CAREL-rtop_pco-MIB
146 objects
This is the MIB module for the rtop_pco device.
Imported Objects
| SNMPv2-CONF | OBJECT-GROUP |
| SNMPv2-MIB | sysContact sysLocation sysName |
| SNMPv2-SMI | enterprises MODULE-IDENTITY |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.9839 | Nodecarel | |||
| 1.3.6.1.4.1.9839.1 | Nodesystm | |||
| 1.3.6.1.4.1.9839.1.1 | ScalaragentRelease | read-only | current | Release of the Agent. |
| 1.3.6.1.4.1.9839.1.2 | ScalaragentCode | read-only | current | Code of the Agent. 1=WebGate |
| 1.3.6.1.4.1.9839.2 | Nodeinstruments | |||
| 1.3.6.1.4.1.9839.2.0 | NodewebGateInfo | |||
| 1.3.6.1.4.1.9839.2.0.1 | NodeagentParameters | |||
| 1.3.6.1.4.1.9839.2.0.1.1 | ScalarnetSize | read-write | current | Network size. It corresponds to the number of units connected to the WebGate. |
| 1.3.6.1.4.1.9839.2.0.1.2 | ScalarbaudRate | read-write | current | Baudrate of the Carel network. |
| 1.3.6.1.4.1.9839.2.0.2 | NodeunitTypeGroup | |||
| 1.3.6.1.4.1.9839.2.0.2.1 | Scalarunit1-Type | read-only | current | Type of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.3 | NodeunitCodeGroup | |||
| 1.3.6.1.4.1.9839.2.0.3.1 | Scalarunit1-Code | read-only | current | Code of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.4 | NodeunitSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.4.1 | Scalarunit1-SoftwareRelease | read-only | current | Software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.5 | NodeunitMinSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.5.1 | Scalarunit1-MinSoftwareRelease | read-only | current | Minimum software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.6 | NodeunitMaxSoftwareReleaseGroup | |||
| 1.3.6.1.4.1.9839.2.0.6.1 | Scalarunit1-MaxSoftwareRelease | read-only | current | Maximum software release of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.7 | NodeunitNoAnswerCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.7.1 | Scalarunit1-NoAnswerCounter | read-only | current | No answer counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.8 | NodeunitErrorChecksumCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.8.1 | Scalarunit1-ErrorChecksumCounter | read-only | current | Error checksum counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.9 | NodeunitTimeoutCounterGroup | |||
| 1.3.6.1.4.1.9839.2.0.9.1 | Scalarunit1-TimeoutCounter | read-only | current | Timeout counter of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.0.10 | NodeunitOnLineStatusGroup | |||
| 1.3.6.1.4.1.9839.2.0.10.1 | Scalarunit1-OnLineStatus | read-only | current | On line status of the unit having serial address 1. |
| 1.3.6.1.4.1.9839.2.1 | Identityrtop_pcoMIB | This is the MIB module for the rtop_pco device. | ||
| 1.3.6.1.4.1.9839.2.1.1 | NodedigitalObjects | |||
| 1.3.6.1.4.1.9839.2.1.1.8 | Scalarstart_stop | read-write | current | Remote ON / OFF |
| 1.3.6.1.4.1.9839.2.1.1.15 | Scalarventilatore_p | read-only | current | Main fan |
| 1.3.6.1.4.1.9839.2.1.1.16 | Scalarcont_avv_a1 | read-only | current | Compressor 1 |
| 1.3.6.1.4.1.9839.2.1.1.17 | Scalarcont_avv_a2 | read-only | current | Compressor 2 |
| 1.3.6.1.4.1.9839.2.1.1.20 | Scalarresistenza1 | read-only | current | Heater n.1 |
| 1.3.6.1.4.1.9839.2.1.1.21 | Scalarresistenza2 | read-only | current | Heater n.2 |
| 1.3.6.1.4.1.9839.2.1.1.22 | Scalarumidifica | read-only | current | Humidification |
| 1.3.6.1.4.1.9839.2.1.1.23 | Scalarventilatore1 | read-only | current | Fan n.1 |
| 1.3.6.1.4.1.9839.2.1.1.24 | Scalarventilatore2 | read-only | current | Fan n.2 |
| 1.3.6.1.4.1.9839.2.1.1.26 | Scalarglb_al | read-only | current | General alarm |
| 1.3.6.1.4.1.9839.2.1.1.27 | Scalarmask_term1 | read-only | current | Compressor n�1 overload alarm |
| 1.3.6.1.4.1.9839.2.1.1.28 | Scalarmask_term2 | read-only | current | Compressor n�2 overload alarm |
| 1.3.6.1.4.1.9839.2.1.1.29 | Scalarmask_press_h1 | read-only | current | Alarm: high pressure pressostat circuit n�1 |
| 1.3.6.1.4.1.9839.2.1.1.30 | Scalarmask_press_h2 | read-only | current | Alarm: high pressure pressostat circuit n�2 |
| 1.3.6.1.4.1.9839.2.1.1.31 | Scalarmask_antigelo | read-only | current | Antifreeze alarm |
| 1.3.6.1.4.1.9839.2.1.1.32 | Scalarmask_q14 | read-only | current | Data acquisition failure - eeprom |
| 1.3.6.1.4.1.9839.2.1.1.33 | Scalarmask_q15 | read-only | current | Clock board faulty |
| 1.3.6.1.4.1.9839.2.1.1.34 | Scalarmask_q3 | read-only | current | Inlet air high temperature alarm |
| 1.3.6.1.4.1.9839.2.1.1.35 | Scalarmask_q4 | read-only | current | Inlet air low temperature alarm |
| 1.3.6.1.4.1.9839.2.1.1.36 | Scalarmask_q5 | read-only | current | Maintenance compressor n�1 |
| 1.3.6.1.4.1.9839.2.1.1.37 | Scalarmask_q6 | read-only | current | Maintenance compressor n�2 |
| 1.3.6.1.4.1.9839.2.1.1.38 | Scalarbassa_press1 | read-only | current | Alarm: low pressure pressostat circuit n�1 |
| 1.3.6.1.4.1.9839.2.1.1.39 | Scalarbassa_press2 | read-only | current | Alarm: low pressure pressostat circuit n�2 |
| 1.3.6.1.4.1.9839.2.1.1.40 | Scalarmask_interbl | read-only | current | Generic lock alarm |
| 1.3.6.1.4.1.9839.2.1.1.41 | Scalarmask_defrost1 | read-only | current | Circuit n�1 defrost probe alarm |
| 1.3.6.1.4.1.9839.2.1.1.42 | Scalarmask_defrost2 | read-only | current | Circuit n�2 defrost probe alarm |
| 1.3.6.1.4.1.9839.2.1.1.43 | Scalarmask_filtro | read-only | current | Clogged filter alarm |
| 1.3.6.1.4.1.9839.2.1.1.44 | Scalarmask_term_res | read-only | current | Heaters overload alarm |
| 1.3.6.1.4.1.9839.2.1.1.45 | Scalaren_pompacalore | read-write | current | Enabling of functioning as heatpump |
| 1.3.6.1.4.1.9839.2.1.1.46 | Scalaren_orologio | read-write | current | Enabling of clock board |
| 1.3.6.1.4.1.9839.2.1.1.47 | Scalaren_umidita | read-write | current | Enabling of humidity function |
| 1.3.6.1.4.1.9839.2.1.1.48 | Scalaren_mandata | read-write | current | Enabling of outlet air temperature probe |
| 1.3.6.1.4.1.9839.2.1.1.50 | Scalaren_supervisore | read-write | current | Enabling of supervisory serial board |
| 1.3.6.1.4.1.9839.2.1.1.51 | Scalaren_stampante | read-write | current | Enabling of printer |
| 1.3.6.1.4.1.9839.2.1.1.52 | Scalaren_freecool | read-write | current | Enabling of summer freecooling |
| 1.3.6.1.4.1.9839.2.1.1.53 | Scalaren_freeheat | read-write | current | Enabling of winter freeheating |
| 1.3.6.1.4.1.9839.2.1.1.55 | Scalaren_compensazio | read-write | current | Enabling of compensation |
| 1.3.6.1.4.1.9839.2.1.1.56 | Scalaroff_ventp_defr | read-write | current | Enabling of main fan OFF during defrost |
| 1.3.6.1.4.1.9839.2.1.1.57 | Scalaren_sbrin_cont | read-write | current | Enabling of simultaneous defrost |
| 1.3.6.1.4.1.9839.2.1.1.58 | Scalarautostart | read-write | current | Enabling of automatic restart |
| 1.3.6.1.4.1.9839.2.1.1.59 | Scalaren_remoto | read-write | current | Enabling of remote ON / OFF |
| 1.3.6.1.4.1.9839.2.1.1.64 | Scalarabil_rotaz | read-write | current | Enabling of compressors rotation |
| 1.3.6.1.4.1.9839.2.1.1.65 | Scalarsys_on | read-write | current | Unit ON / OFF |
| 1.3.6.1.4.1.9839.2.1.1.74 | Scalarsyson1 | read-write | current | Visualisation machine state |
| 1.3.6.1.4.1.9839.2.1.1.75 | Scalaren_binati | read-write | current | Enabling of fans shared |
| 1.3.6.1.4.1.9839.2.1.1.76 | Scalaren_sond_text | read-write | current | Enabling of external air temperature probe |
| 1.3.6.1.4.1.9839.2.1.1.77 | Scalaren_sond_uext | read-write | current | Enabling of external humidity probe |
| 1.3.6.1.4.1.9839.2.1.1.78 | Scalaren_sond_def1 | read-write | current | Enabling of Defrost / Condens.1 probe |
| 1.3.6.1.4.1.9839.2.1.1.79 | Scalaren_sond_def2 | read-write | current | Enabling of Defrost / Condens.2 probe |
| 1.3.6.1.4.1.9839.2.1.1.86 | Scalartipo_cont | read-write | current | Control type: Temp or Enthalpy |
| 1.3.6.1.4.1.9839.2.1.2 | NodeanalogObjects | |||
| 1.3.6.1.4.1.9839.2.1.2.1 | Scalartemp_aria_amb | read-only | current | Recirculated air temperature |
| 1.3.6.1.4.1.9839.2.1.2.2 | Scalartemp_aria_est | read-only | current | External air temperature |
| 1.3.6.1.4.1.9839.2.1.2.5 | Scalarumid_ambiente | read-only | current | Recirculated air relative humidity |
| 1.3.6.1.4.1.9839.2.1.2.6 | Scalarumid_esterna | read-only | current | External air relative humidity |
| 1.3.6.1.4.1.9839.2.1.2.15 | Scalarset_temp_ariae | read-write | current | Summer Temp. Setpoint |
| 1.3.6.1.4.1.9839.2.1.2.16 | Scalarset_temp_ariai | read-write | current | Winter Temp. Setpoint |
| 1.3.6.1.4.1.9839.2.1.2.17 | Scalarset_umid_est | read-write | current | Summer Humid.Setpoint |
| 1.3.6.1.4.1.9839.2.1.2.18 | Scalarset_umid_inv | read-write | current | Winter Humid.Setpoint |
| 1.3.6.1.4.1.9839.2.1.2.19 | Scalarlim_sup_temp | read-write | current | Temperature set-point selection higher limit |
| 1.3.6.1.4.1.9839.2.1.2.20 | Scalarlim_inf_temp | read-write | current | Temperature set-point selection lower limit |
| 1.3.6.1.4.1.9839.2.1.2.21 | Scalarbanda_temp_e | read-write | current | Summer temperature differential |
| 1.3.6.1.4.1.9839.2.1.2.22 | Scalarbanda_temp_i | read-write | current | Winter temperature differential |
| 1.3.6.1.4.1.9839.2.1.2.23 | Scalarlim_sup_umid | read-write | current | Humidity set point selection higher limit |
| 1.3.6.1.4.1.9839.2.1.2.24 | Scalarlim_inf_umid | read-write | current | Humidity set point selection lower limit |
| 1.3.6.1.4.1.9839.2.1.2.25 | Scalardiff_umid_e | read-write | current | Summer humidity differential |
| 1.3.6.1.4.1.9839.2.1.2.26 | Scalardiff_umid_i | read-write | current | Winter humidity differential |
| 1.3.6.1.4.1.9839.2.1.2.28 | Scalaroffset_fcool | read-write | current | Summer freecooling valve: Offset |
| 1.3.6.1.4.1.9839.2.1.2.29 | Scalardiff_fcool | read-write | current | Summer freecooling valve: Differential |
| 1.3.6.1.4.1.9839.2.1.2.30 | Scalaroffset_fheat | read-write | current | Winter freecooling valve: Offset |
| 1.3.6.1.4.1.9839.2.1.2.31 | Scalardiff_fheat | read-write | current | Winter freecooling valve: Differential |
| 1.3.6.1.4.1.9839.2.1.2.32 | Scalarset_mandata | read-write | current | Minimun outlet air temperature control set-point |
| 1.3.6.1.4.1.9839.2.1.2.33 | Scalarban_mandata | read-write | current | Minimun outlet air temperature control differential |
| 1.3.6.1.4.1.9839.2.1.2.34 | Scalarset_esterno | read-write | current | Summer compensation control set-point |
| 1.3.6.1.4.1.9839.2.1.2.35 | Scalardiff_esterno_e | read-write | current | Summer compensation control differential |
| 1.3.6.1.4.1.9839.2.1.2.36 | Scalarmax_comp_e | read-write | current | Maximun summer compensation |
| 1.3.6.1.4.1.9839.2.1.2.37 | Scalarset_min | read-write | current | Defrost starting Set |
| 1.3.6.1.4.1.9839.2.1.2.38 | Scalarset_stop | read-write | current | Defrost stop Set |
| 1.3.6.1.4.1.9839.2.1.2.39 | Scalarzona_morta | read-write | current | Temperature regulation dead zone |
| 1.3.6.1.4.1.9839.2.1.2.40 | Scalarzona_morta_u | read-write | current | Humidity regulation dead zone |
| 1.3.6.1.4.1.9839.2.1.2.41 | Scalarsg_alta_in_e | read-write | current | Summer recirculated air temperature high threshold |
| 1.3.6.1.4.1.9839.2.1.2.42 | Scalarsg_bassa_in_e | read-write | current | Summer recirculated air temperature low threshold |
| 1.3.6.1.4.1.9839.2.1.2.43 | Scalarsg_alta_in_i | read-write | current | Winter recirculated air temperature high threshold |
| 1.3.6.1.4.1.9839.2.1.2.44 | Scalarsg_bassa_in_i | read-write | current | Winter recirculated air temperature low threshold |
| 1.3.6.1.4.1.9839.2.1.2.48 | Scalartar_defrost1 | read-write | current | Defrost 1 temperature calibration |
| 1.3.6.1.4.1.9839.2.1.2.49 | Scalartar_defrost2 | read-write | current | Defrost 2 temperature calibration |
| 1.3.6.1.4.1.9839.2.1.2.52 | Scalaroffset_res | read-write | current | Heaters regulation Offset |
| 1.3.6.1.4.1.9839.2.1.2.53 | Scalardiffer_res | read-write | current | Heaters regulation differential |
| 1.3.6.1.4.1.9839.2.1.2.54 | Scalartar_umid_amb | read-write | current | Recirculated air humidity calibration |
| 1.3.6.1.4.1.9839.2.1.2.62 | Scalaroffset_valv | read-write | current | Heating valve Offset |
| 1.3.6.1.4.1.9839.2.1.2.63 | Scalardiff_valv | read-write | current | Heating valve differential |
| 1.3.6.1.4.1.9839.2.1.2.64 | Scalarset_esternoi | read-write | current | External temperature set-point for Winter compensation |
| 1.3.6.1.4.1.9839.2.1.2.66 | Scalarmax_comp_i | read-write | current | Maximun Winter compensation |
| 1.3.6.1.4.1.9839.2.1.2.67 | Scalarset_vent1 | read-write | current | Set-point fan 1: condensing control |
| 1.3.6.1.4.1.9839.2.1.2.68 | Scalarset_vent2 | read-write | current | Set-point fan 2: condensing control |
| 1.3.6.1.4.1.9839.2.1.2.69 | Scalardiff_vent1 | read-write | current | Diferential fan 1: condensing control |
| 1.3.6.1.4.1.9839.2.1.2.70 | Scalardiff_vent2 | read-write | current | Diferential fan 2: condensing control |
| 1.3.6.1.4.1.9839.2.1.3 | NodeintegerObjects | |||
| 1.3.6.1.4.1.9839.2.1.3.10 | Scalarore_comp1 | read-write | current | Working hours compressorn.1 |
| 1.3.6.1.4.1.9839.2.1.3.11 | Scalarore_comp2 | read-write | current | Working hours compressorn.2 |
| 1.3.6.1.4.1.9839.2.1.3.19 | Scalarrit_all_ht_in | read-write | current | Recirculated air High / Low temperature alarm delay |
| 1.3.6.1.4.1.9839.2.1.3.20 | Scalarrit_all_press | read-write | current | Low pressure alarm delay |
| 1.3.6.1.4.1.9839.2.1.3.23 | Scalarn_comp_deum | read-write | current | Number of dehumidifying compessor |
| 1.3.6.1.4.1.9839.2.1.3.24 | Scalarrit_stop_ventp | read-write | current | Main fan OFF delay |
| 1.3.6.1.4.1.9839.2.1.3.25 | Scalarrit_part_comp | read-write | current | Compressor start-up delay |
| 1.3.6.1.4.1.9839.2.1.3.26 | Scalarrit_interbl | read-write | current | Interblock alarm delay time |
| 1.3.6.1.4.1.9839.2.1.3.27 | Scalarmin_sp_comp | read-write | current | Minimun compressor OFF time |
| 1.3.6.1.4.1.9839.2.1.3.28 | Scalarnew_pass_ut | read-write | current | New user password |
| 1.3.6.1.4.1.9839.2.1.3.30 | Scalarnew_pass_cos | read-write | current | New manifacturer password |
| 1.3.6.1.4.1.9839.2.1.3.31 | Scalarmin_stes_comp | read-write | current | Minimun time between 2 atart-ups of same compressor |
| 1.3.6.1.4.1.9839.2.1.3.32 | Scalarmin_tra_comp | read-write | current | Minimun time between 2 atart-ups of different compressor |
| 1.3.6.1.4.1.9839.2.1.3.33 | Scalarmin_acc_comp | read-write | current | Minimun compressor ON time |
| 1.3.6.1.4.1.9839.2.1.3.35 | Scalartempo_max | read-write | current | Maximun duration of defrost |
| 1.3.6.1.4.1.9839.2.1.3.36 | Scalarmin_apertura | read-write | current | Minimun opening per cent of damper |
| 1.3.6.1.4.1.9839.2.1.3.37 | Scalarsgl_macchina | read-write | current | Machine working hours alarm threshold |
| 1.3.6.1.4.1.9839.2.1.3.41 | Scalarn_res | read-write | current | Number of heaters |
| 1.3.6.1.4.1.9839.2.1.3.42 | Scalartempo_integra | read-write | current | Integration time for Prop.+ Integr. regulation |