MIB Viewer

SPSv1-MIB

382 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.42610Nodepowertek
1.3.6.1.4.1.42610.1Nodeproduct
1.3.6.1.4.1.42610.1.4Nodepdu
1.3.6.1.4.1.42610.1.4.4Nodesps
1.3.6.1.4.1.42610.1.4.4.1NodepduObjects
1.3.6.1.4.1.42610.1.4.4.1.1NodepduIdent
1.3.6.1.4.1.42610.1.4.4.1.1.1ScalarpduIdentAgentSoftwareVersionread-onlymandatoryThe firmware version of the device.
1.3.6.1.4.1.42610.1.4.4.1.1.2ScalarpduIdentSerialNumberread-onlymandatoryA Model of this device.
1.3.6.1.4.1.42610.1.4.4.1.2NodepduNetwork
1.3.6.1.4.1.42610.1.4.4.1.2.1NodepduNetworkTcpip
1.3.6.1.4.1.42610.1.4.4.1.2.1.1ScalarpduNetworkTcpipDhcpControlread-writemandatoryEnable/disable DHCP protocol
1.3.6.1.4.1.42610.1.4.4.1.2.1.2NodepduNetworkTcpipIpv4
1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1ScalarpduNetworkTcpipIpv4Addressread-writemandatoryThe ip address that NMS can identify the managed device.
1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2ScalarpduNetworkTcpipIpv4Gatewayread-writemandatoryThe default gateway that allow device managed through routers.
1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3ScalarpduNetworkTcpipIpv4Subnetread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4ScalarpduNetworkTcpipIpv4PrimaryDNSread-writemandatoryInternet address of Primary DNS Server
1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5ScalarpduNetworkTcpipIpv4SecondaryDNSread-writemandatoryInternet address of Secondary DNS
1.3.6.1.4.1.42610.1.4.4.1.2.1.3NodepduNetworkTcpipIpv6
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.1ScalarpduNetworkTcpipIpv6Controlread-writemandatoryEnable/disable IPv6 protocol
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.2ScalarpduNetworkTcpipIpv6AutoConfigread-writemandatoryIPv6 Auto-config or Maual setting
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.3ScalarpduNetworkTcpipIpv6Addressread-onlymandatoryThe ipv6 address that NMS can identify the managed device.
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.4ScalarpduNetworkTcpipIpv6Prefixread-onlymandatoryThe prefix length for ipv6 address.
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.5ScalarpduNetworkTcpipIpv6Routerread-onlymandatoryThe default gateway that allow device managed through routers.
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.6ScalarpduNetworkTcpipIpv6PrimaryDNSread-writemandatoryInternet address of Primary DNS Server
1.3.6.1.4.1.42610.1.4.4.1.2.1.3.7ScalarpduNetworkTcpipIpv6SecondaryDNSread-writemandatoryInternet address of Secondary DNS
1.3.6.1.4.1.42610.1.4.4.1.2.2NodepduNetworkSecurity
1.3.6.1.4.1.42610.1.4.4.1.2.2.1ScalarpduNetworkSecurityControlread-writemandatoryEnable/disable Network Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.2NodepduNetworkSecuritySsh
1.3.6.1.4.1.42610.1.4.4.1.2.2.2.1ScalarpduNetworkSecuritySshControlread-writemandatoryEnable/disable SSH Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.2.2ScalarpduNetworkSecuritySshIntervalread-writemandatoryDetecting Interval of SSH Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.2.3ScalarpduNetworkSecuritySshFailTimesread-writemandatoryUnsuccessful attempts of SSH Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.2.4ScalarpduNetworkSecuritySshBlockread-writemandatoryBlock Time of SSH Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.3NodepduNetworkSecuritySnmp
1.3.6.1.4.1.42610.1.4.4.1.2.2.3.1ScalarpduNetworkSecuritySnmpControlread-writemandatoryEnable/disable SNMP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.3.2ScalarpduNetworkSecuritySnmpIntervalread-writemandatoryDetecting Interval of SNMP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.3.3ScalarpduNetworkSecuritySnmpFailTimesread-writemandatoryUnsuccessful attempts of SNMP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.3.4ScalarpduNetworkSecuritySnmpBlockread-writemandatoryBlock Time of SNMP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.4NodepduNetworkSecurityHttp
1.3.6.1.4.1.42610.1.4.4.1.2.2.4.1ScalarpduNetworkSecurityHttpControlread-writemandatoryEnable/disable HTTP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.4.2ScalarpduNetworkSecurityHttpIntervalread-writemandatoryDetecting Interval of HTTP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.4.3ScalarpduNetworkSecurityHttpFailTimesread-writemandatoryUnsuccessful attempts of HTTP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.2.4.4ScalarpduNetworkSecurityHttpBlockread-writemandatoryBlock Time of HTTP Access Protection
1.3.6.1.4.1.42610.1.4.4.1.2.3NodepduNetworkService
1.3.6.1.4.1.42610.1.4.4.1.2.3.1NodepduNetworkServiceSsh
1.3.6.1.4.1.42610.1.4.4.1.2.3.1.1ScalarpduNetworkServiceSshControlread-writemandatoryEnable/disable SSH Server Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.1.2ScalarpduNetworkServiceSshPortread-writemandatoryThe Port Number of SSH Server Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.2NodepduNetworkServiceSsl
1.3.6.1.4.1.42610.1.4.4.1.2.3.2.1ScalarpduNetworkServiceSslControlread-writemandatoryEnable/disable HTTPs Server Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.2.2ScalarpduNetworkServiceSslPortread-writemandatoryThe Port Number of HTTPs Server Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.2.3ScalarpduNetworkServiceSslForceread-writemandatoryForce use HTTPs Server Service only.
1.3.6.1.4.1.42610.1.4.4.1.2.3.3ScalarpduNetworkServicePingControlread-writemandatoryEnable/disable to response to PING request.
1.3.6.1.4.1.42610.1.4.4.1.2.3.4NodepduNetworkServiceRadius
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.1ScalarpduNetworkServiceRadiusControlread-writemandatoryEnable/disable RADIUS Client Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.2ScalarpduNetworkServiceRadiusIpread-writemandatoryThe IP Address of RADIUS Client Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.3ScalarpduNetworkServiceRadiusPortread-writemandatoryThe Port Number of RADIUS Client Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.4ScalarpduNetworkServiceRadiusSecretKeyread-writemandatoryThe Secret Key of RADIUS Client Service
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.5ScalarpduNetworkServiceRadiusTimeoutread-writemandatoryThe Timeout Interval of RADIUS Client Service in seconds
1.3.6.1.4.1.42610.1.4.4.1.2.3.4.6ScalarpduNetworkServiceRadiusRetryread-writemandatoryThe Retry Times of RADIUS Client Service
1.3.6.1.4.1.42610.1.4.4.1.3NodepduSystem
1.3.6.1.4.1.42610.1.4.4.1.3.1ScalarpduSystemNameread-writemandatoryThe name of system.
1.3.6.1.4.1.42610.1.4.4.1.3.2ScalarpduSystemContactread-writemandatoryThe contact of system.
1.3.6.1.4.1.42610.1.4.4.1.3.3ScalarpduSystemLocationread-writemandatoryThe location of system.
1.3.6.1.4.1.42610.1.4.4.1.3.4ScalarpduSystemLogIntervalread-writemandatoryThe Log Interval of device
1.3.6.1.4.1.42610.1.4.4.1.3.5ScalarpduSystemWebRefreshread-writemandatoryThe Web Refresh Interval of device
1.3.6.1.4.1.42610.1.4.4.1.3.6NodepduSystemTime
1.3.6.1.4.1.42610.1.4.4.1.3.6.1ScalarpduSystemTimeDisplayread-onlymandatoryThe date/time in agent
1.3.6.1.4.1.42610.1.4.4.1.3.6.2ScalarpduSystemTimeZoneread-writemandatoryTime Zone to use when synchronize with NTP server.
1.3.6.1.4.1.42610.1.4.4.1.3.6.3ScalarpduSystemTimeFormatread-writemandatoryDate Format
1.3.6.1.4.1.42610.1.4.4.1.3.6.4ScalarpduSystemTimeSettingread-writemandatoryTime Setting
1.3.6.1.4.1.42610.1.4.4.1.3.6.5ScalarpduSystemTimeDayLightSavingread-writemandatoryEnable/disable the Day Light Saving when synchronize with NTP server.
1.3.6.1.4.1.42610.1.4.4.1.3.6.6NodepduSystemTimeManual
1.3.6.1.4.1.42610.1.4.4.1.3.6.6.1ScalarpduSystemTimeManualDateread-writemandatoryThe date in agent, format is (dd/mm/yyyy)
1.3.6.1.4.1.42610.1.4.4.1.3.6.6.2ScalarpduSystemTimeManualTimeread-writemandatoryThe time in agent, format is (hh:mm:ss)
1.3.6.1.4.1.42610.1.4.4.1.3.6.7NodepduSystemTimeNtp
1.3.6.1.4.1.42610.1.4.4.1.3.6.7.1ScalarpduSystemTimeNtpControlread-writemandatoryEnable or disable the agent to synchronize date/time with NTP server.
1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2ScalarpduSystemTimeNtpServerread-writemandatoryThe ip address of NTP server.
1.3.6.1.4.1.42610.1.4.4.1.3.6.7.3ScalarpduSystemTimeNtpSyncIntervalread-writemandatoryThe Sync Interval with NTP server.
1.3.6.1.4.1.42610.1.4.4.1.3.6.7.4ScalarpduSystemTimeNtpSyncUnitread-writemandatoryThe Unit of Sync Interval
1.3.6.1.4.1.42610.1.4.4.1.3.7ScalarpduSystemResetToDefaultread-writemandatoryReset the parameter of PDU to default.
1.3.6.1.4.1.42610.1.4.4.1.3.8ScalarpduSystemRebootread-writemandatoryReboot the system of PDU.
1.3.6.1.4.1.42610.1.4.4.1.4NodepduSNMP
1.3.6.1.4.1.42610.1.4.4.1.4.1ScalarpduSnmpControlread-writemandatoryEnable/disable SNMP protocol.
1.3.6.1.4.1.42610.1.4.4.1.4.2ScalarpduSnmpPortread-writemandatoryThe UDP port for SNMP.
1.3.6.1.4.1.42610.1.4.4.1.4.3ScalarpduSnmpVersionread-writemandatorySet SNMP version.
1.3.6.1.4.1.42610.1.4.4.1.4.4TablepduSnmpTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of pduSnmpNumTrapReceivers
1.3.6.1.4.1.42610.1.4.4.1.4.4.1RowpduSnmpTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.42610.1.4.4.1.4.4.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3ColumnreceiverEventLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4ColumnreceiverSnmpVerread-writemandatoryThe SNMP Trap version of trap receivers.
1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5ColumnreceiverDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.42610.1.4.4.1.5NodepduEmail
1.3.6.1.4.1.42610.1.4.4.1.5.1ScalarpduEmailServerread-writemandatoryThe address of Email server.
1.3.6.1.4.1.42610.1.4.4.1.5.2ScalarpduEmailPortread-writemandatoryThe UDP port for Email Server.
1.3.6.1.4.1.42610.1.4.4.1.5.3ScalarpduEmailSenderEmailread-writemandatoryThe sender's Email address
1.3.6.1.4.1.42610.1.4.4.1.5.4ScalarpduEmailPrefixread-writemandatoryThe prefix string of mail subject
1.3.6.1.4.1.42610.1.4.4.1.5.5ScalarpduEmailAuthControlread-writemandatoryEnable/disable SMTP Authentication.
1.3.6.1.4.1.42610.1.4.4.1.5.6ScalarpduEmailAuthUsernameread-writemandatoryThe user name of SMTP Authentication
1.3.6.1.4.1.42610.1.4.4.1.5.7ScalarpduEmailAuthPasswordread-writemandatoryThe password of SMTP Authentication
1.3.6.1.4.1.42610.1.4.4.1.5.8TablepduEmailReceiversTablenot-accessiblemandatoryA list of managers to send email notification to.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1RowpduEmailReceiversEntrynot-accessiblemandatoryThe managers to send email notification to.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1.1ColumnmailRecvIndexread-onlymandatoryThe index to a email notification receiver entry.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2ColumnmailRecvReceiverAddrread-writemandatoryThe Email address of the manager to send a email notification to.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3ColumnmailRecvEmailTyperead-writemandatoryThe Email Type of email notification receivers.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4ColumnmailRecvEventLevelread-writemandatoryThe severity level of email notification to be received by this manager.
1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5ColumnmailRecvDescriptionread-writemandatoryDescription of email notification receivers
1.3.6.1.4.1.42610.1.4.4.1.6NodepduPwrMonitoring
1.3.6.1.4.1.42610.1.4.4.1.6.1NodepduPwrMonitoringInlet
1.3.6.1.4.1.42610.1.4.4.1.6.1.1ScalarpduPwrMonitoringInletNumread-onlymandatoryThe number of Inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2TablepduPwrMonitoringInletStatusTablenot-accessiblemandatoryA list to display status of Inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1RowpduPwrMonitoringInletStatusEntrynot-accessiblemandatoryA list to display status of Inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.1ColumninletIndexread-onlymandatoryThe index to Inlet status entry.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2ColumninletPowerAllread-onlymandatoryThe total power of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3ColumninletResetFromread-onlymandatoryThe reset date of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4ColumninletEnergyread-onlymandatoryThe total energy of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5ColumninletStatusread-onlymandatoryThe Status of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6ColumninletCurrPhase1read-onlymandatoryThe phase1 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.7ColumninletCurrPhase2read-onlymandatoryThe phase2 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.8ColumninletCurrPhase3read-onlymandatoryThe phase3 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9ColumninletVoltPhase1read-onlymandatoryThe phase1 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.10ColumninletVoltPhase2read-onlymandatoryThe phase2 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.11ColumninletVoltPhase3read-onlymandatoryThe phase3 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12ColumninletPwrFactorPhase1read-onlymandatoryThe phase1 power factor of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.13ColumninletPwrFactorPhase2read-onlymandatoryThe phase2 power factor of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.14ColumninletPwrFactorPhase3read-onlymandatoryThe phase3 power factor of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15ColumninletPowerPhase1read-onlymandatoryThe phase1 power of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.16ColumninletPowerPhase2read-onlymandatoryThe phase2 power of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.17ColumninletPowerPhase3read-onlymandatoryThe phase3 power of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18ColumninletStatusPhase1read-onlymandatoryThe phase1 status of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.19ColumninletStatusPhase2read-onlymandatoryThe phase2 status of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.20ColumninletStatusPhase3read-onlymandatoryThe phase3 status of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3TablepduPwrMonitoringInletCfgTablenot-accessiblemandatoryA list to configure thresholds of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1RowpduPwrMonitoringInletCfgEntrynot-accessiblemandatoryA list to configure thresholds of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.1ColumninletCfgIndexread-onlymandatoryThe index to inlet configuration entry.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2ColumninletCfgLoadCriticalread-writemandatoryThe Critical Threshold of inlet load.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3ColumninletCfgLoadWarningread-writemandatoryThe Warning Threshold of inlet load.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4ColumninletCfgCurrCritPhase1read-writemandatoryThe Critical Threshold of pahse1 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5ColumninletCfgCurrCritPhase2read-writemandatoryThe Critical Threshold of pahse2 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6ColumninletCfgCurrCritPhase3read-writemandatoryThe Critical Threshold of pahse3 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7ColumninletCfgCurrWarnPhase1read-writemandatoryThe Warning Threshold of pahse1 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8ColumninletCfgCurrWarnPhase2read-writemandatoryThe Warning Threshold of pahse2 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9ColumninletCfgCurrWarnPhase3read-writemandatoryThe Warning Threshold of pahse3 current of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10ColumninletCfgVoltCritPhase1read-writemandatoryThe Critical Threshold of pahse1 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11ColumninletCfgVoltCritPhase2read-writemandatoryThe Critical Threshold of pahse2 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12ColumninletCfgVoltCritPhase3read-writemandatoryThe Critical Threshold of pahse3 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13ColumninletCfgVoltWarnPhase1read-writemandatoryThe Warning Threshold of pahse1 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14ColumninletCfgVoltWarnPhase2read-writemandatoryThe Warning Threshold of pahse2 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15ColumninletCfgVoltWarnPhase3read-writemandatoryThe Warning Threshold of pahse3 voltage of inlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2NodepduPwrMonitoringOutlet
1.3.6.1.4.1.42610.1.4.4.1.6.2.1NodepduPwrMonitoringOutletPduA
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.1ScalarpduPwrMonitoringOutletNumPduAread-onlymandatoryThe number of PduA Outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2TablepduPwrMonitoringOutletStatusTablePduAnot-accessiblemandatoryA list to display status of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1RowpduPwrMonitoringOutletStatusPduAEntrynot-accessiblemandatoryA list to display status of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.1ColumnoutletPduAIndexread-onlymandatoryThe index to outlet status of PduA.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.2ColumnoutletPduAStateread-onlymandatoryThe state of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.3ColumnoutletPduACurrentread-onlymandatoryThe current of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.4ColumnoutletPduAPwrFactorread-onlymandatoryThe power factor of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.5ColumnoutletPduAPowerread-onlymandatoryThe power of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.6ColumnoutletPduAEnergyread-onlymandatoryThe energy of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.7ColumnoutletPduAResetFromread-onlymandatoryThe reset date of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.8ColumnoutletPduAStatusread-onlymandatoryThe status of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3TablepduPwrMonitoringOutletCfgTablePduAnot-accessiblemandatoryA list to display configuration of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1RowpduPwrMonitoringOutletCfgPduAEntrynot-accessiblemandatoryA list to display configuration of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.1ColumnoutletCfgPduAIndexread-onlymandatoryThe index to outlet configuration of PduA.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.2ColumnoutletCfgPduANameread-writemandatoryThe name for outlet of PduA.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.3ColumnoutletCfgPduADelayOnStatusread-writemandatoryThe Delay On status of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.4ColumnoutletCfgPduADelayOnTimeread-writemandatoryThe Delay On time of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.5ColumnoutletCfgPduADelayOffStatusread-writemandatoryThe Delay Off status of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.6ColumnoutletCfgPduADelayOffTimeread-writemandatoryThe Delay Off time of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.7ColumnoutletCfgPduARebootread-writemandatoryThe Delay On reboot duration of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.8ColumnoutletCfgPduAOverCurrCriticalread-writemandatoryThe Critical Threshold of current of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.9ColumnoutletCfgPduAOverCurrWarningread-writemandatoryThe Warning Threshold of current of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.10ColumnoutletCfgPduAOverPwrCriticalread-writemandatoryThe Critical Threshold of power of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.11ColumnoutletCfgPduAOverPwrWarningread-writemandatoryThe Warning Threshold of power of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4TablepduPwrMonitoringOutletCtlTablePduAnot-accessiblemandatoryA list to display control of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1RowpduPwrMonitoringOutletCtlPduAEntrynot-accessiblemandatoryA list to display control of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1.1ColumnoutletCtlPduAIndexread-onlymandatoryThe index to outlet control of PduA.
1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1.2ColumnoutletCtlPduAControlread-writemandatoryThe control-type of PduA outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2NodepduPwrMonitoringOutletPduB
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.1ScalarpduPwrMonitoringOutletNumPduBread-onlymandatoryThe number of PduB Outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2TablepduPwrMonitoringOutletStatusTablePduBnot-accessiblemandatoryA list to display status of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1RowpduPwrMonitoringOutletStatusPduBEntrynot-accessiblemandatoryA list to display status of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.1ColumnoutletPduBIndexread-onlymandatoryThe index to outlet status of PduB.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.2ColumnoutletPduBStateread-onlymandatoryThe state of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.3ColumnoutletPduBCurrentread-onlymandatoryThe current of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.4ColumnoutletPduBPwrFactorread-onlymandatoryThe power factor of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.5ColumnoutletPduBPowerread-onlymandatoryThe power of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.6ColumnoutletPduBEnergyread-onlymandatoryThe energy of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.7ColumnoutletPduBResetFromread-onlymandatoryThe reset date of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.8ColumnoutletPduBStatusread-onlymandatoryThe status of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3TablepduPwrMonitoringOutletCfgTablePduBnot-accessiblemandatoryA list to display configuration of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1RowpduPwrMonitoringOutletCfgPduBEntrynot-accessiblemandatoryA list to display configuration of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.1ColumnoutletCfgPduBIndexread-onlymandatoryThe index to outlet configuration of PduB.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.2ColumnoutletCfgPduBNameread-writemandatoryThe name for outlet of PduB.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.3ColumnoutletCfgPduBDelayOnStatusread-writemandatoryThe Delay On status of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.4ColumnoutletCfgPduBDelayOnTimeread-writemandatoryThe Delay On time of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.5ColumnoutletCfgPduBDelayOffStatusread-writemandatoryThe Delay Off status of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.6ColumnoutletCfgPduBDelayOffTimeread-writemandatoryThe Delay Off time of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.7ColumnoutletCfgPduBRebootread-writemandatoryThe Delay On reboot duration of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.8ColumnoutletCfgPduBOverCurrCriticalread-writemandatoryThe Critical Threshold of current of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.9ColumnoutletCfgPduBOverCurrWarningread-writemandatoryThe Warning Threshold of current of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.10ColumnoutletCfgPduBOverPwrCriticalread-writemandatoryThe Critical Threshold of power of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.11ColumnoutletCfgPduBOverPwrWarningread-writemandatoryThe Warning Threshold of power of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4TablepduPwrMonitoringOutletCtlTablePduBnot-accessiblemandatoryA list to display control of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1RowpduPwrMonitoringOutletCtlPduBEntrynot-accessiblemandatoryA list to display control of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1.1ColumnoutletCtlPduBIndexread-onlymandatoryThe index to outlet control of PduB.
1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1.2ColumnoutletCtlPduBControlread-writemandatoryThe control-type of PduB outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3NodepduPwrMonitoringOutletPduC
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.1ScalarpduPwrMonitoringOutletNumPduCread-onlymandatoryThe number of PduC Outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2TablepduPwrMonitoringOutletStatusTablePduCnot-accessiblemandatoryA list to display status of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1RowpduPwrMonitoringOutletStatusPduCEntrynot-accessiblemandatoryA list to display status of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.1ColumnoutletPduCIndexread-onlymandatoryThe index to outlet status of PduC.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.2ColumnoutletPduCStateread-onlymandatoryThe state of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.3ColumnoutletPduCCurrentread-onlymandatoryThe current of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.4ColumnoutletPduCPwrFactorread-onlymandatoryThe power factor of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5ColumnoutletPduCPowerread-onlymandatoryThe power of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.6ColumnoutletPduCEnergyread-onlymandatoryThe energy of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.7ColumnoutletPduCResetFromread-onlymandatoryThe reset date of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.8ColumnoutletPduCStatusread-onlymandatoryThe status of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3TablepduPwrMonitoringOutletCfgTablePduCnot-accessiblemandatoryA list to display configuration of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1RowpduPwrMonitoringOutletCfgPduCEntrynot-accessiblemandatoryA list to display configuration of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.1ColumnoutletCfgPduCIndexread-onlymandatoryThe index to outlet configuration of PduC.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.2ColumnoutletCfgPduCNameread-writemandatoryThe name for outlet of PduC.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.3ColumnoutletCfgPduCDelayOnStatusread-writemandatoryThe Delay On status of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.4ColumnoutletCfgPduCDelayOnTimeread-writemandatoryThe Delay On time of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.5ColumnoutletCfgPduCDelayOffStatusread-writemandatoryThe Delay Off status of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.6ColumnoutletCfgPduCDelayOffTimeread-writemandatoryThe Delay Off time of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.7ColumnoutletCfgPduCRebootread-writemandatoryThe Delay On reboot duration of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.8ColumnoutletCfgPduCOverCurrCriticalread-writemandatoryThe Critical Threshold of current of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.9ColumnoutletCfgPduCOverCurrWarningread-writemandatoryThe Warning Threshold of current of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.10ColumnoutletCfgPduCOverPwrCriticalread-writemandatoryThe Critical Threshold of power of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.11ColumnoutletCfgPduCOverPwrWarningread-writemandatoryThe Warning Threshold of power of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4TablepduPwrMonitoringOutletCtlTablePduCnot-accessiblemandatoryA list to display control of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1RowpduPwrMonitoringOutletCtlPduCEntrynot-accessiblemandatoryA list to display control of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1.1ColumnoutletCtlPduCIndexread-onlymandatoryThe index to outlet control of PduC.
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1.2ColumnoutletCtlPduCControlread-writemandatoryThe control-type of PduC outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4NodepduPwrMonitoringOutletPduD
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.1ScalarpduPwrMonitoringOutletNumPduDread-onlymandatoryThe number of PduD Outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2TablepduPwrMonitoringOutletStatusTablePduDnot-accessiblemandatoryA list to display status of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1RowpduPwrMonitoringOutletStatusPduDEntrynot-accessiblemandatoryA list to display status of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.1ColumnoutletPduDIndexread-onlymandatoryThe index to outlet status of PduD.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.2ColumnoutletPduDStateread-onlymandatoryThe state of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.3ColumnoutletPduDCurrentread-onlymandatoryThe current of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.4ColumnoutletPduDPwrFactorread-onlymandatoryThe power factor of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.5ColumnoutletPduDPowerread-onlymandatoryThe power of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.6ColumnoutletPduDEnergyread-onlymandatoryThe energy of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.7ColumnoutletPduDResetFromread-onlymandatoryThe reset date of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.8ColumnoutletPduDStatusread-onlymandatoryThe status of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3TablepduPwrMonitoringOutletCfgTablePduDnot-accessiblemandatoryA list to display configuration of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1RowpduPwrMonitoringOutletCfgPduDEntrynot-accessiblemandatoryA list to display configuration of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.1ColumnoutletCfgPduDIndexread-onlymandatoryThe index to outlet configuration of PduD.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.2ColumnoutletCfgPduDNameread-writemandatoryThe name for outlet of PduD.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.3ColumnoutletCfgPduDDelayOnStatusread-writemandatoryThe Delay On status of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.4ColumnoutletCfgPduDDelayOnTimeread-writemandatoryThe Delay On time of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.5ColumnoutletCfgPduDDelayOffStatusread-writemandatoryThe Delay Off status of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.6ColumnoutletCfgPduDDelayOffTimeread-writemandatoryThe Delay Off time of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.7ColumnoutletCfgPduDRebootread-writemandatoryThe Delay On reboot duration of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.8ColumnoutletCfgPduDOverCurrCriticalread-writemandatoryThe Critical Threshold of current of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.9ColumnoutletCfgPduDOverCurrWarningread-writemandatoryThe Warning Threshold of current of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.10ColumnoutletCfgPduDOverPwrCriticalread-writemandatoryThe Critical Threshold of power of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.11ColumnoutletCfgPduDOverPwrWarningread-writemandatoryThe Warning Threshold of power of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4TablepduPwrMonitoringOutletCtlTablePduDnot-accessiblemandatoryA list to display control of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1RowpduPwrMonitoringOutletCtlPduDEntrynot-accessiblemandatoryA list to display control of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1.1ColumnoutletCtlPduDIndexread-onlymandatoryThe index to outlet control of PduD.
1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1.2ColumnoutletCtlPduDControlread-writemandatoryThe control-type of PduD outlet.
1.3.6.1.4.1.42610.1.4.4.1.7NodepduEnvMonitoring
1.3.6.1.4.1.42610.1.4.4.1.7.1NodepduEnvMonitoringStatus
1.3.6.1.4.1.42610.1.4.4.1.7.1.1ScalarpduEnvMonitoringTempread-onlymandatoryThe temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.1.2ScalarpduEnvMonitoringHumiread-onlymandatoryThe humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.1.3ScalarpduEnvMonitoringTempAlarmread-onlymandatoryThe temperature status of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.1.4ScalarpduEnvMonitoringHumiAlarmread-onlymandatoryThe humidity status of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2NodepduEnvMonitoringCfg
1.3.6.1.4.1.42610.1.4.4.1.7.2.1ScalarpduEnvMonitoringControlread-writemandatoryEnable/disable the EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.2ScalarpduEnvMonitoringTempHighCriticalread-writemandatoryThe High Critical Threshold of temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.3ScalarpduEnvMonitoringTempHighWarningread-writemandatoryThe High Warning Threshold of temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.4ScalarpduEnvMonitoringTempLowCriticalread-writemandatoryThe Low Critical Threshold of temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.5ScalarpduEnvMonitoringTempLowWarningread-writemandatoryThe Low Warning Threshold of temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.6ScalarpduEnvMonitoringTempHystersisread-writemandatoryThe Hystersis of Temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.7ScalarpduEnvMonitoringTempOffsetread-writemandatoryThe Offset of Temperature of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.8ScalarpduEnvMonitoringHumiHighCriticalread-writemandatoryThe High Crtitcal Threshold of humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.9ScalarpduEnvMonitoringHumiHighWarningread-writemandatoryThe High Warning Threshold of humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.10ScalarpduEnvMonitoringHumiLowCriticalread-writemandatoryThe Low Crtitcal Threshold of humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.11ScalarpduEnvMonitoringHumiLowWarningread-writemandatoryThe Low Warning Threshold of humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.12ScalarpduEnvMonitoringHumiHystersisread-writemandatoryThe Hystersis of Humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.1.7.2.13ScalarpduEnvMonitoringHumiOffsetread-writemandatoryThe Ofset of Humidity of EMD.
1.3.6.1.4.1.42610.1.4.4.2NodepduTraps
1.3.6.1.4.1.42610.1.4.4.2.1NodepduSystemColdBootInformational: Cold boot.
1.3.6.1.4.1.42610.1.4.4.2.2NodepduSystemWarmBootInformational: Warm boot.
1.3.6.1.4.1.42610.1.4.4.2.3NodepduSystemRestartInformational: System restart.
1.3.6.1.4.1.42610.1.4.4.2.4NodepduResetToDefaultInformational: Parameters reset to default.
1.3.6.1.4.1.42610.1.4.4.2.5NodepduFirmUpgradeInformational: Firmware upgrade.
1.3.6.1.4.1.42610.1.4.4.2.6NodepduSystemLogClearInformational: System log cleared.
1.3.6.1.4.1.42610.1.4.4.2.7NodepduEventlogClearInformational: Event log cleared.
1.3.6.1.4.1.42610.1.4.4.2.8NodepduInletHistoryClearInformational: Inlet history log cleared.
1.3.6.1.4.1.42610.1.4.4.2.9NodepduOutletHistoryClearInformational: Outlet history log cleared.
1.3.6.1.4.1.42610.1.4.4.2.10NodepduSystemTimeChangeUserInformational: Time changed by user.
1.3.6.1.4.1.42610.1.4.4.2.11NodepduSystemTimeChangeNtpInformational: Time synced with NTP server.
1.3.6.1.4.1.42610.1.4.4.2.12NodepduSystemTimeChangeRtcInformational: Time changed by RTC.
1.3.6.1.4.1.42610.1.4.4.2.13NodepduMailTestPassInformational: Test mail pass.
1.3.6.1.4.1.42610.1.4.4.2.14NodepduMailTestFailInformational: Test mail failed.
1.3.6.1.4.1.42610.1.4.4.2.15NodepduMailSentPassInformational: Mail sent successfully.
1.3.6.1.4.1.42610.1.4.4.2.16NodepduMailSentFailInformational: Mail sent failed.
1.3.6.1.4.1.42610.1.4.4.2.17NodepduSystemCfgChangeInformational: Parameter changed.
1.3.6.1.4.1.42610.1.4.4.2.18NodepduSystemParamImportInformational: Import XML configuration.
1.3.6.1.4.1.42610.1.4.4.2.19NodepduInletCommLostInformational: Inlet communication lost.
1.3.6.1.4.1.42610.1.4.4.2.20NodepduInletCommRestoreInformational: Inlet communication restore.
1.3.6.1.4.1.42610.1.4.4.2.21NodepduOutletCommLostInformational: Outlet communication lost.
1.3.6.1.4.1.42610.1.4.4.2.22NodepduOutletCommRestoreInformational: Outlet communication restore
1.3.6.1.4.1.42610.1.4.4.2.23NodepduOutletOnUserInformational: Outlet turned on by user.
1.3.6.1.4.1.42610.1.4.4.2.24NodepduOutletOnScheduleInformational: Outlet turned on by schedule.
1.3.6.1.4.1.42610.1.4.4.2.25NodepduOutletOffUserInformational: Outlet turned off by user.
1.3.6.1.4.1.42610.1.4.4.2.26NodepduOutletOffScheduleInformational: Outlet turned off by schedule.
1.3.6.1.4.1.42610.1.4.4.2.27NodepduOutletRebootUserInformational: Outlet reboot by user.
1.3.6.1.4.1.42610.1.4.4.2.28NodepduOutletRebootScheduleInformational: Outlet reboot by schedule.
1.3.6.1.4.1.42610.1.4.4.2.29NodepduInletEnergyResetInformational: Inlet energy reset.
1.3.6.1.4.1.42610.1.4.4.2.30NodepduOutletEnergyResetInformational: Outlet energy reset.
1.3.6.1.4.1.42610.1.4.4.2.31NodepduSetUserInformational: Assign outlet to user.
1.3.6.1.4.1.42610.1.4.4.2.32NodepduDeletUserInformational: Delete user.
1.3.6.1.4.1.42610.1.4.4.2.33NodepduUpgradeInletSuccessInformational: Inlet upgrade successfully.
1.3.6.1.4.1.42610.1.4.4.2.34NodepduUpgradeInletFailInformational: Inlet upgrade fail.
1.3.6.1.4.1.42610.1.4.4.2.35NodepduUpgradeOutletSuccessInformational: Outlet upgrade successfully.
1.3.6.1.4.1.42610.1.4.4.2.36NodepduUpgradeOutletFailInformational: Outlet upgrade fail.
1.3.6.1.4.1.42610.1.4.4.2.101NodepduEmdTempHighWarnToNormalInformational: Temperature had returned from high warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.102NodepduEmdTempHighWarnWarning: Temperature was higher than high warning set point.
1.3.6.1.4.1.42610.1.4.4.2.103NodepduEmdTempLowWarnToNormalInformational: Temperature had returned from low warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.104NodepduEmdTempLowWarnWarning: Temperature was lower than low warning set point.
1.3.6.1.4.1.42610.1.4.4.2.105NodepduEmdTempHighCritToWarnInformational: Temperature had returned from high critical to high warning.
1.3.6.1.4.1.42610.1.4.4.2.106NodepduEmdTempHighCriticalCritical: Temperature was higher than high critical set point.
1.3.6.1.4.1.42610.1.4.4.2.107NodepduEmdTempLowCritToWarnInformational: Temperature had returned from low critical to low warning.
1.3.6.1.4.1.42610.1.4.4.2.108NodepduEmdTempLowCriticalCritical: Temperature was lower than low critical set point.
1.3.6.1.4.1.42610.1.4.4.2.109NodepduEmdHumiHighWarnToNormalInformational: Humidity had returned from high warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.110NodepduEmdHumiHighWarnWarning: Humidity was higher than high warning set point.
1.3.6.1.4.1.42610.1.4.4.2.111NodepduEmdHumiLowWarnToNormalInformational: Humidity had returned from low warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.112NodepduEmdHumiLowWarnWarning: Humidity was lower than low warning set point.
1.3.6.1.4.1.42610.1.4.4.2.113NodepduEmdHumiHighCritToWarnInformational: Humidity had returned from high critical to high warning.
1.3.6.1.4.1.42610.1.4.4.2.114NodepduEmdHumiHighCriticalCritical: Humidity was higher than high critical set point.
1.3.6.1.4.1.42610.1.4.4.2.115NodepduEmdHumiLowCritToWarnInformational: Humidity had returned from low critical to low warning.
1.3.6.1.4.1.42610.1.4.4.2.116NodepduEmdHumiLowCriticalCritical: Humidity was lower than low critical set point.
1.3.6.1.4.1.42610.1.4.4.2.117NodepduEmdAlarm1NotActiveInformational: Alarm-1 became inactive.
1.3.6.1.4.1.42610.1.4.4.2.118NodepduEmdAlarm1ActiveWarning: Alarm-1 became active.
1.3.6.1.4.1.42610.1.4.4.2.119NodepduEmdAlarm2NotActiveInformational: Alarm-2 became inactive.
1.3.6.1.4.1.42610.1.4.4.2.120NodepduEmdAlarm2ActiveWarning: Alarm-2 became active.
1.3.6.1.4.1.42610.1.4.4.2.121NodepduRs485OnlineInformational: RS485 Sensor was online.
1.3.6.1.4.1.42610.1.4.4.2.122NodepduRs485OfflineWarning: RS485 Sensor was offline.
1.3.6.1.4.1.42610.1.4.4.2.123NodepduInletLoadCritToWarnInformational: Inlet load had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.124NodepduInletLoadCriticalCritical: Inlet load was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.125NodepduInletLoadWarnToNormalInformational: Inlet load had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.126NodepduInletLoadWarnWarning: Inlet load was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.127NodepduInletCurrPhase1CritToWarnInformational: Inlet phase1 current had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.128NodepduInletCurrPhase1CriticalCritical: Inlet phase1 current was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.129NodepduInletCurrPhase1WarnToNormalInformational: Inlet phase1 current had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.130NodepduInletCurrPhase1WarnWarning: Inlet phase1 current was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.131NodepduInletCurrPhase2CritToWarnInformational: Inlet phase2 current had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.132NodepduInletCurrPhase2CriticalCritical: Inlet phase2 current was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.133NodepduInletCurrPhase2WarnToNormalInformational: Inlet phase2 current had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.134NodepduInletCurrPhase2WarnWarning: Inlet phase2 current was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.135NodepduInletCurrPhase3CritToWarnInformational: Inlet phase3 current had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.136NodepduInletCurrPhase3CriticalCritical: Inlet phase3 current was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.137NodepduInletCurrPhase3WarnToNormalInformational: Inlet phase3 current had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.138NodepduInletCurrPhase3WarnWarning: Inlet phase3 current had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.139NodepduInletVoltPhase1CritToWarnInformational: Inlet phase1 voltage had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.140NodepduInletVoltPhase1CriticalCritical: Inlet phase1 voltage was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.141NodepduInletVoltPhase1WarnToNormalInformational: Inlet phase1 voltage had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.142NodepduInletVoltPhase1WarnWarning: Inlet phase1 voltage was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.143NodepduInletVoltPhase2CritToWarnInformational: Inlet phase2 voltage had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.144NodepduInletVoltPhase2CriticalCritical: Inlet phase2 voltage was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.145NodepduInletVoltPhase2WarnToNormalInformational: Inlet phase2 voltage had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.146NodepduInletVoltPhase2WarnWarning: Inlet phase2 voltage was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.147NodepduInletVoltPhase3CritToWarnInformational: Inlet phase3 voltage had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.148NodepduInletVoltPhase3CriticalCritical: Inlet phase3 voltage was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.149NodepduInletVoltPhase3WarnToNormalInformational: Inlet phase3 voltage had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.150NodepduInletVoltPhase3WarnWarning: Inlet phase3 voltage was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.151NodepduOutletCurrCritToWarnInformational: Outlet current had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.152NodepduOutletCurrCriticalCritical: Outlet current was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.153NodepduOutletCurrWarnToNormalInformational: Outlet current had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.154NodepduOutletCurrWarnWarning: Outlet current was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.155NodepduOutletPwrCritTOWarnInformational: Outlet power had returned from critical to warning.
1.3.6.1.4.1.42610.1.4.4.2.156NodepduOutletPwrCriticalCritical: Outlet power was higher than critical set point.
1.3.6.1.4.1.42610.1.4.4.2.157NodepduOutletPwrWarnToNormalInformational: Outlet power had returned from warning to normal.
1.3.6.1.4.1.42610.1.4.4.2.158NodepduOutletPwrWarnWarning: Outlet power was higher than warning set point.
1.3.6.1.4.1.42610.1.4.4.2.159NodepduAlarm1DisabledInformational: Alarm-1 became disabled.
1.3.6.1.4.1.42610.1.4.4.2.160NodepduAlarm2DisabledInformational: Alarm-2 became disabled.