MIB Viewer

SNMP-UPS-MIB

74 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.1Nodedirectory
1.3.6.1.2Nodemgmt
1.3.6.1.2.1Nodemib-2
1.3.6.1.3Nodeexperimental
1.3.6.1.3.9999NodeunivPowerSupply
1.3.6.1.3.9999.1Nodeident
1.3.6.1.3.9999.1.1ScalaridentDescrread-onlymandatoryThe UPS description. This should include the vendor name, model number and software revision.
1.3.6.1.3.9999.1.2ScalaridentSpecificread-onlymandatoryA reference to MIB definitions specific to the particular UPS being managed. If this information is not present, its value should be set to the OBJECT IDENTIFI…
1.3.6.1.3.9999.2Nodebattery
1.3.6.1.3.9999.2.1ScalarbatTimeRemainingread-onlymandatoryThe estimated time to battery charge depletion. (Unit of measure: Minute)
1.3.6.1.3.9999.2.2ScalarbatTemperatureread-onlymandatoryThe battery temperature. (Unit of measure: Degree, Centigrade)
1.3.6.1.3.9999.2.3ScalarbatVoltageread-onlymandatoryThe current battery voltage. (Unit of measure: volt)
1.3.6.1.3.9999.2.4ScalarbatChargeCurrentread-onlymandatoryThe current battery charging current. (Unit of measure: Amp/10)
1.3.6.1.3.9999.2.5ScalarbatDischargeCurrentread-onlymandatoryThe current battery discharging current. (Unit of measure: Amp/10)
1.3.6.1.3.9999.2.6ScalarbatCapacityread-onlymandatoryThe current battery capacity in percentage of total available.
1.3.6.1.3.9999.3Nodeinput
1.3.6.1.3.9999.3.1ScalarinputFrequencyread-onlymandatoryThe current input frequency. (Unit of measure: mHz)
1.3.6.1.3.9999.3.2ScalarinputBrownOutsread-onlymandatoryThe number of brown-out conditions since the agent started.
1.3.6.1.3.9999.3.3ScalarinputBlackOutsread-onlymandatoryThe number of black-out conditions since the agent started.
1.3.6.1.3.9999.3.4ScalarinputTransientsread-onlymandatoryThe number of transient (sag and surge) conditions since the agent started.
1.3.6.1.3.9999.3.5ScalarinputNumPhasesread-onlymandatoryThe number of input phases utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.3.9999.3.6TableinputTablenot-accessiblemandatory
1.3.6.1.3.9999.3.6.1RowinputEntrynot-accessiblemandatory
1.3.6.1.3.9999.3.6.1.1ColumninputPhaseread-onlymandatoryThe input phase.
1.3.6.1.3.9999.3.6.1.2ColumninputVoltageread-onlymandatoryThe input voltage. (Unit of measure: Volt)
1.3.6.1.3.9999.3.6.1.3ColumninputCurrentread-onlymandatoryThe input current. (Unit of measure: Amp/10)
1.3.6.1.3.9999.3.6.1.4ColumninputVAread-onlymandatoryThe input volt-amps.
1.3.6.1.3.9999.3.6.1.5ColumninputWattsread-onlymandatoryThe input power. (Unit of measure: Watt)
1.3.6.1.3.9999.4Nodeoutput
1.3.6.1.3.9999.4.1ScalaroutputFrequencyread-onlymandatoryMeasured in mHz.
1.3.6.1.3.9999.4.2ScalaroutputInverterTempread-onlymandatoryThe temperature of the inverter. (Unit of measure: degree, Centigrade)
1.3.6.1.3.9999.4.3ScalaroutputControllerTempread-onlymandatoryThe temperature of the controller. (Unit of measure: degree, Centigrade)
1.3.6.1.3.9999.4.4ScalaroutputNumPhasesread-onlymandatoryThe number of output phases utilized in this device. This entry indicates the number of rows in the output table.
1.3.6.1.3.9999.4.5TableoutputTablenot-accessiblemandatory
1.3.6.1.3.9999.4.5.1RowoutputEntrynot-accessiblemandatory
1.3.6.1.3.9999.4.5.1.1ColumnoutputPhaseread-onlymandatoryThe output phase.
1.3.6.1.3.9999.4.5.1.2ColumnoutputVoltageread-onlymandatoryThe output voltage. (Unit of measure: Volt)
1.3.6.1.3.9999.4.5.1.3ColumnoutputCurrentread-onlymandatoryThe output current. (Unit of measure: Amp/10)
1.3.6.1.3.9999.4.5.1.4ColumnoutputVAread-onlymandatoryThe output volt-amps.
1.3.6.1.3.9999.4.5.1.5ColumnoutputWattsread-onlymandatoryThe output power. (Unit of measure: Watt)
1.3.6.1.3.9999.5Nodebypass
1.3.6.1.3.9999.5.1ScalarbypassFrequencyread-onlymandatoryThe bypass frequency. (Unit of measure: mHz)
1.3.6.1.3.9999.5.2ScalarbypassNumPhasesread-onlymandatoryThe number of bypass phases utilized in this device. This entry indicates the number of rows in the input table.
1.3.6.1.3.9999.5.3TablebypassTablenot-accessiblemandatory
1.3.6.1.3.9999.5.3.1RowbypassEntrynot-accessiblemandatory
1.3.6.1.3.9999.5.3.1.1ColumnbypassPhaseread-onlymandatoryThe bypass phase.
1.3.6.1.3.9999.5.3.1.2ColumnbypassVoltageread-onlymandatoryThe bypass voltage. (Unit of measure: Volt)
1.3.6.1.3.9999.5.3.1.3ColumnbypassCurrentread-onlymandatoryThe bypass current. (Unit of measure: Amp/10)
1.3.6.1.3.9999.6Nodestatus
1.3.6.1.3.9999.6.1ScalarstatSummaryread-onlymandatoryA summary of non-critical conditions. Each of the enumerated values are added to compute the value of this object.
1.3.6.1.3.9999.7Nodealarm
1.3.6.1.3.9999.7.1ScalaralarmSummaryread-onlymandatoryA summary of critical conditions. Each of the enumerated values are added to compute the value of this object.
1.3.6.1.3.9999.8Nodetest
1.3.6.1.3.9999.8.1ScalartestBatteryread-writemandatorySetting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, other…
1.3.6.1.3.9999.8.2ScalartestBatteryStatusread-onlymandatoryThe status of the battery test.
1.3.6.1.3.9999.8.3ScalartestDiagread-writemandatorySetting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress…
1.3.6.1.3.9999.8.4ScalartestDiagStatusread-onlymandatoryThe status of the diagnostics test.
1.3.6.1.3.9999.8.5ScalartestIndicatorsread-writemandatorySetting this variable to 'start' will initiate the indicators test. Setting this variable to 'abort' will stop the indicators test if the test is in-progress, …
1.3.6.1.3.9999.8.6ScalartestIndicatorsStatusread-onlymandatoryThe status of the indicators test. Note: this test requires physical verification to be useful.
1.3.6.1.3.9999.9Nodeschedule
1.3.6.1.3.9999.9.1ScalarschedOutputOffDelayread-writemandatorySetting this object will stop the output after the indicated number of TimeTicks. Setting this object to -1 will abort any shutdown sequence. The output will r…
1.3.6.1.3.9999.9.2ScalarschedOutputOnDelayread-writemandatoryThe length of time to delay before coming on- line. If this value is -1 the output will remain off. This object will be set to -1 when the device is initialize…
1.3.6.1.3.9999.9.3ScalarschedSystemShutdownread-writemandatorySetting this object to 'true' will shutdown the device.
1.3.6.1.3.9999.9.4ScalarschedUnixShutdownread-writemandatorySetting this device to 'true' will cause unix shutdown traps to be issued at a system-dependent rate, or until this object is set to false.
1.3.6.1.3.9999.10Nodeconfig
1.3.6.1.3.9999.10.1ScalarconfigOutputVoltageread-onlymandatoryThe nominal output voltage. (Unit of measure: volt)
1.3.6.1.3.9999.10.2ScalarconfigInputVoltageread-onlymandatoryThe nominal input voltage. (Unit of measure: volt)
1.3.6.1.3.9999.10.3ScalarconfigOutputFreqread-onlymandatoryThe nominal output frequency. (Unit of measure: mHz)
1.3.6.1.3.9999.10.4ScalarconfigInputFreqread-onlymandatoryThe nominal input frequency. (Unit of measure: mHz)
1.3.6.1.3.9999.10.5ScalarconfigNominalBatTimeread-onlymandatoryThe nominal battery time. (Unit of measure: minute)
1.3.6.1.3.9999.10.6ScalarconfigAudioStatusread-writemandatoryThe status of the audio alarm. 'Off' indicates the alarm will not sound, while the 'squelch' value indicates the alarm has sounded and squelched. A squelched a…
1.3.6.1.3.9999.10.7ScalarconfigAutoRestartread-writemandatorySetting this object to 'on' will cause the device to restart after a shutdown.
1.3.6.1.4Nodeprivate
1.3.6.1.4.1Nodeenterprises