MIB Viewer

RLE-FALCON-EM-MIB

932 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.3184Noderle
1.3.6.1.4.1.3184.1Nodeproducts
1.3.6.1.4.1.3184.1.5Nodefalcon-em
1.3.6.1.4.1.3184.1.5.1Nodefalcon-emMIB
1.3.6.1.4.1.3184.1.5.1.1NodefalconIdent
1.3.6.1.4.1.3184.1.5.1.1.1ScalarfalconIdentManufacturerread-onlymandatoryThe Monitor Control Unit manufacturer.
1.3.6.1.4.1.3184.1.5.1.1.2ScalarfalconIdentModelread-onlymandatoryThe Monitor Control Unit Model designation.
1.3.6.1.4.1.3184.1.5.1.1.3ScalarfalconIdentSoftwareVersionread-onlymandatoryThe falcon SNMP Agent software version.
1.3.6.1.4.1.3184.1.5.1.1.4ScalarfalconIdentSpecificread-onlymandatoryA reference to MIB definitions specific to the particular Monitor Unit being managed. This object is used to locate the product-specific MIB for this device. I…
1.3.6.1.4.1.3184.1.5.1.1.5NodefalconOptionCards
1.3.6.1.4.1.3184.1.5.1.1.5.1ScalarfalconOptionCard1read-onlymandatoryOption slot #1.
1.3.6.1.4.1.3184.1.5.1.1.5.2ScalarfalconOptionCard2read-onlymandatoryOption slot #2.
1.3.6.1.4.1.3184.1.5.1.1.5.3ScalarfalconOptionCard3read-onlymandatoryOption slot #3.
1.3.6.1.4.1.3184.1.5.1.1.5.4ScalarfalconOptionCard4read-onlymandatoryOption slot #4.
1.3.6.1.4.1.3184.1.5.1.2NodefalconSystem
1.3.6.1.4.1.3184.1.5.1.2.1NodefalconSystemSettings
1.3.6.1.4.1.3184.1.5.1.2.1.1ScalarfalconClockread-writemandatoryThe falcon internal clock settings. Displayed as MM/DD/YY HH:MM:SS
1.3.6.1.4.1.3184.1.5.1.2.1.2ScalarfalconDoorAlarmBypassread-writemandatoryThe falcon door alarm bypass switch. This allows the alarm to be bypassed upon valid keypad access. Zero disables this, or use 1 thru 8 for the corresponding f…
1.3.6.1.4.1.3184.1.5.1.2.1.3ScalarfalconInputVoltageread-onlymandatoryThe falcon input voltage (DC Power).
1.3.6.1.4.1.3184.1.5.1.2.1.4ScalarfalconLowBatteryThresholdread-writemandatoryThe low voltage trip point for the low battery alarm. When the input voltage goes below this voltage, the Low Battery alarm is set.
1.3.6.1.4.1.3184.1.5.1.2.1.5ScalarfalconAnalogAverageread-writemandatoryThis is the analog averaging duration in seconds. The analog input readings are averaged for this time period before updating. This value must be set to 1,2,3,…
1.3.6.1.4.1.3184.1.5.1.2.1.6ScalarfalconPagerStatusStringread-onlymandatoryThe falcon last page status char string.
1.3.6.1.4.1.3184.1.5.1.2.1.7ScalarfalconWebUserread-onlymandatoryThe web user who made the last configuration changes.
1.3.6.1.4.1.3184.1.5.1.2.1.8ScalarfalconMaintenanceModeread-onlymandatoryThe status of the falcon maintenance mode. If this value is notActive(0) then the maintenance mode is not engaged. If this value is active(1) then the maintena…
1.3.6.1.4.1.3184.1.5.1.2.2NodefalconKeypad
1.3.6.1.4.1.3184.1.5.1.2.2.1ScalarfalconKeypadUsersread-onlymandatoryThe number of keypad users allowed on this system.
1.3.6.1.4.1.3184.1.5.1.2.2.2TablefalconKeypadUsersTablenot-accessiblemandatoryA table of the falcon keypad users. The number of users is given by the value of falconKeypadUsers.
1.3.6.1.4.1.3184.1.5.1.2.2.2.1RowfalconKeypadUserEntrynot-accessiblemandatoryAn entry containing objects for the Falcon keypad user configuration.
1.3.6.1.4.1.3184.1.5.1.2.2.2.1.1ColumnfalconKeypadUserIndexread-onlymandatoryA unique value for each keypad user. Its value ranges between 1 and the value of falconKeypadUsers.
1.3.6.1.4.1.3184.1.5.1.2.2.2.1.2ColumnfalconKeypadCoderead-writemandatoryThe falcon keypad access code for user #X. This can be up to six numeric characters.
1.3.6.1.4.1.3184.1.5.1.2.2.2.1.3ColumnfalconKeypadNameread-writemandatoryThe falcon keypad access name for user #X. This can be up to 20 characters.
1.3.6.1.4.1.3184.1.5.1.3NodefalconInputs
1.3.6.1.4.1.3184.1.5.1.3.1NodefalconInputPorts
1.3.6.1.4.1.3184.1.5.1.3.1.1ScalarfalconNumberOfInputPortsread-onlymandatoryThe number of input ports available on this system.
1.3.6.1.4.1.3184.1.5.1.3.1.2TablefalconInputTablenot-accessiblemandatoryA table of the falcon input port status and configuration. The number of input ports is given by the value of falconNumberOfInputPorts.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1RowfalconInputEntrynot-accessiblemandatoryAn entry containing objects for the Falcon input port data and configuration.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.1ColumnfalconInputIndexread-onlymandatoryA unique value for each input port. Its value ranges between 1 and the value of falconNumberOfInputPorts.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.2ColumnfalconInputTyperead-onlymandatoryThe installed hardware for Input Number X. If this value is notInstalled(0) then this input is not physically installed in the falcon.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.3ColumnfalconInputStateread-writemandatoryThe state of use of Input Number X. When a sensor is connected to Input 1 set State to installed(2) to indicate that the value of falconReading1 is valid. When…
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.4ColumnfalconInputReadingread-onlymandatoryThe reading for sensor. If the input is digital, the reading will be 1 (active) or 0 (inactive)
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.5ColumnfalconInputGainread-writemandatoryA correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor to obtain the value of the Input variable.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.6ColumnfalconInputOffsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from the Input Sensor to obtain the value of the Input varia…
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.7ColumnfalconInputLabelread-writemandatoryA user-defined text string associated with the Input port.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.8ColumnfalconInputUOMread-writemandatoryA user-defined text string associated with the Input port.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.9ColumnfalconInputHighLimit2read-writemandatoryWhen the input port reaches or exceeds this value a trap will be generated signifying a high alarm condition at this sensor.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.10ColumnfalconInputHighLimitread-writemandatoryWhen the input port reaches or exceeds this value a trap will be generated signifying a high alarm condition at this sensor.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.11ColumnfalconInputLowLimitread-writemandatoryWhen the input port reaches or goes below this value a trap will be generated signifying a low alarm condition at this sensor.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.12ColumnfalconInputLowLimit2read-writemandatoryWhen the input port reaches or goes below this value a trap will be generated signifying a low alarm condition at this sensor.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.13ColumnfalconInputDelayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.14ColumnfalconInputHysteresisread-writemandatoryThe value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.15ColumnfalconInputScheduleread-onlymandatoryThe current alarm disable schedule for the input port.
1.3.6.1.4.1.3184.1.5.1.3.1.2.1.16ColumnfalconInputDigOffLabelread-writemandatoryA user-defined text string associated with the input port. This string is used for digital off text.
1.3.6.1.4.1.3184.1.5.1.3.2NodefalconTHSensors
1.3.6.1.4.1.3184.1.5.1.3.2.1NodefalconTempSensors
1.3.6.1.4.1.3184.1.5.1.3.2.1.1ScalarfalconNumberOfTempSensorsread-onlymandatoryThe number of internal temperature sensors available on this system.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2TablefalconTSTablenot-accessiblemandatoryA table of the falcon internal temperature sensor status and configuration. The number of sensors is given by the value of falconNumberOfTempSensors.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1RowfalconTSEntrynot-accessiblemandatoryAn entry containing objects for the Falcon internal temperature sensor data and configuration.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.1ColumnfalconTSIndexread-onlymandatoryA unique value for each internal temperature sensor. Its value ranges between 1 and the value of falconNumberOfTempSensors.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.2ColumnfalconTemperatureSensorStateread-writemandatoryThe state of use of the internal temperature sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.3ColumnfalconTemperatureSensorReadingread-onlymandatoryThe reading for internal temperature sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.4ColumnfalconTemperatureSensorOffsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from internal temperature sensor to obtain the value of the …
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.5ColumnfalconTemperatureSensorLabelread-writemandatoryA user-defined text string associated with internal temperature sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.6ColumnfalconTemperatureSensorUOMread-writemandatoryA user-defined text string associated with internal temperature sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.7ColumnfalconTemperatureSensorHighLimit2read-writemandatoryWhen the internal temperature sensor reaches or exceeds this value a trap will be generated signifying a high alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.8ColumnfalconTemperatureSensorHighLimitread-writemandatoryWhen the internal temperature sensor reaches or exceeds this value a trap will be generated signifying a high alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.9ColumnfalconTemperatureSensorLowLimitread-writemandatoryWhen the internal temperature sensor reaches or goes below this value a trap will be generated signifying a low alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.10ColumnfalconTemperatureSensorLowLimit2read-writemandatoryWhen the internal temperature sensor reaches or goes below this value a trap will be generated signifying a low alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.11ColumnfalconTemperatureSensorDelayread-writemandatoryThe number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.12ColumnfalconTemperatureSensorHysteresisread-writemandatoryThe value of alarm hysteresis for this sensor. The reading must decrease or increase by this value before the alarm will clear.
1.3.6.1.4.1.3184.1.5.1.3.2.1.2.1.13ColumnfalconTemperatureSensorScheduleread-onlymandatoryThe current alarm disable schedule for this sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.2NodefalconHumiditySensors
1.3.6.1.4.1.3184.1.5.1.3.2.2.1ScalarfalconNumberOfHumiditySensorsread-onlymandatoryThe number of internal humidity sensors available on this system.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2TablefalconHSTablenot-accessiblemandatoryA table of the falcon internal humidity sensor status and configuration. The number of sensors is given by the value of falconNumberOfHumiditySensors.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1RowfalconHSEntrynot-accessiblemandatoryAn entry containing objects for the Falcon internal humidity sensor data and configuration.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.1ColumnfalconHSIndexread-onlymandatoryA unique value for each internal humidity sensor. Its value ranges between 1 and the value of falconNumberOfHumiditySensors.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.2ColumnfalconHumiditySensorStateread-writemandatoryThe state of use of the internal humidity sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.3ColumnfalconHumiditySensorReadingread-onlymandatoryThe reading for internal humidity sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.4ColumnfalconHumiditySensorOffsetread-writemandatoryA correction Offset associated with the sensor variable. The value of Offset is added to the value from internal humidity sensor to obtain the value of the Hum…
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.5ColumnfalconHumiditySensorLabelread-writemandatoryA user-defined text string associated with internal humidity sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.6ColumnfalconHumiditySensorUOMread-writemandatoryA user-defined text string associated with internal humidity sensor.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.7ColumnfalconHumiditySensorHighLimit2read-writemandatoryWhen the internal humidity sensor reaches or exceeds this value a trap will be generated signifying a high alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.8ColumnfalconHumiditySensorHighLimitread-writemandatoryWhen the internal humidity sensor reaches or exceeds this value a trap will be generated signifying a high alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.9ColumnfalconHumiditySensorLowLimitread-writemandatoryWhen the internal humidity sensor reaches or goes below this value a trap will be generated signifying a low alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.10ColumnfalconHumiditySensorLowLimit2read-writemandatoryWhen the internal humidity sensor reaches or goes below this value a trap will be generated signifying a low alarm condition.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.11ColumnfalconHumiditySensorDelayread-writemandatoryThe number of seconds an alarm for this sensor must be present before annunication. The range of this setting is 0..600.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.12ColumnfalconHumiditySensorHysteresisread-writemandatoryThe value of alarm hysteresis for this sensor. The sensor reading must decrease or increase by this value before the alarm will clear.
1.3.6.1.4.1.3184.1.5.1.3.2.2.2.1.13ColumnfalconHumiditySensorScheduleread-onlymandatoryThe current alarm disable schedule for the humidity sensor.
1.3.6.1.4.1.3184.1.5.1.4NodefalconOutputs
1.3.6.1.4.1.3184.1.5.1.4.1NodefalconRelays
1.3.6.1.4.1.3184.1.5.1.4.1.1ScalarfalconNumberOfRelaysread-onlymandatoryThe number of output relays available on this system.
1.3.6.1.4.1.3184.1.5.1.4.1.2TablefalconRelayTablenot-accessiblemandatoryA table of the falcon output relay status and configuration. The number of relays is given by the value of falconNumberOfRelays.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1RowfalconRelayEntrynot-accessiblemandatoryAn entry containing objects for the Falcon output relay data and configuration.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.1ColumnfalconRelayIndexread-onlymandatoryA unique value for each output relay. Its value ranges between 1 and the value of falconNumberOfRelays.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.2ColumnfalconRelayStateread-writemandatoryThe state of use of this relay. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypa…
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.3ColumnfalconRelayStatusread-onlymandatoryThe current status for this relay.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.4ColumnfalconRelayLabelread-writemandatoryA user-defined text string associated with this relay.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.5ColumnfalconRelayTimeread-writemandatoryThe number of seconds the relay will be activated. Set this to -1 for indefinitely.
1.3.6.1.4.1.3184.1.5.1.4.1.2.1.6ColumnfalconRelayScheduleread-onlymandatoryThe current schedule for this relay.
1.3.6.1.4.1.3184.1.5.1.5NodefalconAlarms
1.3.6.1.4.1.3184.1.5.1.5.1ScalarfalconAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.3184.1.5.1.5.2TablefalconAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.3184.1.5.1.5.2.1RowfalconAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.3184.1.5.1.5.2.1.1ColumnfalconAlarmIdnot-accessiblemandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.3184.1.5.1.5.2.1.2ColumnfalconAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.3184.1.5.1.5.3NodefalconWellKnownAlarms
1.3.6.1.4.1.3184.1.5.1.5.3.10ScalarfalconInput1DigAlarmread-onlymandatoryThe digital input 1 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.11ScalarfalconInput1HighAlarmread-onlymandatoryThe reading for sensor 1 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.12ScalarfalconInput1LowAlarmread-onlymandatoryThe reading for sensor 1 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.13ScalarfalconInput1High2Alarmread-onlymandatoryThe reading for sensor 1 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.14ScalarfalconInput1Low2Alarmread-onlymandatoryThe reading for sensor 1 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.20ScalarfalconInput2DigAlarmread-onlymandatoryThe digital input 2 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.21ScalarfalconInput2HighAlarmread-onlymandatoryThe reading for sensor 2 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.22ScalarfalconInput2LowAlarmread-onlymandatoryThe reading for sensor 2 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.23ScalarfalconInput2High2Alarmread-onlymandatoryThe reading for sensor 2 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.24ScalarfalconInput2Low2Alarmread-onlymandatoryThe reading for sensor 2 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.30ScalarfalconInput3DigAlarmread-onlymandatoryThe digital input 3 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.31ScalarfalconInput3HighAlarmread-onlymandatoryThe reading for sensor 3 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.32ScalarfalconInput3LowAlarmread-onlymandatoryThe reading for sensor 3 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.33ScalarfalconInput3High2Alarmread-onlymandatoryThe reading for sensor 3 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.34ScalarfalconInput3Low2Alarmread-onlymandatoryThe reading for sensor 3 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.40ScalarfalconInput4DigAlarmread-onlymandatoryThe digital input 4 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.41ScalarfalconInput4HighAlarmread-onlymandatoryThe reading for sensor 4 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.42ScalarfalconInput4LowAlarmread-onlymandatoryThe reading for sensor 4 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.43ScalarfalconInput4High2Alarmread-onlymandatoryThe reading for sensor 4 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.44ScalarfalconInput4Low2Alarmread-onlymandatoryThe reading for sensor 4 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.50ScalarfalconInput5DigAlarmread-onlymandatoryThe digital input 5 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.51ScalarfalconInput5HighAlarmread-onlymandatoryThe reading for sensor 5 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.52ScalarfalconInput5LowAlarmread-onlymandatoryThe reading for sensor 5 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.53ScalarfalconInput5High2Alarmread-onlymandatoryThe reading for sensor 5 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.54ScalarfalconInput5Low2Alarmread-onlymandatoryThe reading for sensor 5 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.60ScalarfalconInput6DigAlarmread-onlymandatoryThe digital input 6 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.61ScalarfalconInput6HighAlarmread-onlymandatoryThe reading for sensor 6 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.62ScalarfalconInput6LowAlarmread-onlymandatoryThe reading for sensor 6 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.63ScalarfalconInput6High2Alarmread-onlymandatoryThe reading for sensor 6 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.64ScalarfalconInput6Low2Alarmread-onlymandatoryThe reading for sensor 6 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.70ScalarfalconInput7DigAlarmread-onlymandatoryThe digital input 7 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.71ScalarfalconInput7HighAlarmread-onlymandatoryThe reading for sensor 7 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.72ScalarfalconInput7LowAlarmread-onlymandatoryThe reading for sensor 7 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.73ScalarfalconInput7High2Alarmread-onlymandatoryThe reading for sensor 7 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.74ScalarfalconInput7Low2Alarmread-onlymandatoryThe reading for sensor 7 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.80ScalarfalconInput8DigAlarmread-onlymandatoryThe digital input 8 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.81ScalarfalconInput8HighAlarmread-onlymandatoryThe reading for sensor 8 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.82ScalarfalconInput8LowAlarmread-onlymandatoryThe reading for sensor 8 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.83ScalarfalconInput8High2Alarmread-onlymandatoryThe reading for sensor 8 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.84ScalarfalconInput8Low2Alarmread-onlymandatoryThe reading for sensor 8 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1010ScalarfalconInput9DigAlarmread-onlymandatoryThe digital input 9 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1011ScalarfalconInput9HighAlarmread-onlymandatoryThe reading for sensor 9 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1012ScalarfalconInput9LowAlarmread-onlymandatoryThe reading for sensor 9 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1013ScalarfalconInput9High2Alarmread-onlymandatoryThe reading for sensor 9 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1014ScalarfalconInput9Low2Alarmread-onlymandatoryThe reading for sensor 9 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1020ScalarfalconInput10DigAlarmread-onlymandatoryThe digital input 10 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1021ScalarfalconInput10HighAlarmread-onlymandatoryThe reading for sensor 10 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1022ScalarfalconInput10LowAlarmread-onlymandatoryThe reading for sensor 10 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1023ScalarfalconInput10High2Alarmread-onlymandatoryThe reading for sensor 10 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1024ScalarfalconInput10Low2Alarmread-onlymandatoryThe reading for sensor 10 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1030ScalarfalconInput11DigAlarmread-onlymandatoryThe digital input 11 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1031ScalarfalconInput11HighAlarmread-onlymandatoryThe reading for sensor 11 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1032ScalarfalconInput11LowAlarmread-onlymandatoryThe reading for sensor 11 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1033ScalarfalconInput11High2Alarmread-onlymandatoryThe reading for sensor 11 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1034ScalarfalconInput11Low2Alarmread-onlymandatoryThe reading for sensor 11 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1040ScalarfalconInput12DigAlarmread-onlymandatoryThe digital input 12 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1041ScalarfalconInput12HighAlarmread-onlymandatoryThe reading for sensor 12 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1042ScalarfalconInput12LowAlarmread-onlymandatoryThe reading for sensor 12 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1043ScalarfalconInput12High2Alarmread-onlymandatoryThe reading for sensor 12 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1044ScalarfalconInput12Low2Alarmread-onlymandatoryThe reading for sensor 12 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1050ScalarfalconInput13DigAlarmread-onlymandatoryThe digital input 13 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1051ScalarfalconInput13HighAlarmread-onlymandatoryThe reading for sensor 13 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1052ScalarfalconInput13LowAlarmread-onlymandatoryThe reading for sensor 13 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1053ScalarfalconInput13High2Alarmread-onlymandatoryThe reading for sensor 13 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1054ScalarfalconInput13Low2Alarmread-onlymandatoryThe reading for sensor 13 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1060ScalarfalconInput14DigAlarmread-onlymandatoryThe digital input 14 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1061ScalarfalconInput14HighAlarmread-onlymandatoryThe reading for sensor 14 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1062ScalarfalconInput14LowAlarmread-onlymandatoryThe reading for sensor 14 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1063ScalarfalconInput14High2Alarmread-onlymandatoryThe reading for sensor 14 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1064ScalarfalconInput14Low2Alarmread-onlymandatoryThe reading for sensor 14 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1070ScalarfalconInput15DigAlarmread-onlymandatoryThe digital input 15 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1071ScalarfalconInput15HighAlarmread-onlymandatoryThe reading for sensor 15 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1072ScalarfalconInput15LowAlarmread-onlymandatoryThe reading for sensor 15 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1073ScalarfalconInput15High2Alarmread-onlymandatoryThe reading for sensor 15 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1074ScalarfalconInput15Low2Alarmread-onlymandatoryThe reading for sensor 15 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1080ScalarfalconInput16DigAlarmread-onlymandatoryThe digital input 16 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1081ScalarfalconInput16HighAlarmread-onlymandatoryThe reading for sensor 16 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1082ScalarfalconInput16LowAlarmread-onlymandatoryThe reading for sensor 16 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1083ScalarfalconInput16High2Alarmread-onlymandatoryThe reading for sensor 16 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1084ScalarfalconInput16Low2Alarmread-onlymandatoryThe reading for sensor 16 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1090ScalarfalconInput17DigAlarmread-onlymandatoryThe digital input 17 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1091ScalarfalconInput17HighAlarmread-onlymandatoryThe reading for sensor 17 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1092ScalarfalconInput17LowAlarmread-onlymandatoryThe reading for sensor 17 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1093ScalarfalconInput17High2Alarmread-onlymandatoryThe reading for sensor 17 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1094ScalarfalconInput17Low2Alarmread-onlymandatoryThe reading for sensor 17 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1100ScalarfalconInput18DigAlarmread-onlymandatoryThe digital input 18 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1101ScalarfalconInput18HighAlarmread-onlymandatoryThe reading for sensor 18 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1102ScalarfalconInput18LowAlarmread-onlymandatoryThe reading for sensor 18 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1103ScalarfalconInput18High2Alarmread-onlymandatoryThe reading for sensor 18 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1104ScalarfalconInput18Low2Alarmread-onlymandatoryThe reading for sensor 18 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1110ScalarfalconInput19DigAlarmread-onlymandatoryThe digital input 19 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1111ScalarfalconInput19HighAlarmread-onlymandatoryThe reading for sensor 19 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1112ScalarfalconInput19LowAlarmread-onlymandatoryThe reading for sensor 19 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1113ScalarfalconInput19High2Alarmread-onlymandatoryThe reading for sensor 19 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1114ScalarfalconInput19Low2Alarmread-onlymandatoryThe reading for sensor 19 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1120ScalarfalconInput20DigAlarmread-onlymandatoryThe digital input 20 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1121ScalarfalconInput20HighAlarmread-onlymandatoryThe reading for sensor 20 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1122ScalarfalconInput20LowAlarmread-onlymandatoryThe reading for sensor 20 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1123ScalarfalconInput20High2Alarmread-onlymandatoryThe reading for sensor 20 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1124ScalarfalconInput20Low2Alarmread-onlymandatoryThe reading for sensor 20 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.1130ScalarfalconInput21DigAlarmread-onlymandatoryThe digital input 21 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1140ScalarfalconInput22DigAlarmread-onlymandatoryThe digital input 22 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1150ScalarfalconInput23DigAlarmread-onlymandatoryThe digital input 23 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1160ScalarfalconInput24DigAlarmread-onlymandatoryThe digital input 24 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1170ScalarfalconInput25DigAlarmread-onlymandatoryThe digital input 25 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1180ScalarfalconInput26DigAlarmread-onlymandatoryThe digital input 26 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1190ScalarfalconInput27DigAlarmread-onlymandatoryThe digital input 27 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1200ScalarfalconInput28DigAlarmread-onlymandatoryThe digital input 28 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1210ScalarfalconInput29DigAlarmread-onlymandatoryThe digital input 29 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1220ScalarfalconInput30DigAlarmread-onlymandatoryThe digital input 30 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1230ScalarfalconInput31DigAlarmread-onlymandatoryThe digital input 31 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.1240ScalarfalconInput32DigAlarmread-onlymandatoryThe digital input 32 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2010ScalarfalconInput33DigAlarmread-onlymandatoryThe digital input 33 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2011ScalarfalconInput33HighAlarmread-onlymandatoryThe reading for sensor 33 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2012ScalarfalconInput33LowAlarmread-onlymandatoryThe reading for sensor 33 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2013ScalarfalconInput33High2Alarmread-onlymandatoryThe reading for sensor 33 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2014ScalarfalconInput33Low2Alarmread-onlymandatoryThe reading for sensor 33 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2020ScalarfalconInput34DigAlarmread-onlymandatoryThe digital input 34 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2021ScalarfalconInput34HighAlarmread-onlymandatoryThe reading for sensor 34 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2022ScalarfalconInput34LowAlarmread-onlymandatoryThe reading for sensor 34 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2023ScalarfalconInput34High2Alarmread-onlymandatoryThe reading for sensor 34 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2024ScalarfalconInput34Low2Alarmread-onlymandatoryThe reading for sensor 34 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2030ScalarfalconInput35DigAlarmread-onlymandatoryThe digital input 35 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2031ScalarfalconInput35HighAlarmread-onlymandatoryThe reading for sensor 35 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2032ScalarfalconInput35LowAlarmread-onlymandatoryThe reading for sensor 35 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2033ScalarfalconInput35High2Alarmread-onlymandatoryThe reading for sensor 35 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2034ScalarfalconInput35Low2Alarmread-onlymandatoryThe reading for sensor 35 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2040ScalarfalconInput36DigAlarmread-onlymandatoryThe digital input 36 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2041ScalarfalconInput36HighAlarmread-onlymandatoryThe reading for sensor 36 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2042ScalarfalconInput36LowAlarmread-onlymandatoryThe reading for sensor 36 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2043ScalarfalconInput36High2Alarmread-onlymandatoryThe reading for sensor 36 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2044ScalarfalconInput36Low2Alarmread-onlymandatoryThe reading for sensor 36 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2050ScalarfalconInput37DigAlarmread-onlymandatoryThe digital input 37 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2051ScalarfalconInput37HighAlarmread-onlymandatoryThe reading for sensor 37 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2052ScalarfalconInput37LowAlarmread-onlymandatoryThe reading for sensor 37 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2053ScalarfalconInput37High2Alarmread-onlymandatoryThe reading for sensor 37 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2054ScalarfalconInput37Low2Alarmread-onlymandatoryThe reading for sensor 37 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2060ScalarfalconInput38DigAlarmread-onlymandatoryThe digital input 38 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2061ScalarfalconInput38HighAlarmread-onlymandatoryThe reading for sensor 38 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2062ScalarfalconInput38LowAlarmread-onlymandatoryThe reading for sensor 38 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2063ScalarfalconInput38High2Alarmread-onlymandatoryThe reading for sensor 38 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2064ScalarfalconInput38Low2Alarmread-onlymandatoryThe reading for sensor 38 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2070ScalarfalconInput39DigAlarmread-onlymandatoryThe digital input 39 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2071ScalarfalconInput39HighAlarmread-onlymandatoryThe reading for sensor 39 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2072ScalarfalconInput39LowAlarmread-onlymandatoryThe reading for sensor 39 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2073ScalarfalconInput39High2Alarmread-onlymandatoryThe reading for sensor 39 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2074ScalarfalconInput39Low2Alarmread-onlymandatoryThe reading for sensor 39 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2080ScalarfalconInput40DigAlarmread-onlymandatoryThe digital input 40 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2081ScalarfalconInput40HighAlarmread-onlymandatoryThe reading for sensor 40 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2082ScalarfalconInput40LowAlarmread-onlymandatoryThe reading for sensor 40 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2083ScalarfalconInput40High2Alarmread-onlymandatoryThe reading for sensor 40 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2084ScalarfalconInput40Low2Alarmread-onlymandatoryThe reading for sensor 40 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2090ScalarfalconInput41DigAlarmread-onlymandatoryThe digital input 41 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2091ScalarfalconInput41HighAlarmread-onlymandatoryThe reading for sensor 41 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2092ScalarfalconInput41LowAlarmread-onlymandatoryThe reading for sensor 41 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2093ScalarfalconInput41High2Alarmread-onlymandatoryThe reading for sensor 41 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2094ScalarfalconInput41Low2Alarmread-onlymandatoryThe reading for sensor 41 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2100ScalarfalconInput42DigAlarmread-onlymandatoryThe digital input 42 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2101ScalarfalconInput42HighAlarmread-onlymandatoryThe reading for sensor 42 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2102ScalarfalconInput42LowAlarmread-onlymandatoryThe reading for sensor 42 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2103ScalarfalconInput42High2Alarmread-onlymandatoryThe reading for sensor 42 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2104ScalarfalconInput42Low2Alarmread-onlymandatoryThe reading for sensor 42 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2110ScalarfalconInput43DigAlarmread-onlymandatoryThe digital input 43 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2111ScalarfalconInput43HighAlarmread-onlymandatoryThe reading for sensor 43 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2112ScalarfalconInput43LowAlarmread-onlymandatoryThe reading for sensor 43 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2113ScalarfalconInput43High2Alarmread-onlymandatoryThe reading for sensor 43 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2114ScalarfalconInput43Low2Alarmread-onlymandatoryThe reading for sensor 43 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2120ScalarfalconInput44DigAlarmread-onlymandatoryThe digital input 44 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2121ScalarfalconInput44HighAlarmread-onlymandatoryThe reading for sensor 44 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2122ScalarfalconInput44LowAlarmread-onlymandatoryThe reading for sensor 44 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2123ScalarfalconInput44High2Alarmread-onlymandatoryThe reading for sensor 44 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2124ScalarfalconInput44Low2Alarmread-onlymandatoryThe reading for sensor 44 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.2130ScalarfalconInput45DigAlarmread-onlymandatoryThe digital input 45 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2140ScalarfalconInput46DigAlarmread-onlymandatoryThe digital input 46 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2150ScalarfalconInput47DigAlarmread-onlymandatoryThe digital input 47 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2160ScalarfalconInput48DigAlarmread-onlymandatoryThe digital input 48 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2170ScalarfalconInput49DigAlarmread-onlymandatoryThe digital input 49 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2180ScalarfalconInput50DigAlarmread-onlymandatoryThe digital input 50 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2190ScalarfalconInput51DigAlarmread-onlymandatoryThe digital input 51 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2200ScalarfalconInput52DigAlarmread-onlymandatoryThe digital input 52 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2210ScalarfalconInput53DigAlarmread-onlymandatoryThe digital input 53 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2220ScalarfalconInput54DigAlarmread-onlymandatoryThe digital input 54 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2230ScalarfalconInput55DigAlarmread-onlymandatoryThe digital input 55 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.2240ScalarfalconInput56DigAlarmread-onlymandatoryThe digital input 56 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3010ScalarfalconInput57DigAlarmread-onlymandatoryThe digital input 57 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3011ScalarfalconInput57HighAlarmread-onlymandatoryThe reading for sensor 57 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3012ScalarfalconInput57LowAlarmread-onlymandatoryThe reading for sensor 57 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3013ScalarfalconInput57High2Alarmread-onlymandatoryThe reading for sensor 57 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3014ScalarfalconInput57Low2Alarmread-onlymandatoryThe reading for sensor 57 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3020ScalarfalconInput58DigAlarmread-onlymandatoryThe digital input 58 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3021ScalarfalconInput58HighAlarmread-onlymandatoryThe reading for sensor 58 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3022ScalarfalconInput58LowAlarmread-onlymandatoryThe reading for sensor 58 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3023ScalarfalconInput58High2Alarmread-onlymandatoryThe reading for sensor 58 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3024ScalarfalconInput58Low2Alarmread-onlymandatoryThe reading for sensor 58 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3030ScalarfalconInput59DigAlarmread-onlymandatoryThe digital input 59 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3031ScalarfalconInput59HighAlarmread-onlymandatoryThe reading for sensor 59 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3032ScalarfalconInput59LowAlarmread-onlymandatoryThe reading for sensor 59 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3033ScalarfalconInput59High2Alarmread-onlymandatoryThe reading for sensor 59 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3034ScalarfalconInput59Low2Alarmread-onlymandatoryThe reading for sensor 59 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3040ScalarfalconInput60DigAlarmread-onlymandatoryThe digital input 60 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3041ScalarfalconInput60HighAlarmread-onlymandatoryThe reading for sensor 60 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3042ScalarfalconInput60LowAlarmread-onlymandatoryThe reading for sensor 60 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3043ScalarfalconInput60High2Alarmread-onlymandatoryThe reading for sensor 60 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3044ScalarfalconInput60Low2Alarmread-onlymandatoryThe reading for sensor 60 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3050ScalarfalconInput61DigAlarmread-onlymandatoryThe digital input 61 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3051ScalarfalconInput61HighAlarmread-onlymandatoryThe reading for sensor 61 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3052ScalarfalconInput61LowAlarmread-onlymandatoryThe reading for sensor 61 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3053ScalarfalconInput61High2Alarmread-onlymandatoryThe reading for sensor 61 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3054ScalarfalconInput61Low2Alarmread-onlymandatoryThe reading for sensor 61 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3060ScalarfalconInput62DigAlarmread-onlymandatoryThe digital input 62 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3061ScalarfalconInput62HighAlarmread-onlymandatoryThe reading for sensor 62 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3062ScalarfalconInput62LowAlarmread-onlymandatoryThe reading for sensor 62 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3063ScalarfalconInput62High2Alarmread-onlymandatoryThe reading for sensor 62 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3064ScalarfalconInput62Low2Alarmread-onlymandatoryThe reading for sensor 62 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3070ScalarfalconInput63DigAlarmread-onlymandatoryThe digital input 63 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3071ScalarfalconInput63HighAlarmread-onlymandatoryThe reading for sensor 63 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3072ScalarfalconInput63LowAlarmread-onlymandatoryThe reading for sensor 63 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3073ScalarfalconInput63High2Alarmread-onlymandatoryThe reading for sensor 63 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3074ScalarfalconInput63Low2Alarmread-onlymandatoryThe reading for sensor 63 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3080ScalarfalconInput64DigAlarmread-onlymandatoryThe digital input 64 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3081ScalarfalconInput64HighAlarmread-onlymandatoryThe reading for sensor 64 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3082ScalarfalconInput64LowAlarmread-onlymandatoryThe reading for sensor 64 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3083ScalarfalconInput64High2Alarmread-onlymandatoryThe reading for sensor 64 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3084ScalarfalconInput64Low2Alarmread-onlymandatoryThe reading for sensor 64 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3090ScalarfalconInput65DigAlarmread-onlymandatoryThe digital input 65 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3091ScalarfalconInput65HighAlarmread-onlymandatoryThe reading for sensor 65 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3092ScalarfalconInput65LowAlarmread-onlymandatoryThe reading for sensor 65 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3093ScalarfalconInput65High2Alarmread-onlymandatoryThe reading for sensor 65 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3094ScalarfalconInput65Low2Alarmread-onlymandatoryThe reading for sensor 65 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3100ScalarfalconInput66DigAlarmread-onlymandatoryThe digital input 66 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3101ScalarfalconInput66HighAlarmread-onlymandatoryThe reading for sensor 66 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3102ScalarfalconInput66LowAlarmread-onlymandatoryThe reading for sensor 66 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3103ScalarfalconInput66High2Alarmread-onlymandatoryThe reading for sensor 66 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3104ScalarfalconInput66Low2Alarmread-onlymandatoryThe reading for sensor 66 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3110ScalarfalconInput67DigAlarmread-onlymandatoryThe digital input 67 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3111ScalarfalconInput67HighAlarmread-onlymandatoryThe reading for sensor 67 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3112ScalarfalconInput67LowAlarmread-onlymandatoryThe reading for sensor 67 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3113ScalarfalconInput67High2Alarmread-onlymandatoryThe reading for sensor 67 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3114ScalarfalconInput67Low2Alarmread-onlymandatoryThe reading for sensor 67 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3120ScalarfalconInput68DigAlarmread-onlymandatoryThe digital input 68 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3121ScalarfalconInput68HighAlarmread-onlymandatoryThe reading for sensor 68 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3122ScalarfalconInput68LowAlarmread-onlymandatoryThe reading for sensor 68 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3123ScalarfalconInput68High2Alarmread-onlymandatoryThe reading for sensor 68 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3124ScalarfalconInput68Low2Alarmread-onlymandatoryThe reading for sensor 68 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.3130ScalarfalconInput69DigAlarmread-onlymandatoryThe digital input 69 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3140ScalarfalconInput70DigAlarmread-onlymandatoryThe digital input 70 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3150ScalarfalconInput71DigAlarmread-onlymandatoryThe digital input 71 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3160ScalarfalconInput72DigAlarmread-onlymandatoryThe digital input 72 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3170ScalarfalconInput73DigAlarmread-onlymandatoryThe digital input 73 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3180ScalarfalconInput74DigAlarmread-onlymandatoryThe digital input 74 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3190ScalarfalconInput75DigAlarmread-onlymandatoryThe digital input 75 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3200ScalarfalconInput76DigAlarmread-onlymandatoryThe digital input 76 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3210ScalarfalconInput77DigAlarmread-onlymandatoryThe digital input 77 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3220ScalarfalconInput78DigAlarmread-onlymandatoryThe digital input 78 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3230ScalarfalconInput79DigAlarmread-onlymandatoryThe digital input 79 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.3240ScalarfalconInput80DigAlarmread-onlymandatoryThe digital input 80 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4010ScalarfalconInput81DigAlarmread-onlymandatoryThe digital input 81 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4011ScalarfalconInput81HighAlarmread-onlymandatoryThe reading for sensor 81 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4012ScalarfalconInput81LowAlarmread-onlymandatoryThe reading for sensor 81 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4013ScalarfalconInput81High2Alarmread-onlymandatoryThe reading for sensor 81 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4014ScalarfalconInput81Low2Alarmread-onlymandatoryThe reading for sensor 81 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4020ScalarfalconInput82DigAlarmread-onlymandatoryThe digital input 82 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4021ScalarfalconInput82HighAlarmread-onlymandatoryThe reading for sensor 82 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4022ScalarfalconInput82LowAlarmread-onlymandatoryThe reading for sensor 82 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4023ScalarfalconInput82High2Alarmread-onlymandatoryThe reading for sensor 82 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4024ScalarfalconInput82Low2Alarmread-onlymandatoryThe reading for sensor 82 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4030ScalarfalconInput83DigAlarmread-onlymandatoryThe digital input 83 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4031ScalarfalconInput83HighAlarmread-onlymandatoryThe reading for sensor 83 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4032ScalarfalconInput83LowAlarmread-onlymandatoryThe reading for sensor 83 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4033ScalarfalconInput83High2Alarmread-onlymandatoryThe reading for sensor 83 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4034ScalarfalconInput83Low2Alarmread-onlymandatoryThe reading for sensor 83 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4040ScalarfalconInput84DigAlarmread-onlymandatoryThe digital input 84 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4041ScalarfalconInput84HighAlarmread-onlymandatoryThe reading for sensor 84 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4042ScalarfalconInput84LowAlarmread-onlymandatoryThe reading for sensor 84 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4043ScalarfalconInput84High2Alarmread-onlymandatoryThe reading for sensor 84 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4044ScalarfalconInput84Low2Alarmread-onlymandatoryThe reading for sensor 84 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4050ScalarfalconInput85DigAlarmread-onlymandatoryThe digital input 85 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4051ScalarfalconInput85HighAlarmread-onlymandatoryThe reading for sensor 85 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4052ScalarfalconInput85LowAlarmread-onlymandatoryThe reading for sensor 85 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4053ScalarfalconInput85High2Alarmread-onlymandatoryThe reading for sensor 85 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4054ScalarfalconInput85Low2Alarmread-onlymandatoryThe reading for sensor 85 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4060ScalarfalconInput86DigAlarmread-onlymandatoryThe digital input 86 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4061ScalarfalconInput86HighAlarmread-onlymandatoryThe reading for sensor 86 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4062ScalarfalconInput86LowAlarmread-onlymandatoryThe reading for sensor 86 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4063ScalarfalconInput86High2Alarmread-onlymandatoryThe reading for sensor 86 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4064ScalarfalconInput86Low2Alarmread-onlymandatoryThe reading for sensor 86 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4070ScalarfalconInput87DigAlarmread-onlymandatoryThe digital input 87 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4071ScalarfalconInput87HighAlarmread-onlymandatoryThe reading for sensor 87 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4072ScalarfalconInput87LowAlarmread-onlymandatoryThe reading for sensor 87 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4073ScalarfalconInput87High2Alarmread-onlymandatoryThe reading for sensor 87 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4074ScalarfalconInput87Low2Alarmread-onlymandatoryThe reading for sensor 87 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4080ScalarfalconInput88DigAlarmread-onlymandatoryThe digital input 88 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4081ScalarfalconInput88HighAlarmread-onlymandatoryThe reading for sensor 88 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4082ScalarfalconInput88LowAlarmread-onlymandatoryThe reading for sensor 88 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4083ScalarfalconInput88High2Alarmread-onlymandatoryThe reading for sensor 88 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4084ScalarfalconInput88Low2Alarmread-onlymandatoryThe reading for sensor 88 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4090ScalarfalconInput89DigAlarmread-onlymandatoryThe digital input 89 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4091ScalarfalconInput89HighAlarmread-onlymandatoryThe reading for sensor 89 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4092ScalarfalconInput89LowAlarmread-onlymandatoryThe reading for sensor 89 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4093ScalarfalconInput89High2Alarmread-onlymandatoryThe reading for sensor 89 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4094ScalarfalconInput89Low2Alarmread-onlymandatoryThe reading for sensor 89 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4100ScalarfalconInput90DigAlarmread-onlymandatoryThe digital input 90 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4101ScalarfalconInput90HighAlarmread-onlymandatoryThe reading for sensor 90 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4102ScalarfalconInput90LowAlarmread-onlymandatoryThe reading for sensor 90 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4103ScalarfalconInput90High2Alarmread-onlymandatoryThe reading for sensor 90 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4104ScalarfalconInput90Low2Alarmread-onlymandatoryThe reading for sensor 90 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4110ScalarfalconInput91DigAlarmread-onlymandatoryThe digital input 91 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4111ScalarfalconInput91HighAlarmread-onlymandatoryThe reading for sensor 91 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4112ScalarfalconInput91LowAlarmread-onlymandatoryThe reading for sensor 91 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4113ScalarfalconInput91High2Alarmread-onlymandatoryThe reading for sensor 91 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4114ScalarfalconInput91Low2Alarmread-onlymandatoryThe reading for sensor 91 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4120ScalarfalconInput92DigAlarmread-onlymandatoryThe digital input 92 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4121ScalarfalconInput92HighAlarmread-onlymandatoryThe reading for sensor 92 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4122ScalarfalconInput92LowAlarmread-onlymandatoryThe reading for sensor 92 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4123ScalarfalconInput92High2Alarmread-onlymandatoryThe reading for sensor 92 has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4124ScalarfalconInput92Low2Alarmread-onlymandatoryThe reading for sensor 92 has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.4130ScalarfalconInput93DigAlarmread-onlymandatoryThe digital input 93 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4140ScalarfalconInput94DigAlarmread-onlymandatoryThe digital input 94 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4150ScalarfalconInput95DigAlarmread-onlymandatoryThe digital input 95 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4160ScalarfalconInput96DigAlarmread-onlymandatoryThe digital input 96 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4170ScalarfalconInput97DigAlarmread-onlymandatoryThe digital input 97 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4180ScalarfalconInput98DigAlarmread-onlymandatoryThe digital input 98 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4190ScalarfalconInput99DigAlarmread-onlymandatoryThe digital input 99 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4200ScalarfalconInput100DigAlarmread-onlymandatoryThe digital input 100 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4210ScalarfalconInput101DigAlarmread-onlymandatoryThe digital input 101 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4220ScalarfalconInput102DigAlarmread-onlymandatoryThe digital input 102 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4230ScalarfalconInput103DigAlarmread-onlymandatoryThe digital input 103 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.4240ScalarfalconInput104DigAlarmread-onlymandatoryThe digital input 104 has been activated.
1.3.6.1.4.1.3184.1.5.1.5.3.5011ScalarfalconTemperatureSensorHighAlarmread-onlymandatoryThe reading for internal temperature sensor has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5012ScalarfalconTemperatureSensorLowAlarmread-onlymandatoryThe reading for internal temperature sensor has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5013ScalarfalconTemperatureSensorHigh2Alarmread-onlymandatoryThe reading for internal temperature sensor has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5014ScalarfalconTemperatureSensorLow2Alarmread-onlymandatoryThe reading for internal temperature sensor has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5021ScalarfalconHumiditySensorHighAlarmread-onlymandatoryThe reading for internal humidity sensor has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5022ScalarfalconHumiditySensorLowAlarmread-onlymandatoryThe reading for internal humidity sensor has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5023ScalarfalconHumiditySensorHigh2Alarmread-onlymandatoryThe reading for internal humidity sensor has reached the high limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.5024ScalarfalconHumiditySensorLow2Alarmread-onlymandatoryThe reading for internal humidity sensor has reached the low limit value.
1.3.6.1.4.1.3184.1.5.1.5.3.6010ScalarfalconLowBatteryAlarmread-onlymandatoryThe Faclon has detected a low battery condition.
1.3.6.1.4.1.3184.1.5.1.6NodefalconTraps
1.3.6.1.4.1.3184.1.5.1.6.1NodefalconAlarmEntryAddedAn AlarmEntryAdded Trap signifies that the a sensor reading has reached a high or low limit value.
1.3.6.1.4.1.3184.1.5.1.6.2NodefalconAlarmEntryRemovedAn AlarmEntryAdded Trap signifies that the a sensor reading has gone below the high limit value or above the low limit value.
1.3.6.1.4.1.3184.1.5.1.6.3NodefalconAccessGrantedAn falconAccessGranted Trap signifies that a valid key code sequence was processed by the falcon.
1.3.6.1.4.1.3184.1.5.1.6.4NodefalconAccessDeniedAn falconAccessedDenied Trap signifies that an invalid key code sequence was processed by the falcon.
1.3.6.1.4.1.3184.1.5.1.6.5NodefalconPageUnsuccessfulAn falconPageUnsuccessful Trap signifies that an alpha numeric page could not be sent to the service.
1.3.6.1.4.1.3184.1.5.1.6.6NodefalconConfigurationChangedA falconConfigurationChanged Trap is sent upon configuration changhes made to the falcon via a web page.
1.3.6.1.4.1.3184.1.5.1.7NodefalconAlarmHistory
1.3.6.1.4.1.3184.1.5.1.7.1ScalarfalconAlarmHistoryEntriesread-onlymandatoryThe present number of entries in the alarm history.
1.3.6.1.4.1.3184.1.5.1.7.2ScalarfalconAlarmHistoryClearread-writemandatorySetting this value to ClearBuffer(1) will clear the alarm history buffer.
1.3.6.1.4.1.3184.1.5.1.7.3TablefalconAlarmHistoryTablenot-accessiblemandatoryA list of alarm history table entries stored in the in the non-volatile memory. The table contains zero, one, or many rows at any moment, depending upon the nu…
1.3.6.1.4.1.3184.1.5.1.7.3.1RowfalconAlarmHistoryEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm history entry.
1.3.6.1.4.1.3184.1.5.1.7.3.1.1ColumnfalconAlarmHistoryIdnot-accessiblemandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.3184.1.5.1.7.3.1.2ColumnfalconAlarmHistoryTextread-onlymandatoryA text desciption of the alarm history entry. Each of the strings will have the following format, AHxxx-id-type-timestamp label xxx = number entry in the table…
1.3.6.1.4.1.3184.1.5.1.8NodefalconTrapSettings
1.3.6.1.4.1.3184.1.5.1.8.1ScalarfalconPersistantTrapsread-writemandatoryThe number of minutes between persistant traps. Set this to 0 to turn off persistant traps.
1.3.6.1.4.1.3184.1.5.1.8.2ScalarfalconAlarmAcknowledgeread-writemandatorySetting this value to AcknowledgeAlarms(1) will stop the falcon from sending persistant traps and dial out sequences.
1.3.6.1.4.1.3184.1.5.1.9NodefalconSchedules
1.3.6.1.4.1.3184.1.5.1.9.1ScalarfalconScheduleABeginDOWread-writemandatoryThe beginning day of the week for schedule A.
1.3.6.1.4.1.3184.1.5.1.9.2ScalarfalconScheduleAEndDOWread-writemandatoryThe ending day of the week for schedule A.
1.3.6.1.4.1.3184.1.5.1.9.3ScalarfalconScheduleABeginTimeread-writemandatoryThe schedule A beginning time of day. Displayed as HH:MM
1.3.6.1.4.1.3184.1.5.1.9.4ScalarfalconScheduleAEndTimeread-writemandatoryThe schedule A ending time of day. Displayed as HH:MM
1.3.6.1.4.1.3184.1.5.1.9.5ScalarfalconScheduleBBeginDOWread-writemandatoryThe beginning day of the week for schedule B.
1.3.6.1.4.1.3184.1.5.1.9.6ScalarfalconScheduleBEndDOWread-writemandatoryThe ending day of the week for schedule B.
1.3.6.1.4.1.3184.1.5.1.9.7ScalarfalconScheduleBBeginTimeread-writemandatoryThe schedule B beginning time of day. Displayed as HH:MM
1.3.6.1.4.1.3184.1.5.1.9.8ScalarfalconScheduleBEndTimeread-writemandatoryThe schedule B ending time of day. Displayed as HH:MM
1.3.6.1.4.1.3184.1.5.1.10NodefalconPortTrap
1.3.6.1.4.1.3184.1.5.1.10.1NodefalconPort01TrapThe sensor on port #01 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.2NodefalconPort02TrapThe sensor on port #02 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.3NodefalconPort03TrapThe sensor on port #03 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.4NodefalconPort04TrapThe sensor on port #04 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.5NodefalconPort05TrapThe sensor on port #05 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.6NodefalconPort06TrapThe sensor on port #06 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.7NodefalconPort07TrapThe sensor on port #07 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.8NodefalconPort08TrapThe sensor on port #08 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.9NodefalconPort09TrapThe sensor on port #09 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.10NodefalconPort10TrapThe sensor on port #10 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.11NodefalconPort11TrapThe sensor on port #11 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.12NodefalconPort12TrapThe sensor on port #12 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.13NodefalconPort13TrapThe sensor on port #13 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.14NodefalconPort14TrapThe sensor on port #14 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.15NodefalconPort15TrapThe sensor on port #15 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.16NodefalconPort16TrapThe sensor on port #16 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.17NodefalconPort17TrapThe sensor on port #17 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.18NodefalconPort18TrapThe sensor on port #18 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.19NodefalconPort19TrapThe sensor on port #19 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.20NodefalconPort20TrapThe sensor on port #20 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.21NodefalconPort21TrapThe sensor on port #21 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.22NodefalconPort22TrapThe sensor on port #22 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.23NodefalconPort23TrapThe sensor on port #23 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.24NodefalconPort24TrapThe sensor on port #24 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.25NodefalconPort25TrapThe sensor on port #25 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.26NodefalconPort26TrapThe sensor on port #26 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.27NodefalconPort27TrapThe sensor on port #27 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.28NodefalconPort28TrapThe sensor on port #28 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.29NodefalconPort29TrapThe sensor on port #29 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.30NodefalconPort30TrapThe sensor on port #30 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.31NodefalconPort31TrapThe sensor on port #31 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.32NodefalconPort32TrapThe sensor on port #32 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.33NodefalconPort33TrapThe sensor on port #33 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.34NodefalconPort34TrapThe sensor on port #34 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.35NodefalconPort35TrapThe sensor on port #35 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.36NodefalconPort36TrapThe sensor on port #36 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.37NodefalconPort37TrapThe sensor on port #37 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.38NodefalconPort38TrapThe sensor on port #38 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.39NodefalconPort39TrapThe sensor on port #39 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.40NodefalconPort40TrapThe sensor on port #40 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.41NodefalconPort41TrapThe sensor on port #41 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.42NodefalconPort42TrapThe sensor on port #42 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.43NodefalconPort43TrapThe sensor on port #43 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.44NodefalconPort44TrapThe sensor on port #44 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.45NodefalconPort45TrapThe sensor on port #45 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.46NodefalconPort46TrapThe sensor on port #46 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.47NodefalconPort47TrapThe sensor on port #47 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.48NodefalconPort48TrapThe sensor on port #48 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.49NodefalconPort49TrapThe sensor on port #49 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.50NodefalconPort50TrapThe sensor on port #50 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.51NodefalconPort51TrapThe sensor on port #51 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.52NodefalconPort52TrapThe sensor on port #52 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.53NodefalconPort53TrapThe sensor on port #53 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.54NodefalconPort54TrapThe sensor on port #54 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.55NodefalconPort55TrapThe sensor on port #55 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.56NodefalconPort56TrapThe sensor on port #56 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.57NodefalconPort57TrapThe sensor on port #57 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.58NodefalconPort58TrapThe sensor on port #58 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.59NodefalconPort59TrapThe sensor on port #59 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.60NodefalconPort60TrapThe sensor on port #60 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.61NodefalconPort61TrapThe sensor on port #61 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.62NodefalconPort62TrapThe sensor on port #62 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.63NodefalconPort63TrapThe sensor on port #63 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.64NodefalconPort64TrapThe sensor on port #64 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.65NodefalconPort65TrapThe sensor on port #65 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.66NodefalconPort66TrapThe sensor on port #66 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.67NodefalconPort67TrapThe sensor on port #67 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.68NodefalconPort68TrapThe sensor on port #68 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.69NodefalconPort69TrapThe sensor on port #69 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.70NodefalconPort70TrapThe sensor on port #70 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.71NodefalconPort71TrapThe sensor on port #71 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.72NodefalconPort72TrapThe sensor on port #72 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.73NodefalconPort73TrapThe sensor on port #73 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.74NodefalconPort74TrapThe sensor on port #74 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.75NodefalconPort75TrapThe sensor on port #75 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.76NodefalconPort76TrapThe sensor on port #76 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.77NodefalconPort77TrapThe sensor on port #77 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.78NodefalconPort78TrapThe sensor on port #78 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.79NodefalconPort79TrapThe sensor on port #79 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.80NodefalconPort80TrapThe sensor on port #80 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.81NodefalconPort81TrapThe sensor on port #81 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.82NodefalconPort82TrapThe sensor on port #82 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.83NodefalconPort83TrapThe sensor on port #83 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.84NodefalconPort84TrapThe sensor on port #84 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.85NodefalconPort85TrapThe sensor on port #85 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.86NodefalconPort86TrapThe sensor on port #86 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.87NodefalconPort87TrapThe sensor on port #87 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.88NodefalconPort88TrapThe sensor on port #88 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.89NodefalconPort89TrapThe sensor on port #89 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.90NodefalconPort90TrapThe sensor on port #90 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.91NodefalconPort91TrapThe sensor on port #91 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.92NodefalconPort92TrapThe sensor on port #92 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.93NodefalconPort93TrapThe sensor on port #93 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.94NodefalconPort94TrapThe sensor on port #94 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.95NodefalconPort95TrapThe sensor on port #95 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.96NodefalconPort96TrapThe sensor on port #96 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.97NodefalconPort97TrapThe sensor on port #97 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.98NodefalconPort98TrapThe sensor on port #98 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.99NodefalconPort99TrapThe sensor on port #99 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.100NodefalconPort100TrapThe sensor on port #100 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.101NodefalconPort101TrapThe sensor on port #101 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.102NodefalconPort102TrapThe sensor on port #102 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.103NodefalconPort103TrapThe sensor on port #103 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.104NodefalconPort104TrapThe sensor on port #104 has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.105NodefalconTemperatureSensorTrapThe internal temperature sensor has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.10.106NodefalconHumiditySensorTrapThe internal Humidity sensor has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.11NodefalconPortTrapClear
1.3.6.1.4.1.3184.1.5.1.11.1NodefalconPort01TrapClearThe sensor on port #01 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.2NodefalconPort02TrapClearThe sensor on port #02 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.3NodefalconPort03TrapClearThe sensor on port #03 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.4NodefalconPort04TrapClearThe sensor on port #04 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.5NodefalconPort05TrapClearThe sensor on port #05 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.6NodefalconPort06TrapClearThe sensor on port #06 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.7NodefalconPort07TrapClearThe sensor on port #07 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.8NodefalconPort08TrapClearThe sensor on port #08 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.9NodefalconPort09TrapClearThe sensor on port #09 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.10NodefalconPort10TrapClearThe sensor on port #10 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.11NodefalconPort11TrapClearThe sensor on port #11 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.12NodefalconPort12TrapClearThe sensor on port #12 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.13NodefalconPort13TrapClearThe sensor on port #13 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.14NodefalconPort14TrapClearThe sensor on port #14 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.15NodefalconPort15TrapClearThe sensor on port #15 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.16NodefalconPort16TrapClearThe sensor on port #16 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.17NodefalconPort17TrapClearThe sensor on port #17 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.18NodefalconPort18TrapClearThe sensor on port #18 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.19NodefalconPort19TrapClearThe sensor on port #19 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.20NodefalconPort20TrapClearThe sensor on port #20 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.21NodefalconPort21TrapClearThe sensor on port #21 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.22NodefalconPort22TrapClearThe sensor on port #22 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.23NodefalconPort23TrapClearThe sensor on port #23 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.24NodefalconPort24TrapClearThe sensor on port #24 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.25NodefalconPort25TrapClearThe sensor on port #25 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.26NodefalconPort26TrapClearThe sensor on port #26 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.27NodefalconPort27TrapClearThe sensor on port #27 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.28NodefalconPort28TrapClearThe sensor on port #28 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.29NodefalconPort29TrapClearThe sensor on port #29 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.30NodefalconPort30TrapClearThe sensor on port #30 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.31NodefalconPort31TrapClearThe sensor on port #31 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.32NodefalconPort32TrapClearThe sensor on port #32 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.33NodefalconPort33TrapClearThe sensor on port #33 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.34NodefalconPort34TrapClearThe sensor on port #34 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.35NodefalconPort35TrapClearThe sensor on port #35 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.36NodefalconPort36TrapClearThe sensor on port #36 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.37NodefalconPort37TrapClearThe sensor on port #37 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.38NodefalconPort38TrapClearThe sensor on port #38 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.39NodefalconPort39TrapClearThe sensor on port #39 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.40NodefalconPort40TrapClearThe sensor on port #40 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.41NodefalconPort41TrapClearThe sensor on port #41 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.42NodefalconPort42TrapClearThe sensor on port #42 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.43NodefalconPort43TrapClearThe sensor on port #43 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.44NodefalconPort44TrapClearThe sensor on port #44 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.45NodefalconPort45TrapClearThe sensor on port #45 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.46NodefalconPort46TrapClearThe sensor on port #46 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.47NodefalconPort47TrapClearThe sensor on port #47 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.48NodefalconPort48TrapClearThe sensor on port #48 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.49NodefalconPort49TrapClearThe sensor on port #49 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.50NodefalconPort50TrapClearThe sensor on port #50 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.51NodefalconPort51TrapClearThe sensor on port #51 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.52NodefalconPort52TrapClearThe sensor on port #52 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.53NodefalconPort53TrapClearThe sensor on port #53 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.54NodefalconPort54TrapClearThe sensor on port #54 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.55NodefalconPort55TrapClearThe sensor on port #55 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.56NodefalconPort56TrapClearThe sensor on port #56 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.57NodefalconPort57TrapClearThe sensor on port #57 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.58NodefalconPort58TrapClearThe sensor on port #58 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.59NodefalconPort59TrapClearThe sensor on port #59 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.60NodefalconPort60TrapClearThe sensor on port #60 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.61NodefalconPort61TrapClearThe sensor on port #61 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.62NodefalconPort62TrapClearThe sensor on port #62 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.63NodefalconPort63TrapClearThe sensor on port #63 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.64NodefalconPort64TrapClearThe sensor on port #64 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.65NodefalconPort65TrapClearThe sensor on port #65 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.66NodefalconPort66TrapClearThe sensor on port #66 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.67NodefalconPort67TrapClearThe sensor on port #67 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.68NodefalconPort68TrapClearThe sensor on port #68 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.69NodefalconPort69TrapClearThe sensor on port #69 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.70NodefalconPort70TrapClearThe sensor on port #70 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.71NodefalconPort71TrapClearThe sensor on port #71 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.72NodefalconPort72TrapClearThe sensor on port #72 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.73NodefalconPort73TrapClearThe sensor on port #73 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.74NodefalconPort74TrapClearThe sensor on port #74 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.75NodefalconPort75TrapClearThe sensor on port #75 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.76NodefalconPort76TrapClearThe sensor on port #76 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.77NodefalconPort77TrapClearThe sensor on port #77 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.78NodefalconPort78TrapClearThe sensor on port #78 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.79NodefalconPort79TrapClearThe sensor on port #79 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.80NodefalconPort80TrapClearThe sensor on port #80 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.81NodefalconPort81TrapClearThe sensor on port #81 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.82NodefalconPort82TrapClearThe sensor on port #82 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.83NodefalconPort83TrapClearThe sensor on port #83 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.84NodefalconPort84TrapClearThe sensor on port #84 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.85NodefalconPort85TrapClearThe sensor on port #85 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.86NodefalconPort86TrapClearThe sensor on port #86 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.87NodefalconPort87TrapClearThe sensor on port #87 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.88NodefalconPort88TrapClearThe sensor on port #88 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.89NodefalconPort89TrapClearThe sensor on port #89 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.90NodefalconPort90TrapClearThe sensor on port #90 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.91NodefalconPort91TrapClearThe sensor on port #91 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.92NodefalconPort92TrapClearThe sensor on port #92 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.93NodefalconPort93TrapClearThe sensor on port #93 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.94NodefalconPort94TrapClearThe sensor on port #94 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.95NodefalconPort95TrapClearThe sensor on port #95 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.96NodefalconPort96TrapClearThe sensor on port #96 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.97NodefalconPort97TrapClearThe sensor on port #97 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.98NodefalconPort98TrapClearThe sensor on port #98 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.99NodefalconPort99TrapClearThe sensor on port #99 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.100NodefalconPort100TrapClearThe sensor on port #100 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.101NodefalconPort101TrapClearThe sensor on port #101 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.102NodefalconPort102TrapClearThe sensor on port #102 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.103NodefalconPort103TrapClearThe sensor on port #103 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.104NodefalconPort104TrapClearThe sensor on port #104 has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.105NodefalconTemperatureSensorTrapClearThe internal temperature sensor has returned to normal.
1.3.6.1.4.1.3184.1.5.1.11.106NodefalconHumiditySensorTrapClearThe internal Humidity sensor has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12NodefalconXbus
1.3.6.1.4.1.3184.1.5.1.12.1NodefalconBCMs
1.3.6.1.4.1.3184.1.5.1.12.1.1NodefalconBCM01
1.3.6.1.4.1.3184.1.5.1.12.1.1.1ScalarfalconBCM01Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2TablefalconBCM01CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2.1RowfalconBCM01CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2.1.1ColumnfalconBCM01CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2.1.2ColumnfalconBCM01CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2.1.3ColumnfalconBCM01CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.1.2.1.4ColumnfalconBCM01CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.2NodefalconBCM02
1.3.6.1.4.1.3184.1.5.1.12.1.2.1ScalarfalconBCM02Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2TablefalconBCM02CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2.1RowfalconBCM02CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2.1.1ColumnfalconBCM02CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2.1.2ColumnfalconBCM02CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2.1.3ColumnfalconBCM02CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.2.2.1.4ColumnfalconBCM02CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.3NodefalconBCM03
1.3.6.1.4.1.3184.1.5.1.12.1.3.1ScalarfalconBCM03Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2TablefalconBCM03CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2.1RowfalconBCM03CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2.1.1ColumnfalconBCM03CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2.1.2ColumnfalconBCM03CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2.1.3ColumnfalconBCM03CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.3.2.1.4ColumnfalconBCM03CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.4NodefalconBCM04
1.3.6.1.4.1.3184.1.5.1.12.1.4.1ScalarfalconBCM04Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2TablefalconBCM04CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2.1RowfalconBCM04CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2.1.1ColumnfalconBCM04CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2.1.2ColumnfalconBCM04CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2.1.3ColumnfalconBCM04CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.4.2.1.4ColumnfalconBCM04CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.5NodefalconBCM05
1.3.6.1.4.1.3184.1.5.1.12.1.5.1ScalarfalconBCM05Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2TablefalconBCM05CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2.1RowfalconBCM05CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2.1.1ColumnfalconBCM05CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2.1.2ColumnfalconBCM05CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2.1.3ColumnfalconBCM05CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.5.2.1.4ColumnfalconBCM05CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.6NodefalconBCM06
1.3.6.1.4.1.3184.1.5.1.12.1.6.1ScalarfalconBCM06Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2TablefalconBCM06CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2.1RowfalconBCM06CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2.1.1ColumnfalconBCM06CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2.1.2ColumnfalconBCM06CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2.1.3ColumnfalconBCM06CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.6.2.1.4ColumnfalconBCM06CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.7NodefalconBCM07
1.3.6.1.4.1.3184.1.5.1.12.1.7.1ScalarfalconBCM07Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2TablefalconBCM07CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2.1RowfalconBCM07CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2.1.1ColumnfalconBCM07CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2.1.2ColumnfalconBCM07CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2.1.3ColumnfalconBCM07CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.7.2.1.4ColumnfalconBCM07CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.8NodefalconBCM08
1.3.6.1.4.1.3184.1.5.1.12.1.8.1ScalarfalconBCM08Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2TablefalconBCM08CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2.1RowfalconBCM08CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2.1.1ColumnfalconBCM08CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2.1.2ColumnfalconBCM08CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2.1.3ColumnfalconBCM08CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.8.2.1.4ColumnfalconBCM08CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.9NodefalconBCM09
1.3.6.1.4.1.3184.1.5.1.12.1.9.1ScalarfalconBCM09Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2TablefalconBCM09CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2.1RowfalconBCM09CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2.1.1ColumnfalconBCM09CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2.1.2ColumnfalconBCM09CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2.1.3ColumnfalconBCM09CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.9.2.1.4ColumnfalconBCM09CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.10NodefalconBCM10
1.3.6.1.4.1.3184.1.5.1.12.1.10.1ScalarfalconBCM10Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2TablefalconBCM10CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2.1RowfalconBCM10CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2.1.1ColumnfalconBCM10CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2.1.2ColumnfalconBCM10CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2.1.3ColumnfalconBCM10CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.10.2.1.4ColumnfalconBCM10CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.11NodefalconBCM11
1.3.6.1.4.1.3184.1.5.1.12.1.11.1ScalarfalconBCM11Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2TablefalconBCM11CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2.1RowfalconBCM11CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2.1.1ColumnfalconBCM11CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2.1.2ColumnfalconBCM11CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2.1.3ColumnfalconBCM11CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.11.2.1.4ColumnfalconBCM11CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.12NodefalconBCM12
1.3.6.1.4.1.3184.1.5.1.12.1.12.1ScalarfalconBCM12Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2TablefalconBCM12CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2.1RowfalconBCM12CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2.1.1ColumnfalconBCM12CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2.1.2ColumnfalconBCM12CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2.1.3ColumnfalconBCM12CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.12.2.1.4ColumnfalconBCM12CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.13NodefalconBCM13
1.3.6.1.4.1.3184.1.5.1.12.1.13.1ScalarfalconBCM13Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2TablefalconBCM13CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2.1RowfalconBCM13CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2.1.1ColumnfalconBCM13CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2.1.2ColumnfalconBCM13CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2.1.3ColumnfalconBCM13CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.13.2.1.4ColumnfalconBCM13CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.14NodefalconBCM14
1.3.6.1.4.1.3184.1.5.1.12.1.14.1ScalarfalconBCM14Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2TablefalconBCM14CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2.1RowfalconBCM14CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2.1.1ColumnfalconBCM14CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2.1.2ColumnfalconBCM14CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2.1.3ColumnfalconBCM14CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.14.2.1.4ColumnfalconBCM14CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.15NodefalconBCM15
1.3.6.1.4.1.3184.1.5.1.12.1.15.1ScalarfalconBCM15Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2TablefalconBCM15CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2.1RowfalconBCM15CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2.1.1ColumnfalconBCM15CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2.1.2ColumnfalconBCM15CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2.1.3ColumnfalconBCM15CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.15.2.1.4ColumnfalconBCM15CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.16NodefalconBCM16
1.3.6.1.4.1.3184.1.5.1.12.1.16.1ScalarfalconBCM16Labelread-onlymandatoryA user-defined text string associated with the BCM.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2TablefalconBCM16CBTablenot-accessiblemandatoryA table of the falcon modbus BCM CB port status.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2.1RowfalconBCM16CBEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus BCM CB port.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2.1.1ColumnfalconBCM16CBIndexread-onlymandatoryA unique value for each BCM CB port. Its value ranges between 1 and 42.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2.1.2ColumnfalconBCM16CBStatusread-onlymandatoryThe current status for this circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2.1.3ColumnfalconBCM16CBReadingread-onlymandatoryThe current reading (AMPS) for circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.1.16.2.1.4ColumnfalconBCM16CBLabelread-onlymandatoryA user-defined text string associated with the circuit breaker.
1.3.6.1.4.1.3184.1.5.1.12.2NodefalconBCMTrap
1.3.6.1.4.1.3184.1.5.1.12.2.1NodefalconBCM01TrapThe current on a BCM #01 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.1NodefalconBCM10TrapThe current on a BCM #11 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.2NodefalconBCM02TrapThe current on a BCM #02 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.3NodefalconBCM03TrapThe current on a BCM #03 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.4NodefalconBCM04TrapThe current on a BCM #04 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.5NodefalconBCM05TrapThe current on a BCM #05 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.6NodefalconBCM06TrapThe current on a BCM #06 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.7NodefalconBCM07TrapThe current on a BCM #07 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.8NodefalconBCM08TrapThe current on a BCM #08 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.9NodefalconBCM09TrapThe current on a BCM #09 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.11NodefalconBCM11TrapThe current on a BCM #11 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.12NodefalconBCM12TrapThe current on a BCM #12 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.13NodefalconBCM13TrapThe current on a BCM #13 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.14NodefalconBCM14TrapThe current on a BCM #14 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.15NodefalconBCM15TrapThe current on a BCM #15 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.2.16NodefalconBCM16TrapThe current on a BCM #16 circuit breaker has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.3NodefalconBCMTrapClear
1.3.6.1.4.1.3184.1.5.1.12.3.1NodefalconBCM01TrapClearThe current on a BCM #01 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.2NodefalconBCM02TrapClearThe current on a BCM #02 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.3NodefalconBCM03TrapClearThe current on a BCM #03 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.4NodefalconBCM04TrapClearThe current on a BCM #04 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.5NodefalconBCM05TrapClearThe current on a BCM #05 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.6NodefalconBCM06TrapClearThe current on a BCM #06 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.7NodefalconBCM07TrapClearThe current on a BCM #07 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.8NodefalconBCM08TrapClearThe current on a BCM #08 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.9NodefalconBCM09TrapClearThe current on a BCM #09 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.10NodefalconBCM10TrapClearThe current on a BCM #10 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.11NodefalconBCM11TrapClearThe current on a BCM #11 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.12NodefalconBCM12TrapClearThe current on a BCM #12 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.13NodefalconBCM13TrapClearThe current on a BCM #13 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.14NodefalconBCM14TrapClearThe current on a BCM #14 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.15NodefalconBCM15TrapClearThe current on a BCM #15 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.3.16NodefalconBCM16TrapClearThe current on a BCM #16 circuit breaker has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.4NodefalconXbG628
1.3.6.1.4.1.3184.1.5.1.12.4.1NodefalconXbUnits
1.3.6.1.4.1.3184.1.5.1.12.4.1.1TablefalconXbUnitsTablenot-accessiblemandatoryA table of the falcon modbus/bacnet unit status.
1.3.6.1.4.1.3184.1.5.1.12.4.1.1.1RowfalconXbUnitsEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus/bacnet unit status.
1.3.6.1.4.1.3184.1.5.1.12.4.1.1.1.1ColumnfalconXbUnitsIndexread-onlymandatoryA unique value for each Modbus/bacnet unit. Its value ranges between 1 and 16.
1.3.6.1.4.1.3184.1.5.1.12.4.1.1.1.2ColumnfalconXbUnitsStatusread-onlymandatoryThe current status for this Modbus/bacnet unit.
1.3.6.1.4.1.3184.1.5.1.12.4.1.1.1.3ColumnfalconXbUnitsLabelread-onlymandatoryA user-defined text string associated with the Modbus/bacnet unit.
1.3.6.1.4.1.3184.1.5.1.12.4.2NodefalconXbusTrapData
1.3.6.1.4.1.3184.1.5.1.12.4.2.1ScalarfalconXbusTrapRegisterNumbernot-accessiblemandatoryA Modbus register number (e.g. 40001) or bacnet instance number (e.g. 770033).
1.3.6.1.4.1.3184.1.5.1.12.4.2.2ScalarfalconXbusTrapRegisterLabelnot-accessiblemandatoryA user-defined text string associated with the Modbus register or bacnet instance
1.3.6.1.4.1.3184.1.5.1.12.4.3TablefalconXbusRegisterTablenot-accessiblemandatoryA table of the falcon modbus register status.
1.3.6.1.4.1.3184.1.5.1.12.4.3.1RowfalconXbusRegisterEntrynot-accessiblemandatoryAn entry containing objects for the Falcon modbus register status.
1.3.6.1.4.1.3184.1.5.1.12.4.3.1.1ColumnfalconXbusRegisterIndexread-onlymandatoryA unique value for each Modbus register. Its value ranges between 1 and 628.
1.3.6.1.4.1.3184.1.5.1.12.4.3.1.2ColumnfalconXbusRegisterTyperead-onlymandatoryThe current type for this Modbus register.
1.3.6.1.4.1.3184.1.5.1.12.4.3.1.3ColumnfalconXbusRegisterDataread-onlymandatoryThe current data value for this Modbus register.
1.3.6.1.4.1.3184.1.5.1.12.4.3.1.4ColumnfalconXbusRegisterLabelread-onlymandatoryA user-defined text string associated with the modbus register.
1.3.6.1.4.1.3184.1.5.1.12.5NodefalconXbusTraps
1.3.6.1.4.1.3184.1.5.1.12.5.1NodefalconXbusUnit01TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.2NodefalconXbusUnit02TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.3NodefalconXbusUnit03TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.4NodefalconXbusUnit04TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.5NodefalconXbusUnit05TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.6NodefalconXbusUnit06TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.7NodefalconXbusUnit07TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.8NodefalconXbusUnit08TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.9NodefalconXbusUnit09TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.10NodefalconXbusUnit10TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.11NodefalconXbusUnit11TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.12NodefalconXbusUnit12TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.13NodefalconXbusUnit13TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.14NodefalconXbusUnit14TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.15NodefalconXbusUnit15TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.5.16NodefalconXbusUnit16TrapA Modbus/bacnet device has reached an alarm state.
1.3.6.1.4.1.3184.1.5.1.12.6NodefalconXbusTrapsClear
1.3.6.1.4.1.3184.1.5.1.12.6.1NodefalconXbusUnit01TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.2NodefalconXbusUnit02TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.3NodefalconXbusUnit03TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.4NodefalconXbusUnit04TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.5NodefalconXbusUnit05TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.6NodefalconXbusUnit06TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.7NodefalconXbusUnit07TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.8NodefalconXbusUnit08TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.9NodefalconXbusUnit09TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.10NodefalconXbusUnit10TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.11NodefalconXbusUnit11TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.12NodefalconXbusUnit12TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.13NodefalconXbusUnit13TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.14NodefalconXbusUnit14TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.15NodefalconXbusUnit15TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.1.12.6.16NodefalconXbusUnit16TrapClearA Modbus/bacnet device has returned to normal.
1.3.6.1.4.1.3184.1.5.2Nodefms-X
1.3.6.1.4.1.3184.1.5.3Nodefms-A
1.3.6.1.4.1.3184.1.5.4Nodefms-B
1.3.6.1.4.1.3184.1.5.5Nodefms-C
1.3.6.1.4.1.3184.1.5.3300Nodefms-AAxx
1.3.6.1.4.1.3184.1.5.3330Nodefms-AAAx
1.3.6.1.4.1.3184.1.5.3333Nodefms-AAAA
1.3.6.1.4.1.3184.1.5.3335Nodefms-AAAC
1.3.6.1.4.1.3184.1.5.3340Nodefms-AABx
1.3.6.1.4.1.3184.1.5.3344Nodefms-AABB
1.3.6.1.4.1.3184.1.5.3350Nodefms-AACx
1.3.6.1.4.1.3184.1.5.3355Nodefms-AACC
1.3.6.1.4.1.3184.1.5.3400Nodefms-ABxx
1.3.6.1.4.1.3184.1.5.3440Nodefms-ABBx
1.3.6.1.4.1.3184.1.5.3444Nodefms-ABBB
1.3.6.1.4.1.3184.1.5.3445Nodefms-ABBC
1.3.6.1.4.1.3184.1.5.3450Nodefms-ABCx
1.3.6.1.4.1.3184.1.5.3455Nodefms-ABCC
1.3.6.1.4.1.3184.1.5.3500Nodefms-ACxx
1.3.6.1.4.1.3184.1.5.3550Nodefms-ACCx
1.3.6.1.4.1.3184.1.5.3555Nodefms-ACCC
1.3.6.1.4.1.3184.1.5.4400Nodefms-BBxx
1.3.6.1.4.1.3184.1.5.4440Nodefms-BBBx
1.3.6.1.4.1.3184.1.5.4444Nodefms-BBBB
1.3.6.1.4.1.3184.1.5.4445Nodefms-BBBC
1.3.6.1.4.1.3184.1.5.4450Nodefms-BBCx
1.3.6.1.4.1.3184.1.5.4455Nodefms-BBCC
1.3.6.1.4.1.3184.1.5.4500Nodefms-BCxx
1.3.6.1.4.1.3184.1.5.4550Nodefms-BCCx
1.3.6.1.4.1.3184.1.5.4555Nodefms-BCCC
1.3.6.1.4.1.3184.1.5.5055Nodefms-CxCC
1.3.6.1.4.1.3184.1.5.5500Nodefms-CCxx
1.3.6.1.4.1.3184.1.5.5505Nodefms-CCxC
1.3.6.1.4.1.3184.1.5.5550Nodefms-CCCx
1.3.6.1.4.1.3184.1.5.5555Nodefms-CCCC
Type Definitions
NameSyntaxStatusDescription
PositiveIntegerINTEGER (1..2147483647)