatus | read-only | current | On line status of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.1 | IdentityariaMIB | This is the MIB module for the aria device. | ||
| 1.3.6.1.4.1.9839.2.1.1 | NodedigitalObjects | |||
| 1.3.6.1.4.1.9839.2.1.1.1 | Scalarid1 | read-only | current | Digital input 1. |
| 1.3.6.1.4.1.9839.2.1.1.2 | Scalarid2 | read-only | current | Digital input 2. |
| 1.3.6.1.4.1.9839.2.1.1.3 | Scalarid3 | read-only | current | Digital input 3. |
| 1.3.6.1.4.1.9839.2.1.1.4 | Scalarreset_allarmi | read-write | current | Alarm reset. |
| 1.3.6.1.4.1.9839.2.1.1.5 | Scalarreset_hardware | read-write | current | ARIA terminal reboot. |
| 1.3.6.1.4.1.9839.2.1.1.6 | Scalarforza_invio_parametri | read-write | current | Read all configuration parameters. |
| 1.3.6.1.4.1.9839.2.1.1.7 | Scalarstato_uscite_remoto | read-write | current | Uses remote output status. |
| 1.3.6.1.4.1.9839.2.1.1.8 | Scalarbuzzer | read-write | current | Buzzer command. |
| 1.3.6.1.4.1.9839.2.1.1.9 | Scalarallarme_remoto | read-only | current | Remote alarm. |
| 1.3.6.1.4.1.9839.2.1.1.10 | Scalarid1_remoto | read-write | current | Digital remote input 1. |
| 1.3.6.1.4.1.9839.2.1.1.11 | Scalarid2_remoto | read-write | current | Digital remote input 2. |
| 1.3.6.1.4.1.9839.2.1.1.12 | Scalarid3_remoto | read-write | current | Digital remote input 3. |
| 1.3.6.1.4.1.9839.2.1.1.13 | Scalarstato_regolazione | read-write | current | Clock functions. |
| 1.3.6.1.4.1.9839.2.1.1.14 | Scalarsbrinamento_manuale | read-write | current | Manual defrost. |
| 1.3.6.1.4.1.9839.2.1.1.15 | Scalarforzatura_on | read-write | current | Standby override. |
| 1.3.6.1.4.1.9839.2.1.2 | NodeanalogObjects | |||
| 1.3.6.1.4.1.9839.2.1.2.1 | Scalarsonda_b1 | read-only | current | NTC temperature probe B1. |
| 1.3.6.1.4.1.9839.2.1.2.2 | Scalarsonda_b2 | read-only | current | Temperature or humidity probe B2. |
| 1.3.6.1.4.1.9839.2.1.2.3 | Scalarsonda_b3 | read-only | current | Remote temperature probe B3. |
| 1.3.6.1.4.1.9839.2.1.2.5 | Scalarsetpoint_valigia | read-write | current | Unoccupied mode temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.6 | Scalarsetpoint_poltrona | read-write | current | Comfort mode temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.7 | Scalarsetpoint_luna | read-write | current | Night mode temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.8 | Scalardiffheat | read-write | current | Temperature regulating band. |
| 1.3.6.1.4.1.9839.2.1.2.21 | Scalarr1 | read-write | current | Swimming pool temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.23 | Scalarr8 | read-write | current | Relative setpoint for heating resistors. |
| 1.3.6.1.4.1.9839.2.1.2.25 | Scalarr12 | read-write | current | Minimum allowable temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.26 | Scalarr13 | read-write | current | Maximum allowable temperature setpoint. |
| 1.3.6.1.4.1.9839.2.1.2.30 | Scalarr9 | read-write | current | Heating resistors regulating band. |
| 1.3.6.1.4.1.9839.2.1.2.31 | Scalarr2 | read-write | current | Swimming pool temper. regulating band. |
| 1.3.6.1.4.1.9839.2.1.2.32 | Scalarr4 | read-write | current | Temperature dead band. |
| 1.3.6.1.4.1.9839.2.1.2.33 | Scalarc5 | read-only | current | Hour counter for compressor 1. |
| 1.3.6.1.4.1.9839.2.1.2.34 | Scalarc6 | read-only | current | Hour counter for compressor 2. |
| 1.3.6.1.4.1.9839.2.1.2.37 | Scalarf3 | read-only | current | Hour counter for main fan. |
| 1.3.6.1.4.1.9839.2.1.2.38 | Scalarc7 | read-write | current | Maintenance compressors hour threshold. |
| 1.3.6.1.4.1.9839.2.1.2.39 | Scalarf4 | read-write | current | Maintenance main fan hour threshold. |
| 1.3.6.1.4.1.9839.2.1.2.40 | Scalarp3 | read-write | current | High temperature alarm threshold. |
| 1.3.6.1.4.1.9839.2.1.2.41 | Scalarp4 | read-write | current | Low temperature alarm threshold. |
| 1.3.6.1.4.1.9839.2.1.2.44 | Scalard3 | read-write | current | Defrost start temperature. |
| 1.3.6.1.4.1.9839.2.1.2.45 | Scalard4 | read-write | current | Defrost stop temperature. |
| 1.3.6.1.4.1.9839.2.1.2.46 | Scalard11 | read-write | current | Forced defrost start temperature. |
| 1.3.6.1.4.1.9839.2.1.2.51 | Scalarr28 | read-write | current | Freecooling/heating proportional band. |
| 1.3.6.1.4.1.9839.2.1.2.52 | Scalarr29 | read-write | current | Compressor disable temp. hysteresis. |
| 1.3.6.1.4.1.9839.2.1.2.53 | Scalarr23 | read-write | current | Positive gain for setpoint compensation. |
| 1.3.6.1.4.1.9839.2.1.2.54 | Scalarr24 | read-write | current | Negative gain for setpoint compensation. |
| 1.3.6.1.4.1.9839.2.1.2.55 | Scalarr25 | read-write | current | Lower setpoint compensation limit. |
| 1.3.6.1.4.1.9839.2.1.2.56 | Scalarr26 | read-write | current | Upper setpoint compensation limit. |
| 1.3.6.1.4.1.9839.2.1.2.57 | Scalars2 | read-write | current | Minimum B2 reading. |
| 1.3.6.1.4.1.9839.2.1.2.58 | Scalars3 | read-write | current | Maximum B2 reading. |
| 1.3.6.1.4.1.9839.2.1.2.59 | Scalars4 | read-write | current | B1 fixed offset. |
| 1.3.6.1.4.1.9839.2.1.2.60 | Scalars5 | read-write | current | B2 fixed offset. |
| 1.3.6.1.4.1.9839.2.1.3 | NodeintegerObjects | |||
| 1.3.6.1.4.1.9839.2.1.3.8 | Scalarmodalita_ventole | read-write | current | Fan status. |
| 1.3.6.1.4.1.9839.2.1.3.21 | Scalars1 | read-write | current | B2 probe type selection. |
| 1.3.6.1.4.1.9839.2.1.3.22 | Scalars8 | read-write | current | Internal/external B1 probe. |
| 1.3.6.1.4.1.9839.2.1.3.23 | Scalars6 | read-write | current | B1 digital filter time constant. |
| 1.3.6.1.4.1.9839.2.1.3.24 | Scalars9 | read-write | current | B2 digital filter time constant. |
| 1.3.6.1.4.1.9839.2.1.3.25 | Scalars10 | read-write | current | B3 digital filter time constant. |
| 1.3.6.1.4.1.9839.2.1.3.26 | Scalarr19 | read-write | current | Type regulation. |
| 1.3.6.1.4.1.9839.2.1.3.27 | Scalarr20 | read-write | current | Regulation integral time. |
| 1.3.6.1.4.1.9839.2.1.3.28 | Scalarr21 | read-write | current | Regulation startup delay. |
| 1.3.6.1.4.1.9839.2.1.3.29 | Scalarh3 | read-write | current | Digital input ID1 operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.30 | Scalarh4 | read-write | current | Digital input ID2 operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.31 | Scalarh5 | read-write | current | Digital input ID3 operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.32 | Scalarp2 | read-write | current | Digital input ID3 alarm type. |
| 1.3.6.1.4.1.9839.2.1.3.33 | Scalars7 | read-write | current | Temperature �C/�F unit selection. |
| 1.3.6.1.4.1.9839.2.1.3.35 | Scalarh18 | read-write | current | Pump operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.36 | Scalarc1 | read-write | current | Minimum compressor ON time. |
| 1.3.6.1.4.1.9839.2.1.3.37 | Scalarc2 | read-write | current | Minimum compressor OFF time. |
| 1.3.6.1.4.1.9839.2.1.3.38 | Scalarc3 | read-write | current | Minimum delay for compressor restart. |
| 1.3.6.1.4.1.9839.2.1.3.39 | Scalarc4 | read-write | current | Minimum delay for second comp. start. |
| 1.3.6.1.4.1.9839.2.1.3.40 | Scalarc8 | read-write | current | Fan ON delay from heat resistor ON. |
| 1.3.6.1.4.1.9839.2.1.3.41 | Scalarf1 | read-write | current | Fan ON supplementary delay. |
| 1.3.6.1.4.1.9839.2.1.3.42 | Scalarf2 | read-write | current | Fan OFF supplementary delay. |
| 1.3.6.1.4.1.9839.2.1.3.43 | Scalarf6 | read-write | current | External fan OFF delay. |
| 1.3.6.1.4.1.9839.2.1.3.46 | Scalarf14 | read-write | current | Anti-stratification inactivity time |
| 1.3.6.1.4.1.9839.2.1.3.47 | Scalarf15 | read-write | current | Air stirring active duration. |
| 1.3.6.1.4.1.9839.2.1.3.48 | Scalarr18 | read-write | current | Compressor selection rotation enable. |
| 1.3.6.1.4.1.9839.2.1.3.49 | Scalarr10 | read-write | current | Heating resistors enable. |
| 1.3.6.1.4.1.9839.2.1.3.50 | Scalarr11 | read-write | current | Heating resistors with compressor enable. |
| 1.3.6.1.4.1.9839.2.1.3.51 | Scalarf7 | read-write | current | Condensation control operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.52 | Scalarp5 | read-write | current | High/low temper./humidity alarm delay. |
| 1.3.6.1.4.1.9839.2.1.3.53 | Scalarp9 | read-write | current | ID2 low pressure alarm delay (COOL). |
| 1.3.6.1.4.1.9839.2.1.3.54 | Scalarp10 | read-write | current | ID2 low pressure alarm delay (HEAT). |
| 1.3.6.1.4.1.9839.2.1.3.55 | Scalarp11 | read-write | current | ID2 low pressure alarm delay (defrost). |
| 1.3.6.1.4.1.9839.2.1.3.56 | Scalarp6 | read-write | current | ID3 alarm delay. |
| 1.3.6.1.4.1.9839.2.1.3.57 | Scalarh7 | read-write | current | Small LCD reading selection. |
| 1.3.6.1.4.1.9839.2.1.3.59 | Scalarh13 | read-write | current | Clock and timetable mode selection. |
| 1.3.6.1.4.1.9839.2.1.3.60 | Scalarh6 | read-write | current | Local keyboard lock. |
| 1.3.6.1.4.1.9839.2.1.3.61 | Scalarh10 | read-write | current | LCD contrast. |
| 1.3.6.1.4.1.9839.2.1.3.67 | Scalarh1 | read-write | current | Machine type selection. |
| 1.3.6.1.4.1.9839.2.1.3.68 | Scalarh2 | read-write | current | Programmable output operating mode. |
| 1.3.6.1.4.1.9839.2.1.3.70 | Scalarf5 | read-write | current | Continuous main fan operation enable. |
| 1.3.6.1.4.1.9839.2.1.3.71 | Scalard1 | read-write | current | Defrost enable. |
| 1.3.6.1.4.1.9839.2.1.3.72 | Scalard2 | read-write | current | Defrost stop mode selection. |
| 1.3.6.1.4.1.9839.2.1.3.73 | Scalard5 | read-write | current | Defrost start delay. |
| 1.3.6.1.4.1.9839.2.1.3.74 | Scalard6 | read-write | current | Defrost maximum duration. |
| 1.3.6.1.4.1.9839.2.1.3.75 | Scalard7 | read-write | current | Successive defrost start delay. |
| 1.3.6.1.4.1.9839.2.1.3.76 | Scalard8 | read-write | current | Defrost with heat resistors enable. |
| 1.3.6.1.4.1.9839.2.1.3.77 | Scalard9 | read-write | current | Compressor pause at defrost start & stop. |
| 1.3.6.1.4.1.9839.2.1.3.78 | Scalard10 | read-write | current | Compr. ON delay after valve inversion. |
| 1.3.6.1.4.1.9839.2.1.3.79 | Scalard12 | read-write | current | d7 step change for smart defrost. |
| 1.3.6.1.4.1.9839.2.1.3.80 | Scalard13 | read-write | current | Manual defrost request. |
| 1.3.6.1.4.1.9839.2.1.3.83 | Scalarr27 | read-write | current | Freecooling/heating mode selection. |
| 1.3.6.1.4.1.9839.2.1.3.84 | Scalarl4 | read-write | current | Air duct shutter total run time. |
| 1.3.6.1.4.1.9839.2.1.3.85 | Scalarh16 | read-write | current | Setpoint compensation enable. |
| 1.3.6.1.4.1.9839.2.1.3.86 | Scalarp12 | read-write | current | ID2 low pressure alarm reset mode. |
| 1.3.6.1.4.1.9839.2.1.3.87 | Scalarl1 | read-only | current | Network address. |
| 1.3.6.1.4.1.9839.2.1.3.88 | Scalarl2 | read-write | current | pLAN description address |
| 1.3.6.1.4.1.9839.2.1.3.89 | Scalarl3 | read-write | current | pLAN pages |
| 1.3.6.1.4.1.9839.2.1.3.90 | Scalarl5 | read-write | current | Remote input selection mask. |
| 1.3.6.1.4.1.9839.2.1.3.91 | Scalarr14 | read-write | current | Antifreeze enable. |