CAREL-rtop_pco-MIB

146 objects
This is the MIB module for the rtop_pco device.
OIDNameAccessStatusDescription
1.3.6.1.4.1.9839Nodecarel
1.3.6.1.4.1.9839.1Nodesystm
1.3.6.1.4.1.9839.1.1ScalaragentReleaseread-onlycurrentRelease of the Agent.
1.3.6.1.4.1.9839.1.2ScalaragentCoderead-onlycurrentCode of the Agent. 1=WebGate
1.3.6.1.4.1.9839.2Nodeinstruments
1.3.6.1.4.1.9839.2.0NodewebGateInfo
1.3.6.1.4.1.9839.2.0.1NodeagentParameters
1.3.6.1.4.1.9839.2.0.1.1ScalarnetSizeread-writecurrentNetwork size. It corresponds to the number of units connected to the WebGate.
1.3.6.1.4.1.9839.2.0.1.2ScalarbaudRateread-writecurrentBaudrate of the Carel network.
1.3.6.1.4.1.9839.2.0.2NodeunitTypeGroup
1.3.6.1.4.1.9839.2.0.2.1Scalarunit1-Typeread-onlycurrentType of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.3NodeunitCodeGroup
1.3.6.1.4.1.9839.2.0.3.1Scalarunit1-Coderead-onlycurrentCode of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.4NodeunitSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.4.1Scalarunit1-SoftwareReleaseread-onlycurrentSoftware release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.5NodeunitMinSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.5.1Scalarunit1-MinSoftwareReleaseread-onlycurrentMinimum software release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.6NodeunitMaxSoftwareReleaseGroup
1.3.6.1.4.1.9839.2.0.6.1Scalarunit1-MaxSoftwareReleaseread-onlycurrentMaximum software release of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.7NodeunitNoAnswerCounterGroup
1.3.6.1.4.1.9839.2.0.7.1Scalarunit1-NoAnswerCounterread-onlycurrentNo answer counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.8NodeunitErrorChecksumCounterGroup
1.3.6.1.4.1.9839.2.0.8.1Scalarunit1-ErrorChecksumCounterread-onlycurrentError checksum counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.9NodeunitTimeoutCounterGroup
1.3.6.1.4.1.9839.2.0.9.1Scalarunit1-TimeoutCounterread-onlycurrentTimeout counter of the unit having serial address 1.
1.3.6.1.4.1.9839.2.0.10NodeunitOnLineStatusGroup
1.3.6.1.4.1.9839.2.0.10.1Scalarunit1-OnLineStatusread-onlycurrentOn line status of the unit having serial address 1.
1.3.6.1.4.1.9839.2.1Identityrtop_pcoMIBThis is the MIB module for the rtop_pco device.
1.3.6.1.4.1.9839.2.1.1NodedigitalObjects
1.3.6.1.4.1.9839.2.1.1.8Scalarstart_stopread-writecurrentRemote ON / OFF
1.3.6.1.4.1.9839.2.1.1.15Scalarventilatore_pread-onlycurrentMain fan
1.3.6.1.4.1.9839.2.1.1.16Scalarcont_avv_a1read-onlycurrentCompressor 1
1.3.6.1.4.1.9839.2.1.1.17Scalarcont_avv_a2read-onlycurrentCompressor 2
1.3.6.1.4.1.9839.2.1.1.20Scalarresistenza1read-onlycurrentHeater n.1
1.3.6.1.4.1.9839.2.1.1.21Scalarresistenza2read-onlycurrentHeater n.2
1.3.6.1.4.1.9839.2.1.1.22Scalarumidificaread-onlycurrentHumidification
1.3.6.1.4.1.9839.2.1.1.23Scalarventilatore1read-onlycurrentFan n.1
1.3.6.1.4.1.9839.2.1.1.24Scalarventilatore2read-onlycurrentFan n.2
1.3.6.1.4.1.9839.2.1.1.26Scalarglb_alread-onlycurrentGeneral alarm
1.3.6.1.4.1.9839.2.1.1.27Scalarmask_term1read-onlycurrentCompressor n�1 overload alarm
1.3.6.1.4.1.9839.2.1.1.28Scalarmask_term2read-onlycurrentCompressor n�2 overload alarm
1.3.6.1.4.1.9839.2.1.1.29Scalarmask_press_h1read-onlycurrentAlarm: high pressure pressostat circuit n�1
1.3.6.1.4.1.9839.2.1.1.30Scalarmask_press_h2read-onlycurrentAlarm: high pressure pressostat circuit n�2
1.3.6.1.4.1.9839.2.1.1.31Scalarmask_antigeloread-onlycurrentAntifreeze alarm
1.3.6.1.4.1.9839.2.1.1.32Scalarmask_q14read-onlycurrentData acquisition failure - eeprom
1.3.6.1.4.1.9839.2.1.1.33Scalarmask_q15read-onlycurrentClock board faulty
1.3.6.1.4.1.9839.2.1.1.34Scalarmask_q3read-onlycurrentInlet air high temperature alarm
1.3.6.1.4.1.9839.2.1.1.35Scalarmask_q4read-onlycurrentInlet air low temperature alarm
1.3.6.1.4.1.9839.2.1.1.36Scalarmask_q5read-onlycurrentMaintenance compressor n�1
1.3.6.1.4.1.9839.2.1.1.37Scalarmask_q6read-onlycurrentMaintenance compressor n�2
1.3.6.1.4.1.9839.2.1.1.38Scalarbassa_press1read-onlycurrentAlarm: low pressure pressostat circuit n�1
1.3.6.1.4.1.9839.2.1.1.39Scalarbassa_press2read-onlycurrentAlarm: low pressure pressostat circuit n�2
1.3.6.1.4.1.9839.2.1.1.40Scalarmask_interblread-onlycurrentGeneric lock alarm
1.3.6.1.4.1.9839.2.1.1.41Scalarmask_defrost1read-onlycurrentCircuit n�1 defrost probe alarm
1.3.6.1.4.1.9839.2.1.1.42Scalarmask_defrost2read-onlycurrentCircuit n�2 defrost probe alarm
1.3.6.1.4.1.9839.2.1.1.43Scalarmask_filtroread-onlycurrentClogged filter alarm
1.3.6.1.4.1.9839.2.1.1.44Scalarmask_term_resread-onlycurrentHeaters overload alarm
1.3.6.1.4.1.9839.2.1.1.45Scalaren_pompacaloreread-writecurrentEnabling of functioning as heatpump
1.3.6.1.4.1.9839.2.1.1.46Scalaren_orologioread-writecurrentEnabling of clock board
1.3.6.1.4.1.9839.2.1.1.47Scalaren_umiditaread-writecurrentEnabling of humidity function
1.3.6.1.4.1.9839.2.1.1.48Scalaren_mandataread-writecurrentEnabling of outlet air temperature probe
1.3.6.1.4.1.9839.2.1.1.50Scalaren_supervisoreread-writecurrentEnabling of supervisory serial board
1.3.6.1.4.1.9839.2.1.1.51Scalaren_stampanteread-writecurrentEnabling of printer
1.3.6.1.4.1.9839.2.1.1.52Scalaren_freecoolread-writecurrentEnabling of summer freecooling
1.3.6.1.4.1.9839.2.1.1.53Scalaren_freeheatread-writecurrentEnabling of winter freeheating
1.3.6.1.4.1.9839.2.1.1.55Scalaren_compensazioread-writecurrentEnabling of compensation
1.3.6.1.4.1.9839.2.1.1.56Scalaroff_ventp_defrread-writecurrentEnabling of main fan OFF during defrost
1.3.6.1.4.1.9839.2.1.1.57Scalaren_sbrin_contread-writecurrentEnabling of simultaneous defrost
1.3.6.1.4.1.9839.2.1.1.58Scalarautostartread-writecurrentEnabling of automatic restart
1.3.6.1.4.1.9839.2.1.1.59Scalaren_remotoread-writecurrentEnabling of remote ON / OFF
1.3.6.1.4.1.9839.2.1.1.64Scalarabil_rotazread-writecurrentEnabling of compressors rotation
1.3.6.1.4.1.9839.2.1.1.65Scalarsys_onread-writecurrentUnit ON / OFF
1.3.6.1.4.1.9839.2.1.1.74Scalarsyson1read-writecurrentVisualisation machine state
1.3.6.1.4.1.9839.2.1.1.75Scalaren_binatiread-writecurrentEnabling of fans shared
1.3.6.1.4.1.9839.2.1.1.76Scalaren_sond_textread-writecurrentEnabling of external air temperature probe
1.3.6.1.4.1.9839.2.1.1.77Scalaren_sond_uextread-writecurrentEnabling of external humidity probe
1.3.6.1.4.1.9839.2.1.1.78Scalaren_sond_def1read-writecurrentEnabling of Defrost / Condens.1 probe
1.3.6.1.4.1.9839.2.1.1.79Scalaren_sond_def2read-writecurrentEnabling of Defrost / Condens.2 probe
1.3.6.1.4.1.9839.2.1.1.86Scalartipo_contread-writecurrentControl type: Temp or Enthalpy
1.3.6.1.4.1.9839.2.1.2NodeanalogObjects
1.3.6.1.4.1.9839.2.1.2.1Scalartemp_aria_ambread-onlycurrentRecirculated air temperature
1.3.6.1.4.1.9839.2.1.2.2Scalartemp_aria_estread-onlycurrentExternal air temperature
1.3.6.1.4.1.9839.2.1.2.5Scalarumid_ambienteread-onlycurrentRecirculated air relative humidity
1.3.6.1.4.1.9839.2.1.2.6Scalarumid_esternaread-onlycurrentExternal air relative humidity
1.3.6.1.4.1.9839.2.1.2.15Scalarset_temp_ariaeread-writecurrentSummer Temp. Setpoint
1.3.6.1.4.1.9839.2.1.2.16Scalarset_temp_ariairead-writecurrentWinter Temp. Setpoint
1.3.6.1.4.1.9839.2.1.2.17Scalarset_umid_estread-writecurrentSummer Humid.Setpoint
1.3.6.1.4.1.9839.2.1.2.18Scalarset_umid_invread-writecurrentWinter Humid.Setpoint
1.3.6.1.4.1.9839.2.1.2.19Scalarlim_sup_tempread-writecurrentTemperature set-point selection higher limit
1.3.6.1.4.1.9839.2.1.2.20Scalarlim_inf_tempread-writecurrentTemperature set-point selection lower limit
1.3.6.1.4.1.9839.2.1.2.21Scalarbanda_temp_eread-writecurrentSummer temperature differential
1.3.6.1.4.1.9839.2.1.2.22Scalarbanda_temp_iread-writecurrentWinter temperature differential
1.3.6.1.4.1.9839.2.1.2.23Scalarlim_sup_umidread-writecurrentHumidity set point selection higher limit
1.3.6.1.4.1.9839.2.1.2.24Scalarlim_inf_umidread-writecurrentHumidity set point selection lower limit
1.3.6.1.4.1.9839.2.1.2.25Scalardiff_umid_eread-writecurrentSummer humidity differential
1.3.6.1.4.1.9839.2.1.2.26Scalardiff_umid_iread-writecurrentWinter humidity differential
1.3.6.1.4.1.9839.2.1.2.28Scalaroffset_fcoolread-writecurrentSummer freecooling valve: Offset
1.3.6.1.4.1.9839.2.1.2.29Scalardiff_fcoolread-writecurrentSummer freecooling valve: Differential
1.3.6.1.4.1.9839.2.1.2.30Scalaroffset_fheatread-writecurrentWinter freecooling valve: Offset
1.3.6.1.4.1.9839.2.1.2.31Scalardiff_fheatread-writecurrentWinter freecooling valve: Differential
1.3.6.1.4.1.9839.2.1.2.32Scalarset_mandataread-writecurrentMinimun outlet air temperature control set-point
1.3.6.1.4.1.9839.2.1.2.33Scalarban_mandataread-writecurrentMinimun outlet air temperature control differential
1.3.6.1.4.1.9839.2.1.2.34Scalarset_esternoread-writecurrentSummer compensation control set-point
1.3.6.1.4.1.9839.2.1.2.35Scalardiff_esterno_eread-writecurrentSummer compensation control differential
1.3.6.1.4.1.9839.2.1.2.36Scalarmax_comp_eread-writecurrentMaximun summer compensation
1.3.6.1.4.1.9839.2.1.2.37Scalarset_minread-writecurrentDefrost starting Set
1.3.6.1.4.1.9839.2.1.2.38Scalarset_stopread-writecurrentDefrost stop Set
1.3.6.1.4.1.9839.2.1.2.39Scalarzona_mortaread-writecurrentTemperature regulation dead zone
1.3.6.1.4.1.9839.2.1.2.40Scalarzona_morta_uread-writecurrentHumidity regulation dead zone
1.3.6.1.4.1.9839.2.1.2.41Scalarsg_alta_in_eread-writecurrentSummer recirculated air temperature high threshold
1.3.6.1.4.1.9839.2.1.2.42Scalarsg_bassa_in_eread-writecurrentSummer recirculated air temperature low threshold
1.3.6.1.4.1.9839.2.1.2.43Scalarsg_alta_in_iread-writecurrentWinter recirculated air temperature high threshold
1.3.6.1.4.1.9839.2.1.2.44Scalarsg_bassa_in_iread-writecurrentWinter recirculated air temperature low threshold
1.3.6.1.4.1.9839.2.1.2.48Scalartar_defrost1read-writecurrentDefrost 1 temperature calibration
1.3.6.1.4.1.9839.2.1.2.49Scalartar_defrost2read-writecurrentDefrost 2 temperature calibration
1.3.6.1.4.1.9839.2.1.2.52Scalaroffset_resread-writecurrentHeaters regulation Offset
1.3.6.1.4.1.9839.2.1.2.53Scalardiffer_resread-writecurrentHeaters regulation differential
1.3.6.1.4.1.9839.2.1.2.54Scalartar_umid_ambread-writecurrentRecirculated air humidity calibration
1.3.6.1.4.1.9839.2.1.2.62Scalaroffset_valvread-writecurrentHeating valve Offset
1.3.6.1.4.1.9839.2.1.2.63Scalardiff_valvread-writecurrentHeating valve differential
1.3.6.1.4.1.9839.2.1.2.64Scalarset_esternoiread-writecurrentExternal temperature set-point for Winter compensation
1.3.6.1.4.1.9839.2.1.2.66Scalarmax_comp_iread-writecurrentMaximun Winter compensation
1.3.6.1.4.1.9839.2.1.2.67Scalarset_vent1read-writecurrentSet-point fan 1: condensing control
1.3.6.1.4.1.9839.2.1.2.68Scalarset_vent2read-writecurrentSet-point fan 2: condensing control
1.3.6.1.4.1.9839.2.1.2.69Scalardiff_vent1read-writecurrentDiferential fan 1: condensing control
1.3.6.1.4.1.9839.2.1.2.70Scalardiff_vent2read-writecurrentDiferential fan 2: condensing control
1.3.6.1.4.1.9839.2.1.3NodeintegerObjects
1.3.6.1.4.1.9839.2.1.3.10Scalarore_comp1read-writecurrentWorking hours compressorn.1
1.3.6.1.4.1.9839.2.1.3.11Scalarore_comp2read-writecurrentWorking hours compressorn.2
1.3.6.1.4.1.9839.2.1.3.19Scalarrit_all_ht_inread-writecurrentRecirculated air High / Low temperature alarm delay
1.3.6.1.4.1.9839.2.1.3.20Scalarrit_all_pressread-writecurrentLow pressure alarm delay
1.3.6.1.4.1.9839.2.1.3.23Scalarn_comp_deumread-writecurrentNumber of dehumidifying compessor
1.3.6.1.4.1.9839.2.1.3.24Scalarrit_stop_ventpread-writecurrentMain fan OFF delay
1.3.6.1.4.1.9839.2.1.3.25Scalarrit_part_compread-writecurrentCompressor start-up delay
1.3.6.1.4.1.9839.2.1.3.26Scalarrit_interblread-writecurrentInterblock alarm delay time
1.3.6.1.4.1.9839.2.1.3.27Scalarmin_sp_compread-writecurrentMinimun compressor OFF time
1.3.6.1.4.1.9839.2.1.3.28Scalarnew_pass_utread-writecurrentNew user password
1.3.6.1.4.1.9839.2.1.3.30Scalarnew_pass_cosread-writecurrentNew manifacturer password
1.3.6.1.4.1.9839.2.1.3.31Scalarmin_stes_compread-writecurrentMinimun time between 2 atart-ups of same compressor
1.3.6.1.4.1.9839.2.1.3.32Scalarmin_tra_compread-writecurrentMinimun time between 2 atart-ups of different compressor
1.3.6.1.4.1.9839.2.1.3.33Scalarmin_acc_compread-writecurrentMinimun compressor ON time
1.3.6.1.4.1.9839.2.1.3.35Scalartempo_maxread-writecurrentMaximun duration of defrost
1.3.6.1.4.1.9839.2.1.3.36Scalarmin_aperturaread-writecurrentMinimun opening per cent of damper
1.3.6.1.4.1.9839.2.1.3.37Scalarsgl_macchinaread-writecurrentMachine working hours alarm threshold
1.3.6.1.4.1.9839.2.1.3.41Scalarn_resread-writecurrentNumber of heaters
1.3.6.1.4.1.9839.2.1.3.42Scalartempo_integraread-writecurrentIntegration time for Prop.+ Integr. regulation