OIDNameAccessStatusDescription
1.3.6.1.4.1.232.165NodecpqPower
1.3.6.1.4.1.232.165.1NodepowerDevice
1.3.6.1.4.1.232.165.1NodetrapCriticalA critical alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.1.1NodetrapInfo
1.3.6.1.4.1.232.165.1.1.1ScalartrapCoderead-onlymandatoryA number identifying the event for the trap that was sent. Mapped unique trap code per unique event to be used by ISEE's decoder ring.
1.3.6.1.4.1.232.165.1.1.2ScalartrapDescriptionread-onlymandatoryA string identifying the event for that last trap that was sent.
1.3.6.1.4.1.232.165.1.1.3ScalartrapDeviceMgmtUrlread-onlymandatoryA string contains the URL for the management software.
1.3.6.1.4.1.232.165.1.1.4ScalartrapDeviceDetailsread-onlymandatoryA string details information about the device, including model, serial number, part number, etc....
1.3.6.1.4.1.232.165.1.1.5ScalartrapDeviceNameread-onlymandatoryA string contains the name of the device.
1.3.6.1.4.1.232.165.1.2NodemanagementModuleIdent
1.3.6.1.4.1.232.165.1.2.1ScalardeviceManufacturerread-onlymandatoryThe device manufacturer.
1.3.6.1.4.1.232.165.1.2.2ScalardeviceModelread-onlymandatoryThe device model.
1.3.6.1.4.1.232.165.1.2.3ScalardeviceFirmwareVersionread-onlymandatoryThe device firmware version(s).
1.3.6.1.4.1.232.165.1.2.4ScalardeviceHardwareVersionread-onlymandatoryThe device hardware version.
1.3.6.1.4.1.232.165.1.2.5ScalardeviceIdentNameread-writemandatoryA string identifying the device.
1.3.6.1.4.1.232.165.1.2.6ScalardevicePartNumberread-onlymandatoryThe device part number.
1.3.6.1.4.1.232.165.1.2.7ScalardeviceSerialNumberread-onlymandatoryThe device serial number.
1.3.6.1.4.1.232.165.1.2.8ScalardeviceMACAddressread-onlymandatoryThe device MAC address.
1.3.6.1.4.1.232.165.2Nodepdu
1.3.6.1.4.1.232.165.2NodetrapWarningA warning alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.2.1NodepduIdent
1.3.6.1.4.1.232.165.2.1.1ScalarnumOfPduread-onlymandatoryThe number of PDUs.
1.3.6.1.4.1.232.165.2.1.2TablepduIdentTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduIdent group.
1.3.6.1.4.1.232.165.2.1.2.1RowpduIdentEntrynot-accessiblemandatoryThe ident table entry containing the name, model, manufacturer, firmware version, part number, etc.
1.3.6.1.4.1.232.165.2.1.2.1.1ColumnpduIdentIndexread-onlymandatoryIndex for the PduIdentEntry table.
1.3.6.1.4.1.232.165.2.1.2.1.2ColumnpduNameread-writemandatoryThe string identify the device.
1.3.6.1.4.1.232.165.2.1.2.1.3ColumnpduModelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.2.1.2.1.4ColumnpduManufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.2.1.2.1.5ColumnpduFirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.2.1.2.1.6ColumnpduPartNumberread-onlymandatoryThe device part number.
1.3.6.1.4.1.232.165.2.1.2.1.7ColumnpduSerialNumberread-onlymandatoryThe deice serial number.
1.3.6.1.4.1.232.165.2.1.2.1.8ColumnpduStatusread-onlymandatoryThe overall status of the device. A value of OK(2) indicates the device is operating normally. A value of degraded(3) indicates the device is operating with wa…
1.3.6.1.4.1.232.165.2.1.2.1.9ColumnpduControllableread-onlymandatoryThis object indicates whether or not the device is controllable.
1.3.6.1.4.1.232.165.2.2NodepduInput
1.3.6.1.4.1.232.165.2.2.1TablepduInputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
1.3.6.1.4.1.232.165.2.2.1.1RowpduInputEntrynot-accessiblemandatoryThe input table entry containing the voltage and current for the PDU
1.3.6.1.4.1.232.165.2.2.1.1.1ColumnpduInputIndexread-onlymandatoryIndex for the PduInputEntry table.
1.3.6.1.4.1.232.165.2.2.1.1.2ColumninputVoltageread-onlymandatoryThe measured input voltage from the PDU meters in volts.
1.3.6.1.4.1.232.165.2.2.1.1.3ColumninputCurrentread-onlymandatoryThe measured input current from the PDU meters in amps.
1.3.6.1.4.1.232.165.2.3NodepduOutput
1.3.6.1.4.1.232.165.2.3.1TablepduOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
1.3.6.1.4.1.232.165.2.3.1.1RowpduOutputEntrynot-accessiblemandatoryThe input table entry containing the name, heat load, current load, power load, firmware, etc.
1.3.6.1.4.1.232.165.2.3.1.1.1ColumnpduOutputIndexread-onlymandatoryIndex for the PduOutputEntry table.
1.3.6.1.4.1.232.165.2.3.1.1.2ColumnpduOutputLoadread-onlymandatoryThe device output load in percent of rated capacity. A value of -1 will be returned if the heat load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.3ColumnpduOutputHeatread-onlymandatoryThe total heat load measured on the PDU in BTUs. A value of -1 will be returned if the heat load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.4ColumnpduOutputPowerread-onlymandatoryThe total power load measured on the PDU in watts. A value of -1 will be returned if the power load is unable to be measured.
1.3.6.1.4.1.232.165.2.3.1.1.5ColumnpduOutputNumBreakersread-onlymandatoryThe number of breakers for the device. This variable indicates the number of rows in the breakers table.
1.3.6.1.4.1.232.165.2.3.2TablepduOutputBreakerTablenot-accessiblemandatoryList of breaker table entries. The number of entries is given by pduOutputNumBreakers .
1.3.6.1.4.1.232.165.2.3.2.1RowpduOutputBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to an breaker.
1.3.6.1.4.1.232.165.2.3.2.1.1ColumnbreakerIndexread-onlymandatoryThe breaker identifier.
1.3.6.1.4.1.232.165.2.3.2.1.2ColumnbreakerVoltageread-onlymandatoryThe breaker voltage in volts.
1.3.6.1.4.1.232.165.2.3.2.1.3ColumnbreakerCurrentread-onlymandatoryThe breaker current draw in Amps.
1.3.6.1.4.1.232.165.2.3.2.1.4ColumnbreakerPercentLoadread-onlymandatoryThe breaker load in percent.
1.3.6.1.4.1.232.165.2.3.2.1.5ColumnbreakerStatusread-onlymandatoryThis object indicates the status of the breaker. A value of normal(1) indicates the breaker is operating normally. A value of overloadWarning(2) indicates the …
1.3.6.1.4.1.232.165.3NodetrapInformationAn informational alarm has occurred. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.3Nodeups
1.3.6.1.4.1.232.165.3.1NodeupsIdent
1.3.6.1.4.1.232.165.3.1.1ScalarupsIdentManufacturerread-onlymandatoryThe UPS Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.3.1.2ScalarupsIdentModelread-onlymandatoryThe UPS Model;Part number;Serial number (e.g. HP R5500 XR;204451-B21;B00123456W).
1.3.6.1.4.1.232.165.3.1.3ScalarupsIdentSoftwareVersionsread-onlymandatoryThe firmware revision level(s) of the UPS microcontroller(s).
1.3.6.1.4.1.232.165.3.1.4ScalarupsIdentOemCoderead-onlymandatoryA binary code indicating vendor. This should be a ?0x0c? for HP
1.3.6.1.4.1.232.165.3.2NodeupsBattery
1.3.6.1.4.1.232.165.3.2.1ScalarupsBatTimeRemainingread-onlymandatoryBattery run time in seconds before UPS turns off due to low battery.
1.3.6.1.4.1.232.165.3.2.2ScalarupsBatVoltageread-onlymandatoryBattery voltage as reported by the UPS meters.
1.3.6.1.4.1.232.165.3.2.3ScalarupsBatCurrentread-onlymandatoryBattery Current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery.
1.3.6.1.4.1.232.165.3.2.4ScalarupsBatCapacityread-onlymandatoryBattery percent charge.
1.3.6.1.4.1.232.165.3.2.5ScalarupsBatteryAbmStatusread-onlymandatoryGives the status of the Advanced Battery Management; batteryFloating(3) status means that the charger is temporarily charging the battery to its float voltage;…
1.3.6.1.4.1.232.165.3.3NodeupsInput
1.3.6.1.4.1.232.165.3.3.1ScalarupsInputFrequencyread-onlymandatoryThe utility line frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.3.2ScalarupsInputLineBadsread-onlymandatoryThe number of times the Input was out of tolerance in voltage or frequency.
1.3.6.1.4.1.232.165.3.3.3ScalarupsInputNumPhasesread-onlymandatory
1.3.6.1.4.1.232.165.3.3.4TableupsInputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
1.3.6.1.4.1.232.165.3.3.4.1RowupsInputEntrynot-accessiblemandatoryThe input table entry containing the current, voltage, etc.
1.3.6.1.4.1.232.165.3.3.4.1.1ColumnupsInputPhaseread-onlymandatoryThe number of the phase. Serves as index for input table.
1.3.6.1.4.1.232.165.3.3.4.1.2ColumnupsInputVoltageread-onlymandatoryThe measured input voltage from the UPS meters in volts.
1.3.6.1.4.1.232.165.3.3.4.1.3ColumnupsInputCurrentread-onlymandatoryThe measured input current from the UPS meters in amps.
1.3.6.1.4.1.232.165.3.3.4.1.4ColumnupsInputWattsread-onlymandatoryThe measured input real power in watts.
1.3.6.1.4.1.232.165.3.3.5ScalarupsInputSourceread-onlymandatoryThe present external source of input power. The enumeration none(2) indicates that there is no external source of power, for example, the UPS is On Battery (an…
1.3.6.1.4.1.232.165.3.4NodeupsOutput
1.3.6.1.4.1.232.165.3.4.1ScalarupsOutputLoadread-onlymandatoryThe UPS output load in percent of rated capacity.
1.3.6.1.4.1.232.165.3.4.2ScalarupsOutputFrequencyread-onlymandatoryThe measured UPS output frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.4.3ScalarupsOutputNumPhasesread-onlymandatoryThe number of metered output phases, serves as the table index.
1.3.6.1.4.1.232.165.3.4.4TableupsOutputTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
1.3.6.1.4.1.232.165.3.4.4.1RowupsOutputEntrynot-accessiblemandatoryOutput Table Entry containing voltage, current, etc.
1.3.6.1.4.1.232.165.3.4.4.1.1ColumnupsOutputPhaseread-onlymandatoryThe number {1..3} of the output phase.
1.3.6.1.4.1.232.165.3.4.4.1.2ColumnupsOutputVoltageread-onlymandatoryThe measured output voltage from the UPS metering in volts.
1.3.6.1.4.1.232.165.3.4.4.1.3ColumnupsOutputCurrentread-onlymandatoryThe measured UPS output current in amps.
1.3.6.1.4.1.232.165.3.4.4.1.4ColumnupsOutputWattsread-onlymandatoryThe measured real output power in watts.
1.3.6.1.4.1.232.165.3.4.5ScalarupsOutputSourceread-onlymandatoryThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.232.165.3.5NodeupsBypass
1.3.6.1.4.1.232.165.3.5.1ScalarupsBypassFrequencyread-onlymandatoryThe bypass frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.5.2ScalarupsBypassNumPhasesread-onlymandatoryThe number of lines in the UPS bypass table.
1.3.6.1.4.1.232.165.3.5.3TableupsBypassTablenot-accessiblemandatory
1.3.6.1.4.1.232.165.3.5.3.1RowupsBypassEntrynot-accessiblemandatoryEntry in the UpsBypassTable.
1.3.6.1.4.1.232.165.3.5.3.1.1ColumnupsBypassPhaseread-onlymandatoryThe Bypass Phase, index for the table.
1.3.6.1.4.1.232.165.3.5.3.1.2ColumnupsBypassVoltageread-onlymandatoryThe measured UPS bypass voltage in volts.
1.3.6.1.4.1.232.165.3.6NodeupsEnvironment
1.3.6.1.4.1.232.165.3.6.1ScalarupsEnvAmbientTempread-onlymandatoryThe reading of the ambient temperature in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.2ScalarupsEnvAmbientLowerLimitread-writemandatoryThe Lower Limit of the ambient temperature; if UpsEnvAmbientTemp falls below this value, the UpsAmbientTempBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.3ScalarupsEnvAmbientUpperLimitread-writemandatoryThe Upper Limit of the ambient temperature; if UpsEnvAmbientTemp rises above this value, the UpsAmbientTempBad alarm will occur. This value should be greater t…
1.3.6.1.4.1.232.165.3.6.4ScalarupsEnvAmbientHumidityread-onlymandatoryThe reading of the ambient humidity in the vicinity of the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.5ScalarupsEnvRemoteTempread-onlymandatoryThe reading of a remote temperature sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.6ScalarupsEnvRemoteHumidityread-onlymandatoryThe reading of a remote humidity sensor connected to the UPS or SNMP agent.
1.3.6.1.4.1.232.165.3.6.7ScalarupsEnvNumContactsread-onlymandatoryThe number of Contacts in the UpsContactsTable. This object indicates the number of rows in the UpsContactsTable.
1.3.6.1.4.1.232.165.3.6.8TableupsContactsTablenot-accessiblemandatoryA list of Contact Sensing table entries. The number of entries is given by the value of UpsEnvNumContacts.
1.3.6.1.4.1.232.165.3.6.8.1RowupsContactsTableEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Contact input.
1.3.6.1.4.1.232.165.3.6.8.1.1ColumnupsContactIndexread-onlymandatoryThe Contact identifier; identical to the Contact Number.
1.3.6.1.4.1.232.165.3.6.8.1.2ColumnupsContactTyperead-writemandatoryThe normal state for this contact. The 'other' state is the Active state for generating the UpstdContactActiveNotice trap. If anyChange(3) is selected, then th…
1.3.6.1.4.1.232.165.3.6.8.1.3ColumnupsContactStateread-onlymandatoryThe current state of the Contact input; the value is based on the open/closed input state and the setting for UpsContactType. When entering the openWithNotice(…
1.3.6.1.4.1.232.165.3.6.8.1.4ColumnupsContactDescrread-writemandatoryA label identifying the Contact. This object should be set by the administrator.
1.3.6.1.4.1.232.165.3.6.9ScalarupsEnvRemoteTempLowerLimitread-writemandatoryThe Lower Limit of the remote temperature; if UpsEnvRemoteTemp falls below this value, the UpsRemoteTempBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.10ScalarupsEnvRemoteTempUpperLimitread-writemandatoryThe Upper Limit of the remote temperature; if UpsEnvRemoteTemp rises above this value, the UpsRemoteTempBad alarm will occur. This value should be greater than…
1.3.6.1.4.1.232.165.3.6.11ScalarupsEnvRemoteHumidityLowerLimitread-writemandatoryThe Lower Limit of the remote humidity reading; if UpsEnvRemoteHumidity falls below this value, the UpsRemoteHumidityBad alarm will occur.
1.3.6.1.4.1.232.165.3.6.12ScalarupsEnvRemoteHumidityUpperLimitread-writemandatoryThe Upper Limit of the remote humidity reading; if UpsEnvRemoteHumidity rises above this value, the UpsRemoteHumidityBad alarm will occur. This value should be…
1.3.6.1.4.1.232.165.3.7NodeupsTest
1.3.6.1.4.1.232.165.3.7.1ScalarupsTestBatteryread-writemandatorySetting this variable to startTest initiates the battery test. All other set values are invalid.
1.3.6.1.4.1.232.165.3.7.2ScalarupsTestBatteryStatusread-onlymandatoryReading this enumerated value gives an indication of the UPS Battery test status.
1.3.6.1.4.1.232.165.3.7.3ScalarupsTestTrapread-writemandatorySetting this variable to startTestTrap initiates a TrapTest is sent out from HPMM. All other set values are invalid.
1.3.6.1.4.1.232.165.3.8NodeupsControl
1.3.6.1.4.1.232.165.3.8.1ScalarupsControlOutputOffDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn off after the number of seconds. Setting it to 0 will cause an attempt to abort a pendi…
1.3.6.1.4.1.232.165.3.8.2ScalarupsControlOutputOnDelayread-writemandatorySetting this value to other than zero will cause the UPS output to turn on after the number of seconds. Setting it to 0 will cause an attempt to abort a pendin…
1.3.6.1.4.1.232.165.3.8.3ScalarupsControlOutputOffTrapDelayread-writemandatoryWhen UpsControlOutputOffDelay reaches this value, a trap will be sent.
1.3.6.1.4.1.232.165.3.8.4ScalarupsControlOutputOnTrapDelayread-writedeprecatedWhen UpsControlOutputOnDelay reaches this value, a UpsOutputOff trap will be sent.
1.3.6.1.4.1.232.165.3.8.5ScalarupsControlToBypassDelayread-writemandatorySetting this value to other than zero will cause the UPS output to go to Bypass after the number of seconds. If the Bypass is unavailable, this may cause the U…
1.3.6.1.4.1.232.165.3.8.6ScalarupsLoadShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.232.165.3.9NodeupsConfig
1.3.6.1.4.1.232.165.3.9.1ScalarupsConfigOutputVoltageread-onlymandatoryThe nominal UPS Output voltage per phase in volts.
1.3.6.1.4.1.232.165.3.9.2ScalarupsConfigInputVoltageread-onlymandatoryThe nominal UPS Input voltage per phase in volts.
1.3.6.1.4.1.232.165.3.9.3ScalarupsConfigOutputWattsread-onlymandatoryThe nominal UPS available real power output in watts.
1.3.6.1.4.1.232.165.3.9.4ScalarupsConfigOutputFreqread-onlymandatoryThe nominal output frequency in tenths of Hz.
1.3.6.1.4.1.232.165.3.9.5ScalarupsConfigDateAndTimeread-writemandatoryDate and time information for the UPS. Setting this variable will initiate a set UPS date and time to this value. Reading this variable will return the UPS tim…
1.3.6.1.4.1.232.165.3.9.6ScalarupsConfigLowOutputVoltageLimitread-onlymandatoryThe Lower limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.232.165.3.9.7ScalarupsConfigHighOutputVoltageLimitread-onlymandatoryThe Upper limit for acceptable Output Voltage, per the UPS specifications.
1.3.6.1.4.1.232.165.3.10NodeupsRecep
1.3.6.1.4.1.232.165.3.10.1ScalarupsNumReceptaclesread-onlymandatoryThe number of independently controllable Receptacles, as described in the UpsRecepTable.
1.3.6.1.4.1.232.165.3.10.2TableupsRecepTablenot-accessiblemandatoryThe Aggregate Object with number of entries equal to NumReceptacles and including the UpsRecep group.
1.3.6.1.4.1.232.165.3.10.2.1RowupsRecepEntrynot-accessiblemandatoryThe Recep table entry, etc.
1.3.6.1.4.1.232.165.3.10.2.1.1ColumnupsRecepIndexread-onlymandatoryThe number of the Receptacle. Serves as index for Receptacle table.
1.3.6.1.4.1.232.165.3.10.2.1.2ColumnupsRecepStatusread-onlymandatoryThe Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off, 4=Off w/Pending ON, 5=Unknown.
1.3.6.1.4.1.232.165.3.10.2.1.3ColumnupsRecepOffDelaySecsread-writemandatoryThe Delay until the Receptacle is turned Off. Setting this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immed…
1.3.6.1.4.1.232.165.3.10.2.1.4ColumnupsRecepOnDelaySecsread-writemandatoryThe Delay until the Receptacle is turned On. Setting this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immedia…
1.3.6.1.4.1.232.165.3.10.2.1.5ColumnupsRecepAutoOffDelayread-writemandatoryThe delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automaticall…
1.3.6.1.4.1.232.165.3.10.2.1.6ColumnupsRecepAutoOnDelayread-writemandatorySeconds delay after the Outlet is signaled to turn On before the Output is Automatically turned ON. A value of -1 means that this Output should never be turned…
1.3.6.1.4.1.232.165.3.10.2.1.7ColumnupsRecepShedSecsWithRestartread-writemandatorySetting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is ag…
1.3.6.1.4.1.232.165.3.11NodeupsTopology
1.3.6.1.4.1.232.165.3.11.1ScalarupsTopologyTyperead-onlymandatoryValue which denotes the type of UPS by its power topology. Values are the same as those described in the XCP Topology block's Overall Topology field.
1.3.6.1.4.1.232.165.3.11.2ScalarupsTopoMachineCoderead-onlymandatoryID Value which denotes the Compaq/HP model of the UPS for software. Values are the same as those described in the XCP Configuration block's Machine Code field.
1.3.6.1.4.1.232.165.3.11.3ScalarupsTopoUnitNumberread-onlymandatoryIdentifies which unit and what type of data is being reported. A value of 0 means that this MIB information comes from the top-level system view (eg, manifold …
1.3.6.1.4.1.232.165.3.11.4ScalarupsTopoPowerStrategyread-writemandatoryValue which denotes which Power Strategy is currently set for the UPS. The values are: highAlert(1) - The UPS shall optimize its operating state to maximize it…
1.3.6.1.4.1.232.165.4Nodepdr
1.3.6.1.4.1.232.165.4NodetrapClearedAn alarm has cleared. Action: Check the Trap Details for more information.
1.3.6.1.4.1.232.165.4.1NodepdrIdent
1.3.6.1.4.1.232.165.4.1.1ScalarpdrNameread-writemandatoryThe string identify the device.
1.3.6.1.4.1.232.165.4.1.2ScalarpdrModelread-onlymandatoryThe Device Model.
1.3.6.1.4.1.232.165.4.1.3ScalarpdrManufacturerread-onlymandatoryThe Device Manufacturer Name (e.g. Hewlett-Packard).
1.3.6.1.4.1.232.165.4.1.4ScalarpdrFirmwareVersionread-onlymandatoryThe firmware revision level of the device.
1.3.6.1.4.1.232.165.4.1.5ScalarpdrPartNumberread-onlymandatoryThe device part number.
1.3.6.1.4.1.232.165.4.1.6ScalarpdrSerialNumberread-onlymandatoryThe PDR's serial number.
1.3.6.1.4.1.232.165.4.1.7ScalarpdrVARatingread-onlymandatoryThe VA Rating of this PDR (all phases)
1.3.6.1.4.1.232.165.4.1.8ScalarpdrNominalOutputVoltageread-onlymandatoryThe nominal Output Voltage may differ from the nominal Input Voltage if the PDR has an input transformer
1.3.6.1.4.1.232.165.4.1.9ScalarpdrNumPhasesread-onlymandatoryThe number of phases for this PDR
1.3.6.1.4.1.232.165.4.1.10ScalarpdrNumPanelsread-onlymandatoryThe number of panels or subfeeds in this PDR
1.3.6.1.4.1.232.165.4.1.11ScalarpdrNumBreakersread-onlymandatoryThe number of breakers in this PDR
1.3.6.1.4.1.232.165.4.2NodepdrPanel
1.3.6.1.4.1.232.165.4.2.1TablepdrPanelTablenot-accessiblemandatoryAggregate Object with number of entries equal to pdrNumPanels
1.3.6.1.4.1.232.165.4.2.1.1RowpdrPanelEntrynot-accessiblemandatoryThe panel table entry containing all power parameters for each panel.
1.3.6.1.4.1.232.165.4.2.1.1.1ColumnpdrPanelIndexread-onlymandatoryIndex for the pdrPanelEntry table.
1.3.6.1.4.1.232.165.4.2.1.1.2ColumnpdrPanelFrequencyread-onlymandatoryThe present frequency reading for the panel voltage.
1.3.6.1.4.1.232.165.4.2.1.1.3ColumnpdrPanelPowerread-onlymandatoryThe present power of the panel.
1.3.6.1.4.1.232.165.4.2.1.1.4ColumnpdrPanelRatedCurrentread-onlymandatoryThe present rated current of the panel.
1.3.6.1.4.1.232.165.4.2.1.1.5ColumnpdrPanelMonthlyKWHread-onlymandatoryThe accumulated KWH for this panel since the beginning of this calendar month or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.6ColumnpdrPanelYearlyKWHread-onlymandatoryThe accumulated KWH for this panel since the beginning of this calendar year or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.7ColumnpdrPanelTotalKWHread-onlymandatoryThe accumulated KWH for this panel since it was put into service or since the last reset.
1.3.6.1.4.1.232.165.4.2.1.1.8ColumnpdrPanelVoltageAread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.9ColumnpdrPanelVoltageBread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.10ColumnpdrPanelVoltageCread-onlymandatoryThe measured panel output voltage.
1.3.6.1.4.1.232.165.4.2.1.1.11ColumnpdrPanelCurrentAread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.12ColumnpdrPanelCurrentBread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.13ColumnpdrPanelCurrentCread-onlymandatoryThe measured panel output current.
1.3.6.1.4.1.232.165.4.2.1.1.14ColumnpdrPanelLoadAread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.2.1.1.15ColumnpdrPanelLoadBread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.2.1.1.16ColumnpdrPanelLoadCread-onlymandatoryThe percentage of load is the ratio of each output current to the rated output current to the panel.
1.3.6.1.4.1.232.165.4.3NodepdrBreaker
1.3.6.1.4.1.232.165.4.3.1TablepdrBreakerTablenot-accessiblemandatoryList of breaker table entries. The number of entries is given by pdrNumBreakers for this panel.
1.3.6.1.4.1.232.165.4.3.1.1RowpdrBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output breaker of a particular panel.
1.3.6.1.4.1.232.165.4.3.1.1.1ColumnpdrBreakerIndexread-onlymandatoryThe index of breakers. 42 breakers in each panel, arranged in odd and even columns
1.3.6.1.4.1.232.165.4.3.1.1.2ColumnpdrBreakerPanelread-onlymandatoryThe index of panel that these breakers are installed on.
1.3.6.1.4.1.232.165.4.3.1.1.3ColumnpdrBreakerNumPositionread-onlymandatoryThe position of this breaker in the panel, 1-phase breaker or n-m breaker for 2-phase or n-m-k breaker for 3-phase.
1.3.6.1.4.1.232.165.4.3.1.1.4ColumnpdrBreakerNumPhasesread-onlymandatoryThe number of phase for this particular breaker.
1.3.6.1.4.1.232.165.4.3.1.1.5ColumnpdrBreakerNumSequenceread-onlymandatoryThe sequence of this breaker. i.e. 1 for single phase 1,2 for 2-phase or 1,2,3 for 3-phase.
1.3.6.1.4.1.232.165.4.3.1.1.6ColumnpdrBreakerRatedCurrentread-onlymandatoryThe rated current in Amps for this particular breaker.
1.3.6.1.4.1.232.165.4.3.1.1.7ColumnpdrBreakerMonthlyKWHread-onlymandatoryThe accumulated KWH for this breaker since the beginning of this calendar month or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.8ColumnpdrBreakerYearlyKWHread-onlymandatoryThe accumulated KWH for this breaker since the beginning of this calendar year or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.9ColumnpdrBreakerTotalKWHread-onlymandatoryThe accumulated KWH for this breaker since it was put into service or since the last reset.
1.3.6.1.4.1.232.165.4.3.1.1.10ColumnpdrBreakerCurrentread-onlymandatoryThe measured output current for this breaker Current.
1.3.6.1.4.1.232.165.4.3.1.1.11ColumnpdrBreakerCurrentPercentread-onlymandatoryThe ratio of output current over rated current for each breaker.
1.3.6.1.4.1.232.165.4.3.1.1.12ColumnpdrBreakerPowerread-onlymandatoryThe power for this breaker.
1.3.6.1.4.1.232.165.4.3.1.1.13ColumnpdrBreakerPercentWarningread-onlymandatoryThe percentage of Warning set for this breaker.
1.3.6.1.4.1.232.165.4.3.1.1.14ColumnpdrBreakerPercentOverloadread-onlymandatoryThe percentage of Overload set for this breaker.
1.3.6.1.4.1.232.165.5NodetrapTestTest trap sent to a trap receiver to check proper reception of traps
1.3.6.1.4.1.232.165.6NodedeviceTrapInitializationThis trap is sent each time a power device is initialized.