MIB Viewer

RUGGEDCOM-IRIGB-MIB

30 objects
Siemens - RuggedCom proprietary to control and monitor IRIGB module.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.15004.4.10IdentityrcIrigbSiemens - RuggedCom proprietary to control and monitor IRIGB module.
1.3.6.1.4.1.15004.4.10.1NodercIrigbBase
1.3.6.1.4.1.15004.4.10.1.1ScalarrcIrigbStatusread-onlycurrentThe system synchronization status when IRIGB is a primary time source. If value of this object is changed, rcIrigbStatusChange notification will be sent.
1.3.6.1.4.1.15004.4.10.1.2ScalarrcIrigbAMOutputread-writecurrentSelects AM (Amplitude Modulation) mode of IRIGB port.
1.3.6.1.4.1.15004.4.10.1.3ScalarrcIrigbTimeCoderead-writecurrentThis device uses the following convention to decode the IRIGB time code: letter [B] represents IRIG-B format, [xx] represents [00] for PWM/TTL mode of operatio…
1.3.6.1.4.1.15004.4.10.1.4ScalarrcIrigbExtread-writecurrentIRIGB extensions use extra bits of the Control Functions (CF) portion of the IRIGB time code. Within this portion of the time code, bits are designated for add…
1.3.6.1.4.1.15004.4.10.1.5ScalarrcIrigbInputread-writecurrentSelects operational mode of IRIGB input port. IRIGB module is capable of interpreting IRIGB extensions such as C37.118-2011, C37.118-2005 and IEEE1344.
1.3.6.1.4.1.15004.4.10.1.6ScalarrcIrigbLockIntread-writecurrentTo set time interval in minute with in which IRIGB receiver should acquire lock to the time source. Normally IRIGB receiver needs couple of minutes to lock the…
1.3.6.1.4.1.15004.4.10.1.7ScalarrcIrigbCableCompread-writecurrentCable compensation in ns may be desired to compensate for a long cable run in order to minimize the timing inaccuracy.
1.3.6.1.4.1.15004.4.10.1.8ScalarrcIrigbOFMread-onlycurrentThe current time offset between system and reference clocks.
1.3.6.1.4.1.15004.4.10.1.9ScalarrcIrigbFreqAdjread-onlycurrentThe current amount of discipline applied to the local frequency reference (TCXO).
1.3.6.1.4.1.15004.4.10.1.10ScalarrcIrigbOutputPWM1read-writecurrentSelects Operational mode of TTL output port. PWM mode complies with IRIG Standard 200-04. PPx provides generic pulse per x second interface to synchronize exte…
1.3.6.1.4.1.15004.4.10.1.11ScalarrcIrigbPulseInterval1read-writecurrentSelects Pulse Interval in s for TTL output port. This parameter is used in conjunction with PPx in order to provides generic pulse per x second interface to sy…
1.3.6.1.4.1.15004.4.10.1.12ScalarrcIrigbPulseWidth1read-writecurrentSelects Pulse Width in ms for TTL output port. This parameter is used in conjunction with PPx to control the width of the pulse.
1.3.6.1.4.1.15004.4.10.1.13ScalarrcIrigbStartTime1read-writecurrentThis parameter is used in conjunction with PPx to set the starting time of first PPx event. Note that this parameter must be set at least 15 seconds before the…
1.3.6.1.4.1.15004.4.10.1.14ScalarrcIrigbOutputPWM2read-writecurrentSelects Operational mode of TTL output port2. PWM mode complies with IRIG Standard 200-04. PPx provides generic pulse per x second interface to synchronize ext…
1.3.6.1.4.1.15004.4.10.1.15ScalarrcIrigbPulseInterval2read-writecurrentSelects Pulse Interval in s for TTL output port2. This parameter is used in conjunction with PPx in order to provides generic pulse per x second interface to s…
1.3.6.1.4.1.15004.4.10.1.16ScalarrcIrigbPulseWidth2read-writecurrentSelects Pulse Width in ms for TTL output port2. This parameter is used in conjunction with PPx to control the width of the pulse.
1.3.6.1.4.1.15004.4.10.1.17ScalarrcIrigbStartTime2read-writecurrentThis parameter is used in conjunction with PPx to set the starting time of first PPx event. Note that this parameter must be set at least 15 seconds before the…
1.3.6.1.4.1.15004.4.10.2NodercIrigbConformance
1.3.6.1.4.1.15004.4.10.2.2NodercIrigbGroups
1.3.6.1.4.1.15004.4.10.2.2.1GrouprcIrigbBaseGroupcurrentA group of objects providing ability ability to monitor and configure IRIGB status.
1.3.6.1.4.1.15004.4.10.2.2.2GrouprcIrigbNotifyGroupcurrentA group of objects that define trap.
1.3.6.1.4.1.15004.4.10.2.2.3GrouprcIrigbCommonGroupcurrentA group of objects providing ability to monitor and configure IRIGB device.
1.3.6.1.4.1.15004.4.10.2.2.4GrouprcIrigbAMOutGroupcurrentA group of objects providing ability to configure IRIGB AM output interface.
1.3.6.1.4.1.15004.4.10.2.2.5GrouprcIrigbInputGroupcurrentThis parameter covers both AM and PWM inputs.
1.3.6.1.4.1.15004.4.10.2.2.6GrouprcIrigbTTLOutput01GroupcurrentA group of objects providing ability to configure IRIGB TTL output interface01.
1.3.6.1.4.1.15004.4.10.2.2.7GrouprcIrigbTTLOutput02GroupcurrentA group of objects providing ability to configure IRIGB TTL output interface02.
1.3.6.1.4.1.15004.5.35NotificationrcIrigbStatusChangecurrentNotification generated if status of the IRIGB module is changed.
Type Definitions
NameSyntaxStatusDescription
RcTimeStampOCTET STRING (SIZE (8))currentTimestamps are represented as a 64-bit unsigned fixed-point number in seconds relative to 00:00 on 1 January 1970. The integer part is in the first 32 bits and the fraction part is in the last 32 bits.