LIEBERT-UPSTATION-GXT-UPS-MIB
117 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter enterprises Gauge TimeTicks |
| RFC1213-MIB | DisplayString sysUpTime |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.476 | Nodeemerson | |||
| 1.3.6.1.4.1.476.1 | NodeliebertCorp | |||
| 1.3.6.1.4.1.476.1.1 | NodeliebertUps | |||
| 1.3.6.1.4.1.476.1.1.1 | NodeluExtensions | |||
| 1.3.6.1.4.1.476.1.1.1.1 | NodeluCore | |||
| 1.3.6.1.4.1.476.1.1.1.1.1 | NodelcUpsIdent | |||
| 1.3.6.1.4.1.476.1.1.1.1.1.1 | ScalarlcUpsIdentManufacturer | read-only | optional | The UPS manufacturer. |
| 1.3.6.1.4.1.476.1.1.1.1.1.2 | ScalarlcUpsIdentModel | read-write | optional | The UPS Model designation. |
| 1.3.6.1.4.1.476.1.1.1.1.1.3 | ScalarlcUpsIdentSoftwareVersion | read-only | optional | The UPS SNMP Agent software version. |
| 1.3.6.1.4.1.476.1.1.1.1.1.4 | ScalarlcUpsIdentSpecific | read-only | optional | A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this in… |
| 1.3.6.1.4.1.476.1.1.1.1.1.5 | ScalarlcUpsIdentFirmwareVersion | read-only | optional | The firmware revision level of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.1.6 | ScalarlcUpsIdentSerialNumber | read-only | optional | The serial number of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.1.7 | ScalarlcUpsIdentManufactureDate | read-only | optional | The date of manufacture of the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.2 | NodelcUpsBattery | |||
| 1.3.6.1.4.1.476.1.1.1.1.2.1 | ScalarlcUpsBatTimeRemaining | read-only | optional | The estimated time to depletion of battery charge. (Unit of measure: Minute) |
| 1.3.6.1.4.1.476.1.1.1.1.2.3 | ScalarlcUpsBatVoltage | read-only | optional | The current battery voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.2.6 | ScalarlcUpsBatCapacity | read-only | optional | The current battery capacity in percentage of total available. |
| 1.3.6.1.4.1.476.1.1.1.1.3 | NodelcUpsInput | |||
| 1.3.6.1.4.1.476.1.1.1.1.3.1 | ScalarlcUpsInputFrequency | read-only | optional | The current input frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.3.5 | ScalarlcUpsInputNumLines | read-only | optional | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| 1.3.6.1.4.1.476.1.1.1.1.3.6 | TablelcUpsInputTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1 | RowlcUpsInputEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.1 | ColumnlcUpsInputLine | read-only | optional | The input Line. |
| 1.3.6.1.4.1.476.1.1.1.1.3.6.1.2 | ColumnlcUpsInputVoltage | read-only | optional | The input voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.4 | NodelcUpsOutput | |||
| 1.3.6.1.4.1.476.1.1.1.1.4.1 | ScalarlcUpsOutputFrequency | read-only | optional | The current output frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.4.2 | ScalarlcUpsOutputLoad | read-only | optional | The current output load percentage. |
| 1.3.6.1.4.1.476.1.1.1.1.4.3 | ScalarlcUpsOutputNumLines | read-only | optional | The number of output lines utilized in this device. This entry indicates the number of rows in the output table. |
| 1.3.6.1.4.1.476.1.1.1.1.4.4 | TablelcUpsOutputTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1 | RowlcUpsOutputEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.1 | ColumnlcUpsOutputLine | read-only | optional | The output Line. |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.2 | ColumnlcUpsOutputVoltage | read-only | optional | The output voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.4.4.1.3 | ColumnlcUpsOutputCurrent | read-only | optional | The output current. (Unit of measure: Amp) |
| 1.3.6.1.4.1.476.1.1.1.1.4.5 | ScalarlcUpsOutputWatts | read-only | optional | The output power in watts. |
| 1.3.6.1.4.1.476.1.1.1.1.5 | NodelcUpsInverter | |||
| 1.3.6.1.4.1.476.1.1.1.1.5.1 | ScalarlcUpsInverterStatus | read-only | optional | The state of the inverter. Unknown is returned if the state can not be determined. |
| 1.3.6.1.4.1.476.1.1.1.1.6 | NodelcUpsAlarm | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.1 | ScalarlcUpsAlarms | read-only | optional | The current number of alarm conditions. |
| 1.3.6.1.4.1.476.1.1.1.1.6.2 | TablelcUpsAlarmTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1 | RowlcUpsAlarmEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 | ColumnlcUpsAlarmId | read-only | optional | A unique identifier for an alarm condition. This value must remain constant between agent initializations. |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 | ColumnlcUpsAlarmDescr | read-only | optional | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3 | ColumnlcUpsAlarmTime | read-only | optional | The value of sysUpTime when the alarm condition occured. |
| 1.3.6.1.4.1.476.1.1.1.1.6.3 | NodelcUpsAlarmConditions | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.1 | NodelcUpsAlarmLowBatteryWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.2 | NodelcUpsAlarmLowBatteryShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.3 | NodelcUpsAlarmUtilFailed | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.4 | NodelcUpsAlarmOverTempWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.5 | NodelcUpsAlarmOverTempShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.6 | NodelcUpsAlarmOutputOverloadWarning | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.7 | NodelcUpsAlarmOutputOverloadShutdown | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.8 | NodelcUpsAlarmInputOverVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.9 | NodelcUpsAlarmBatteryBad | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.10 | NodelcUpsAlarmOnBattery | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.11 | NodelcUpsAlarmStopNoticeIssued | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.12 | NodelcUpsAlarmUpsOff | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.13 | NodelcUpsAlarmInputFreqError | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.15 | NodelcUpsAlarmOutputUnderVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.16 | NodelcUpsAlarmOutputOverVoltage | |||
| 1.3.6.1.4.1.476.1.1.1.1.6.3.17 | NodelcUpsBadBypassPower | |||
| 1.3.6.1.4.1.476.1.1.1.1.7 | NodelcUpsTest | |||
| 1.3.6.1.4.1.476.1.1.1.1.7.1 | ScalarlcUpsTestBattery | read-write | optional | Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, other… |
| 1.3.6.1.4.1.476.1.1.1.1.7.2 | ScalarlcUpsTestBatteryStatus | read-only | optional | The status of the battery test. |
| 1.3.6.1.4.1.476.1.1.1.1.8 | NodelcUpsControl | |||
| 1.3.6.1.4.1.476.1.1.1.1.8.1 | ScalarlcUpsControlOutputOffDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seco… |
| 1.3.6.1.4.1.476.1.1.1.1.8.2 | ScalarlcUpsControlOutputOnDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of secon… |
| 1.3.6.1.4.1.476.1.1.1.1.8.3 | ScalarlcUpsControlOutputOffTrapDelay | read-write | optional | When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will… |
| 1.3.6.1.4.1.476.1.1.1.1.8.4 | ScalarlcUpsControlOutputOnTrapDelay | read-write | optional | When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will b… |
| 1.3.6.1.4.1.476.1.1.1.1.8.5 | ScalarlcUpsControlUnixShutdownDelay | read-write | optional | Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of sec… |
| 1.3.6.1.4.1.476.1.1.1.1.8.6 | ScalarlcUpsControlUnixShutdownTrapDelay | read-write | optional | When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this objec… |
| 1.3.6.1.4.1.476.1.1.1.1.8.7 | ScalarlcUpsControlCancelCommands | read-write | optional | Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUp… |
| 1.3.6.1.4.1.476.1.1.1.1.8.8 | ScalarlcUpsControlRebootAgentDelay | read-write | optional | Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The c… |
| 1.3.6.1.4.1.476.1.1.1.1.9 | NodelcUpsNominal | |||
| 1.3.6.1.4.1.476.1.1.1.1.9.1 | ScalarlcUpsNominalOutputVoltage | read-write | optional | The nominal output voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.9.2 | ScalarlcUpsNominalInputVoltage | read-write | optional | The nominal input voltage. (Unit of measure: volt) |
| 1.3.6.1.4.1.476.1.1.1.1.9.5 | ScalarlcUpsNominalOutputFreq | read-write | optional | The nominal output frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.9.6 | ScalarlcUpsNominalInputFreq | read-write | optional | The nominal input frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.9.7 | ScalarlcUpsNominalOutputVaRating | read-write | optional | The nominal Volt-Amp rating. |
| 1.3.6.1.4.1.476.1.1.1.1.9.8 | ScalarlcUpsNominalOutputWattsRating | read-write | optional | The nominal power rating. (Unit of measure: watt) |
| 1.3.6.1.4.1.476.1.1.1.1.11 | NodelcUpsTraps | |||
| 1.3.6.1.4.1.476.1.1.1.1.11.1 | NodelcUpsOverloadWarningTrap | An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.2 | NodelcUpsOverloadShutdownTrap | An lcUpsOverloadShutdownTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity and has shut… | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.3 | NodelcUpsOnBatteryTrap | An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.4 | NodelcUpsLowBatteryWarningTrap | An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.5 | NodelcUpsLowBatteryShutdownTrap | An lcUpsLowBatteryShutdownTrap signifies that the UPS has shut off the output due to a Low Battery state. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.6 | NodelcUpsUtilPowerFailedTrap | An lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.7 | NodelcUpsUtilPowerRestoredTrap | An lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.8 | NodelcUpsInputOverVoltageTrap | An lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.9 | NodelcUpsOverTempWarningTrap | An lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.10 | NodelcUpsOverTempShutdownTrap | An lcUpsOverTempShutdownTrap signifies that the UPS has detected a excessive temperature condition and shut off the output. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.11 | NodelcUpsAlarmTrap | An Alarm condition has occurred and is being reported in the lcUpsAlarmTable. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.12 | NodelcUpsOutputOffTrap | An lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.13 | NodelcUpsOutputOffWarningTrap | An lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.14 | NodelcUpsOutputOnTrap | An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.15 | NodelcUpsOutputOnWarningTrap | An lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.16 | NodelcUpsUnixShutdownTrap | An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.17 | NodelcUpsUnixShutdownWarningTrap | An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.22 | NodelcUpsInputFreqErrorTrap | An ldUpsInputFreqErrorTrap signifies that the UPS has detected that input frequency is outside tolerable variance. | ||
| 1.3.6.1.4.1.476.1.1.1.1.11.24 | NodelcUpsOutputOverVoltageTrap | An lcUpsOutputOverVoltageTrap signifies that the UPS has detected that the output voltage is too high. | ||
| 1.3.6.1.4.1.476.1.1.1.1.13 | NodelcUpsBypass | |||
| 1.3.6.1.4.1.476.1.1.1.1.13.1 | ScalarlcUpsOnBypass | read-only | optional | Indicates that the UPS is currently on bypass. |
| 1.3.6.1.4.1.476.1.1.1.1.13.2 | ScalarlcUpsBypassFrequency | read-only | optional | The current bypass frequency. (Unit of measure: Hertz) |
| 1.3.6.1.4.1.476.1.1.1.1.13.3 | ScalarlcUpsBypassNumLines | read-only | optional | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.476.1.1.1.1.13.4 | TablelcUpsBypassTable | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1 | RowlcUpsBypassEntry | not-accessible | optional | |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1.1 | ColumnlcUpsBypassLine | read-only | optional | The bypass Line. |
| 1.3.6.1.4.1.476.1.1.1.1.13.4.1.2 | ColumnlcUpsBypassVoltage | read-only | optional | The bypass voltage. (Unit of measure: Volt) |
| 1.3.6.1.4.1.476.1.1.1.1.14 | NodelcUpsConfig | |||
| 1.3.6.1.4.1.476.1.1.1.1.14.1 | ScalarlcUpsConfigType | read-only | optional | Indicates the UPS topology. |
| 1.3.6.1.4.1.476.1.1.1.1.14.2 | ScalarlcUpsConfigBypassInstalled | read-only | optional | Indicates if a bypass is installed in the UPS. |
| 1.3.6.1.4.1.476.1.1.1.1.14.3 | ScalarlcUpsConfigModuleCount | read-only | optional | A number identifying how many multi-module UPS are connected to the System Control Cabinet. |
| 1.3.6.1.4.1.476.1.1.1.1.14.5 | ScalarlcUpsConfigAudibleStatus | read-write | optional | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this … |
| 1.3.6.1.4.1.476.1.1.1.1.14.6 | ScalarlcUpsConfigLowBattTime | read-write | optional | The value of lcUpsBatTimeRemaining at which a lowBatteryWarning condition is declared. (Unit of measure: Minute) |
| 1.3.6.1.4.1.476.1.1.1.1.14.7 | ScalarlcUpsConfigAutoRestart | read-write | optional | Setting this object will start the output after the indicated number of ticks (1 tick = 10 seconds), including starting the UPS, if necessary. Setting this obj… |
| 1.3.6.1.4.1.476.1.1.1.14 | NodeluUPStationGxt | |||
| 1.3.6.1.4.1.476.1.1.2 | NodeluExperimental | |||
| 1.3.6.1.4.1.476.1.1.3 | NodeluPrivate |