MIB Viewer

USHA-MIB

277 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.2468Nodeingrasys
1.3.6.1.4.1.2468.1Nodeproduct
1.3.6.1.4.1.2468.1.2NodeupsAgent
1.3.6.1.4.1.2468.1.2.1Nodeushap
1.3.6.1.4.1.2468.1.2.1.1NodeupsObjectGroup
1.3.6.1.4.1.2468.1.2.1.1.1NodeupsIdentGroup
1.3.6.1.4.1.2468.1.2.1.1.1.1ScalarupsIdentGroupManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.2468.1.2.1.1.1.2ScalarupsIdentGroupModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.2468.1.2.1.1.1.3ScalarupsIdentGroupUPSFirmwareVersionread-onlymandatoryThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentGroupAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.2468.1.2.1.1.1.4ScalarupsIdentGroupAgentSoftwareVersionread-onlymandatoryThe USHA software/firmware version. This variable may or may not have the same value as upsIdentGroupUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.2468.1.2.1.1.1.5ScalarupsIdentGroupNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.2468.1.2.1.1.1.6ScalarupsIdentGroupAttachedDevicesread-writemandatoryA string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.2468.1.2.1.1.1.7ScalarupsIdentGroupUpsSerialNumberread-onlymandatoryThe UPS serial no.
1.3.6.1.4.1.2468.1.2.1.1.2NodeupsBatteryGroup
1.3.6.1.4.1.2468.1.2.1.1.2.1ScalarupsBatteryGroupStatusread-onlymandatoryThe indication of the status in the UPS system's batteries.
1.3.6.1.4.1.2468.1.2.1.1.2.2ScalarupsBatteryGroupSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.2468.1.2.1.1.2.3ScalarupsBatteryGroupEstimatedMinutesRemainingread-onlymandatoryAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.2468.1.2.1.1.2.4ScalarupsBatteryGroupEstimatedChargeRemainingread-onlymandatoryAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.2468.1.2.1.1.2.5ScalarupsBatteryGroupVoltageread-onlymandatoryThe magnitude of the present battery voltage in 0.1 Volt DC.
1.3.6.1.4.1.2468.1.2.1.1.2.6ScalarupsBatteryGroupMandatoryread-onlymandatoryThe present battery mandatory.
1.3.6.1.4.1.2468.1.2.1.1.2.7ScalarupsBatteryGroupTemperatureread-onlymandatoryThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.2468.1.2.1.1.3NodeupsInputGroup
1.3.6.1.4.1.2468.1.2.1.1.3.1ScalarupsInputGroupLineBadsread-onlymandatoryA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.2468.1.2.1.1.3.2ScalarupsInputGroupNumLinesread-onlymandatoryThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.2468.1.2.1.1.3.3TableupsInputGroupTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputGroupNumLines.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1RowupsInputGroupEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.1ColumnupsInputGroupLineIndexread-onlymandatoryThe index of UpsInputGroupEntry.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.2ColumnupsInputGroupFrequencyread-onlymandatoryThe present input frequency.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.3ColumnupsInputGroupVoltageread-onlymandatoryThe input utility line voltage in 0.1 volts.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.4ColumnupsInputGroupCurrentread-onlymandatoryThe magnitude of the present input current in 0.1 A.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.5ColumnupsInputGroupTruePowerread-onlymandatoryThe magnitude of the present input true power.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.6ColumnupsInputGroupVoltageMaxread-onlymandatoryThe maximum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.2468.1.2.1.1.3.3.1.7ColumnupsInputGroupVoltageMinread-onlymandatoryThe minimum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.2468.1.2.1.1.4NodeupsOutputGroup
1.3.6.1.4.1.2468.1.2.1.1.4.1ScalarupsOutputGroupSourceread-onlymandatoryThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.2468.1.2.1.1.4.2ScalarupsOutputGroupFrequencyread-onlymandatoryThe current output frequency of the UPS system in 0.1 of HZ.
1.3.6.1.4.1.2468.1.2.1.1.4.3ScalarupsOutputGroupNumLinesread-onlymandatoryThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.2468.1.2.1.1.4.4TableupsOutputGroupTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputGroupNumLines.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1RowupsOutputGroupEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1.1ColumnupsOutputGroupLineIndexread-onlymandatoryThe output line identifier.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1.2ColumnupsOutputGroupVoltageread-onlymandatoryThe output voltage of the UPS system in 0.1 volts.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1.3ColumnupsOutputGroupCurrentread-onlymandatoryThe output current of the UPS system in 0.1 Amps.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1.4ColumnupsOutputGroupPowerread-onlymandatoryThe present output true power.
1.3.6.1.4.1.2468.1.2.1.1.4.4.1.5ColumnupsOutputGroupPercentLoadread-onlymandatoryThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.2468.1.2.1.1.5NodeupsBypassGroup
1.3.6.1.4.1.2468.1.2.1.1.5.1ScalarupsBypassGroupFrequencyread-onlymandatoryThe present bypass frequency.
1.3.6.1.4.1.2468.1.2.1.1.5.2ScalarupsBypassGroupNumLinesread-onlymandatoryThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.2468.1.2.1.1.5.3TableupsBypassGroupTablenot-accessiblemandatoryA list of bypass table entries. The number of entries is given by the value of upsBypassGroupNumLines.
1.3.6.1.4.1.2468.1.2.1.1.5.3.1RowupsBypassGroupEntrynot-accessiblemandatoryAn entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.2468.1.2.1.1.5.3.1.1ColumnupsBypassGroupLineIndexread-onlymandatoryThe bypass line identifier.
1.3.6.1.4.1.2468.1.2.1.1.5.3.1.2ColumnupsBypassGroupVoltageread-onlymandatoryThe present bypass voltage.
1.3.6.1.4.1.2468.1.2.1.1.5.3.1.3ColumnupsBypassGroupCurrentread-onlymandatoryThe present bypass current.
1.3.6.1.4.1.2468.1.2.1.1.5.3.1.4ColumnupsBypassGroupPowerread-onlymandatoryThe present true power conveyed by the bypass.
1.3.6.1.4.1.2468.1.2.1.1.6NodeupsTestGroup
1.3.6.1.4.1.2468.1.2.1.1.6.1ScalarupsTestBatteryTestSettingTimeread-writemandatoryThe object specify the test time for battery test.
1.3.6.1.4.1.2468.1.2.1.1.6.2ScalarupsBatteryTestread-writemandatoryThis object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
1.3.6.1.4.1.2468.1.2.1.1.6.3ScalarupsTestBatteryTestResultread-onlymandatoryThe results of the current or last UPS diagnostics test performed. The values for donePassed(1), doneWarning(2), and doneError(3) indicate that the test comple…
1.3.6.1.4.1.2468.1.2.1.1.6.4ScalarupsTestBatteryTestStartTimeread-onlymandatoryThe value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestBatte…
1.3.6.1.4.1.2468.1.2.1.1.6.5ScalarupsTestBatteryTestElapsedTimeread-onlymandatoryThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.2468.1.2.1.1.6.6TableupsBatteryTestScheduleTablenot-accessiblemandatoryTable which describes the schedule for automatically battery test.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1RowupsBatteryTestScheduleEntrynot-accessiblemandatory
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.1ColumnupsBatteryTestScheduleIndexread-onlymandatoryThe index of battery test scheduled.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.2ColumnupsBatteryTestScheduleDayread-writemandatoryThe weekday on which the UPS should start battery test.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.3ColumnupsBatteryTestScheduleTimeread-writemandatoryThe time that the battery test will be initiated in hh:mm format.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.4ColumnupsBatteryTestScheduleTyperead-writemandatoryThe type of battery test.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.5ColumnupsBatteryTestScheduleTestWithTimeread-onlymandatoryThe battTestWithTime of battery test is supported or not.
1.3.6.1.4.1.2468.1.2.1.1.6.6.1.6ColumnupsBatteryTestScheduleSpecialDayread-writemandatoryThe special day that the battery test will be initiated in dd/mm/yyyy format.
1.3.6.1.4.1.2468.1.2.1.1.7NodeupsControlGroup
1.3.6.1.4.1.2468.1.2.1.1.7.1ScalarupsControlUpsShutdownDelayread-writemandatoryThe delay in seconds the UPS remains on after being told to turn off.
1.3.6.1.4.1.2468.1.2.1.1.7.2ScalarupsControlUpsSleepTimeread-writemandatoryThe time in minutes for the UPS to go to sleep when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state. O…
1.3.6.1.4.1.2468.1.2.1.1.7.3ScalarupsControlUpsOnOffControlread-writemandatorySetting this variable to control UPS output status. turnUpsOff(1) will set UPS turn off output after upsControlUpsShutdownDelay period expired. putUpsToSleep(2…
1.3.6.1.4.1.2468.1.2.1.1.7.4TableupsControlShutdownParametersTablenot-accessiblemandatoryTable which describes the parametes for shutdown process when shutdown event occurs
1.3.6.1.4.1.2468.1.2.1.1.7.4.1RowupsControlShutdownParametersEntrynot-accessiblemandatory
1.3.6.1.4.1.2468.1.2.1.1.7.4.1.1ColumnupsControlEventread-onlymandatoryThe shutdown event identification
1.3.6.1.4.1.2468.1.2.1.1.7.4.1.2ColumnupsControlEventStatusread-writemandatoryStatus of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
1.3.6.1.4.1.2468.1.2.1.1.7.4.1.3ColumnupsControlDelayread-writemandatoryThe Delay after the occurance of the curresponding shutdown event that USHA should issue shutdown request to connected clients. For WeeklyScheduledShutdown and…
1.3.6.1.4.1.2468.1.2.1.1.7.4.1.4ColumnupsControlFirstWarningread-writemandatoryThe delay after the occurance of the curresponding shutdown event that the USHA will start sending the warning message to the connected clients. The value is i…
1.3.6.1.4.1.2468.1.2.1.1.7.4.1.5ColumnupsControlWarningIntervalread-writemandatoryThe frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
1.3.6.1.4.1.2468.1.2.1.1.7.5TableupsControlWeeklyScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups by weekly.
1.3.6.1.4.1.2468.1.2.1.1.7.5.1RowupsControlWeeklyScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.2468.1.2.1.1.7.5.1.1ColumnupsControlWeeklyIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.2468.1.2.1.1.7.5.1.2ColumnupsControlWeeklyShutdownDayread-writemandatoryThe weekday on which the UPS should shut down.
1.3.6.1.4.1.2468.1.2.1.1.7.5.1.3ColumnupsControlWeeklyShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm format.
1.3.6.1.4.1.2468.1.2.1.1.7.5.1.4ColumnupsControlWeeklyRestartDayread-writemandatoryThe weekday on which the UPS should restart
1.3.6.1.4.1.2468.1.2.1.1.7.5.1.5ColumnupsControlWeeklyRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm format.
1.3.6.1.4.1.2468.1.2.1.1.7.6TableupsControlSpecialScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups.
1.3.6.1.4.1.2468.1.2.1.1.7.6.1RowupsControlSpecialScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.2468.1.2.1.1.7.6.1.1ColumnupsControlSpecialIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.2468.1.2.1.1.7.6.1.2ColumnupsControlSpecialShutdownDayread-writemandatoryThe date on which the UPS should shut down in dd/mm/yyyy format.
1.3.6.1.4.1.2468.1.2.1.1.7.6.1.3ColumnupsControlSpecialShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm format
1.3.6.1.4.1.2468.1.2.1.1.7.6.1.4ColumnupsControlSpecialRestartDayread-writemandatoryThe date on which the UPS should restart in dd/mm/yyyy format
1.3.6.1.4.1.2468.1.2.1.1.7.6.1.5ColumnupsControlSpecialRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm format.
1.3.6.1.4.1.2468.1.2.1.1.8NodeupsConfigGroup
1.3.6.1.4.1.2468.1.2.1.1.8.1ScalarupsConfigGroupInputVoltageread-onlymandatoryThe magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a v…
1.3.6.1.4.1.2468.1.2.1.1.8.2ScalarupsConfigGroupInputFreqread-onlymandatoryThe nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is no…
1.3.6.1.4.1.2468.1.2.1.1.8.3ScalarupsConfigGroupOutputVoltageread-onlymandatoryThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.2468.1.2.1.1.8.4ScalarupsConfigGroupOutputFreqread-onlymandatoryThe nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is n…
1.3.6.1.4.1.2468.1.2.1.1.8.5ScalarupsConfigGroupOutputVAread-onlymandatoryThe magnitude of the nominal Volt-Amp rating.
1.3.6.1.4.1.2468.1.2.1.1.8.6ScalarupsConfigGroupOutputPowerread-onlymandatoryThe magnitude of the nominal true power rating.
1.3.6.1.4.1.2468.1.2.1.1.8.7ScalarupsConfigGroupOverTemperatureSetPointread-writemandatoryThe maximum temperature allowed before the UPS operation temperature is too high.
1.3.6.1.4.1.2468.1.2.1.1.8.8ScalarupsConfigGroupOverLoadSetPointread-writemandatoryThe maximum output load allowed before the load is too high for UPS operation.
1.3.6.1.4.1.2468.1.2.1.1.9NodeupsClients
1.3.6.1.4.1.2468.1.2.1.1.9.1ScalarupsClientsConnectedNumread-onlymandatoryThe count of clients which have resgistered for UPS shutdown control.
1.3.6.1.4.1.2468.1.2.1.1.9.2TableupsDevicesTablenot-accessiblemandatoryThe devices powered by UPS and registered to USHA
1.3.6.1.4.1.2468.1.2.1.1.9.2.1RowupsDevicesEntrynot-accessiblemandatoryThe devices protected by USHA
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.1ColumnindexOfDeviceread-onlymandatoryThe index of the device that is plugged into the UPS.
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.2ColumnaddrOfDeviceread-onlymandatoryThe ip address of the device.
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.3ColumnnameOfDeviceread-onlymandatoryThe name/description of the device plugged into the UPS.
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.4ColumntimeOfConnectionread-onlymandatoryThe device registered to USHA
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.5ColumntimeOfConnectionTimeread-onlymandatoryThe device registered time to USHA.
1.3.6.1.4.1.2468.1.2.1.1.9.2.1.6ColumntimeOfConnectionTimeoutread-onlymandatoryThe device timeout counter. Unit: 10 seconds
1.3.6.1.4.1.2468.1.2.1.1.10NodeagentConfig
1.3.6.1.4.1.2468.1.2.1.1.10.1ScalaragentConfigIpaddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.2468.1.2.1.1.10.2ScalaragentConfigGatewayread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.2468.1.2.1.1.10.3ScalaragentConfigSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.2468.1.2.1.1.10.4ScalaragentConfigDateread-writemandatoryThe date in agent, format is (dd/mm/yyyy)
1.3.6.1.4.1.2468.1.2.1.1.10.5ScalaragentConfigTimeread-writemandatoryThe time in agent, format is (hh:mm:ss)
1.3.6.1.4.1.2468.1.2.1.1.10.6ScalaragentConfigPrimaryTimeServerread-writemandatoryThe primary time server is responsible for sending the correct time to the agent.
1.3.6.1.4.1.2468.1.2.1.1.10.7ScalaragentConfigSecondaryTimeServerread-writemandatoryThe secondary time server is responsible for sending the correct time to the agent.
1.3.6.1.4.1.2468.1.2.1.1.10.8ScalaragentConfigHistoryLogFrequencyread-writemandatoryThe frequency of the updation of the history log. The value is in seconds
1.3.6.1.4.1.2468.1.2.1.1.10.9ScalaragentConfigExtHistoryLogFrequencyread-writemandatoryThe ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which i…
1.3.6.1.4.1.2468.1.2.1.1.10.10ScalaragentConfigPollRateread-writemandatoryThe frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
1.3.6.1.4.1.2468.1.2.1.1.10.11ScalaragentConfigBaudRateread-onlymandatoryThe serial port communication speed. only 9600 allowed
1.3.6.1.4.1.2468.1.2.1.1.10.12ScalaragentConfigDhcpStatueread-writemandatoryEnable or disable DHCP/BootP capability
1.3.6.1.4.1.2468.1.2.1.1.10.13ScalaragentConfigTelnetStatueread-writemandatoryEnable or disable telnet access
1.3.6.1.4.1.2468.1.2.1.1.10.14ScalaragentConfigTftpStatueread-writemandatoryEnable or disable network upgrade capability
1.3.6.1.4.1.2468.1.2.1.1.10.15ScalaragentConfigResetToDefaultread-writemandatoryReset all parameters of USHA to default value
1.3.6.1.4.1.2468.1.2.1.1.10.16ScalaragentConfigRestartread-writemandatoryRestart USHA
1.3.6.1.4.1.2468.1.2.1.1.10.17ScalaragentConfigClearAgentLogread-writemandatoryClear agent log data
1.3.6.1.4.1.2468.1.2.1.1.10.18ScalaragentConfigClearEventLogread-writemandatoryClear event log data
1.3.6.1.4.1.2468.1.2.1.1.10.19ScalaragentConfigClearExtHistoryLogread-writemandatoryClear extented history log data
1.3.6.1.4.1.2468.1.2.1.1.10.20ScalaragentConfigClearHistoryLogread-writemandatoryClear history log data
1.3.6.1.4.1.2468.1.2.1.1.10.21ScalaragentConfigTrapRetryCountread-writemandatoryThe count of repeat traps to send to NMS before trap acknowledge received.
1.3.6.1.4.1.2468.1.2.1.1.10.22ScalaragentConfigTrapRetryTimeread-writemandatoryThe time between retry traps sned to NMS.
1.3.6.1.4.1.2468.1.2.1.1.10.23ScalaragentConfigTrapAckSignatureread-writemandatoryThe signature of trap acknowledge.
1.3.6.1.4.1.2468.1.2.1.1.10.24ScalaragentConfigMibVersionread-onlymandatoryThe version of MIB spec.
1.3.6.1.4.1.2468.1.2.1.1.10.25TableagentConfigTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers
1.3.6.1.4.1.2468.1.2.1.1.10.25.1RowagentConfigTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.3ColumnreceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.4ColumnreceiverNmsTyperead-writemandatoryThe trap group that NMS desired.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.5ColumnreceiverSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.2468.1.2.1.1.10.25.1.6ColumnreceiverDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.2468.1.2.1.1.10.26TableagentConfigAccessControlTablenot-accessiblemandatoryA list of managers which can access USHA with private community string.
1.3.6.1.4.1.2468.1.2.1.1.10.26.1RowagentConfigAccessControlEntrynot-accessiblemandatoryThe managers.
1.3.6.1.4.1.2468.1.2.1.1.10.26.1.1ColumnaccessIndexread-onlymandatoryThe index to a access control entry.
1.3.6.1.4.1.2468.1.2.1.1.10.26.1.2ColumnaccessControlAddrread-writemandatoryThe IP address of the manager to access USHA
1.3.6.1.4.1.2468.1.2.1.1.10.26.1.3ColumnaccessCommunityStringread-writemandatoryThe community name to use in the manager when access USHA
1.3.6.1.4.1.2468.1.2.1.1.10.26.1.4ColumnaccessControlModeread-writemandatoryAccess type, only read/Write access type can change parameter of USHA
1.3.6.1.4.1.2468.1.2.1.1.10.27ScalaragentConfigDefaultLanguageread-writemandatoryThe default languauge for browser, when set to auto(1) USHA will send page in the language depends on the request language of browser.
1.3.6.1.4.1.2468.1.2.1.1.11NodeemdStatus
1.3.6.1.4.1.2468.1.2.1.1.11.1ScalaremdSatatusEmdTyperead-onlymandatoryThe type of EMD plugged into the port.
1.3.6.1.4.1.2468.1.2.1.1.11.2ScalaremdSatatusTemperatureread-onlymandatoryThe measurement of EMD temperature, in 0.1 degree
1.3.6.1.4.1.2468.1.2.1.1.11.3ScalaremdSatatusHumidityread-onlymandatoryThe measurement of EMD humidity, in 0.1 degree
1.3.6.1.4.1.2468.1.2.1.1.11.4ScalaremdSatatusAlarm1read-onlymandatoryThe EMD alarm-1 status
1.3.6.1.4.1.2468.1.2.1.1.11.5ScalaremdSatatusAlarm2read-onlymandatoryThe EMD alarm-2 status
1.3.6.1.4.1.2468.1.2.1.1.12NodeemdConfig
1.3.6.1.4.1.2468.1.2.1.1.12.1ScalarusahEmdConfigEmdConfigread-writemandatoryEnable or disable to detect presence of EMD
1.3.6.1.4.1.2468.1.2.1.1.12.2ScalaremdConfigEmdNameread-writemandatoryDescription of EMD
1.3.6.1.4.1.2468.1.2.1.1.12.3NodeemdConfigTemperature
1.3.6.1.4.1.2468.1.2.1.1.12.3.1ScalaremdConfigTempNameread-writemandatoryDescription of EMD temperature sensor
1.3.6.1.4.1.2468.1.2.1.1.12.3.2ScalaremdConfigTempHighSetPointread-writemandatoryThe set point for high temperature warning, in degrees
1.3.6.1.4.1.2468.1.2.1.1.12.3.3ScalaremdConfigTempHighStatusread-writemandatoryTo enable/disable high set point check with emd temperature.
1.3.6.1.4.1.2468.1.2.1.1.12.3.4ScalaremdConfigTempLowSetPointread-writemandatoryThe set point for low temperature warning, in degrees
1.3.6.1.4.1.2468.1.2.1.1.12.3.5ScalaremdConfigTempLowStatusread-writemandatoryTo enable/disable low set point check with emd temperature.
1.3.6.1.4.1.2468.1.2.1.1.12.3.6ScalaremdConfigTempOffsetread-writemandatoryThe offset to calibrate temperature of EMD, in degrees
1.3.6.1.4.1.2468.1.2.1.1.12.4NodeemdConfigHumidity
1.3.6.1.4.1.2468.1.2.1.1.12.4.1ScalaremdConfigHumidityNameread-writemandatoryDescription of EMD humidity sensor
1.3.6.1.4.1.2468.1.2.1.1.12.4.2ScalaremdConfigHumidityHighSetPointread-writemandatoryThe set point for high humidity warning, in %
1.3.6.1.4.1.2468.1.2.1.1.12.4.3ScalaremdConfigHumidityLowStatusread-writemandatoryTo enable/disable high set point check with emd humidity.
1.3.6.1.4.1.2468.1.2.1.1.12.4.4ScalaremdConfigHumidityLowSetPointread-writemandatoryThe set point for low humidity warning, in %
1.3.6.1.4.1.2468.1.2.1.1.12.4.5ScalaremdConfigHumidityHighStatusread-writemandatoryTo enable/disable low set point check with emd humidity.
1.3.6.1.4.1.2468.1.2.1.1.12.4.6ScalaremdConfigHumidityOffsetread-writemandatoryThe offset to calibrate humidity of EMD, in %
1.3.6.1.4.1.2468.1.2.1.1.12.5NodeemdConfigAlarm1
1.3.6.1.4.1.2468.1.2.1.1.12.5.1ScalaremdConfigAlarm1Nameread-writemandatoryDescription of EMD alarm-1
1.3.6.1.4.1.2468.1.2.1.1.12.5.2ScalaremdConfigAlarm1Typeread-writemandatoryThe alarm-1 operation type
1.3.6.1.4.1.2468.1.2.1.1.12.6NodeemdConfigAlarm2
1.3.6.1.4.1.2468.1.2.1.1.12.6.1ScalaremdConfigAlarm2Nameread-writemandatoryDescription of EMD alarm-2
1.3.6.1.4.1.2468.1.2.1.1.12.6.2ScalaremdConfigAlarm2Typeread-writemandatoryThe alarm-1 operation type
1.3.6.1.4.1.2468.1.2.1.2NodeupsTrapGroup
1.3.6.1.4.1.2468.1.2.1.2.1NodeushaPowerRestoredINFORMATION: Utility power has been restore.
1.3.6.1.4.1.2468.1.2.1.2.2NodeushaPowerFailWARNING: Utility power not available.
1.3.6.1.4.1.2468.1.2.1.2.3NodeushaReturnFromLowBatteryINFORMATION: The UPS has return from a low battery condition.
1.3.6.1.4.1.2468.1.2.1.2.4NodeushaLowBatterySEVERE: The UPS batteries are low and will soon be exhausted.
1.3.6.1.4.1.2468.1.2.1.2.5NodeushaUpsOkINFORMATION: The ups is working fine.
1.3.6.1.4.1.2468.1.2.1.2.6NodeushaUpsFailedSEVERE: The ups is not working fine.
1.3.6.1.4.1.2468.1.2.1.2.7NodeushaUpsNotOnBatteryINFORMATION: The UPS is not on battery power.
1.3.6.1.4.1.2468.1.2.1.2.8NodeushaUpsOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.2468.1.2.1.2.9NodeushaTestOverINFORMATION: The testing of UPS is completed.
1.3.6.1.4.1.2468.1.2.1.2.10NodeushaTestInProgressINFORMATION: The testing is going on ups.
1.3.6.1.4.1.2468.1.2.1.2.11NodeushaBypassOnINFORMATION: The UPS has enabled bypass.
1.3.6.1.4.1.2468.1.2.1.2.12NodeushaUpsOnlineINFORMATION: The UPS is not on Bypass and return to normal status.
1.3.6.1.4.1.2468.1.2.1.2.13NodeushaCommunicationLostSEVERE: Communication to the UPS has been lost.
1.3.6.1.4.1.2468.1.2.1.2.14NodeushaCommunicationEstablishedINFORMATION: Communication with the UPS has been established.
1.3.6.1.4.1.2468.1.2.1.2.15NodeushaUpsGoingDownWARNING: The ups has been given shutdown command.
1.3.6.1.4.1.2468.1.2.1.2.16NodeushaUpsTurnedOffINFORMATION: UPS turn off.
1.3.6.1.4.1.2468.1.2.1.2.17NodeushaUpsSleepingINFORMATION: UPS has entered sleep mode.
1.3.6.1.4.1.2468.1.2.1.2.18NodeushaUpsWokeUpINFORMATION: The UPS woke up from sleep mode.
1.3.6.1.4.1.2468.1.2.1.2.19NodeushaUpsRebootedINFORMATION: The UPS is reboot.
1.3.6.1.4.1.2468.1.2.1.2.20NodeushaUpsShutdownCancelledINFORMATION: The UPS shutdown process had been cancelled.
1.3.6.1.4.1.2468.1.2.1.2.21NodeushaUpsNotOverTemperatureINFORMATION: The UPS internal temperature return to normal.
1.3.6.1.4.1.2468.1.2.1.2.22NodeushaUpsOverTemperatureSEVERE: The UPS temperature is too high.
1.3.6.1.4.1.2468.1.2.1.2.23NodeushaUpsNotOverLoadINFORMATION: The UPS load return from overload.
1.3.6.1.4.1.2468.1.2.1.2.24NodeushaUpsOverLoadSEVERE: The UPS is overload.
1.3.6.1.4.1.2468.1.2.1.2.25NodeushaUpsModuleInsertedWARNING: UPS Battery Module plug-in.
1.3.6.1.4.1.2468.1.2.1.2.26NodeushaUpsModuleRemovedWARNING: UPS Battery Module unplug.
1.3.6.1.4.1.2468.1.2.1.2.27NodeemdTemperatureNotHighINFORMATION: EMD Temperature not over high Set point.
1.3.6.1.4.1.2468.1.2.1.2.28NodeemdTemperatureTooHighWARNING: EMD Temperature over high Set point.
1.3.6.1.4.1.2468.1.2.1.2.29NodeemdTemperatureNotLowINFORMATION: EMD Temperature not under low Set point.
1.3.6.1.4.1.2468.1.2.1.2.30NodeemdTemperatureTooLowWARNING: EMD Temperature under low Set point.
1.3.6.1.4.1.2468.1.2.1.2.31NodeemdHumidityNotHighINFORMATION: EMD Humidity not over high Set point.
1.3.6.1.4.1.2468.1.2.1.2.32NodeemdHumidityTooHighWARNING: EMD Humidity over high Set point.
1.3.6.1.4.1.2468.1.2.1.2.33NodeemdHumidityNotLowINFORMATION: EMD Humidity not under low Set point.
1.3.6.1.4.1.2468.1.2.1.2.34NodeemdHumidityTooLowWARNING: EMD Humidity under low Set point.
1.3.6.1.4.1.2468.1.2.1.2.35NodeemdAlarm1NormalINFORMATION: EMD Alarm-1 not active.
1.3.6.1.4.1.2468.1.2.1.2.36NodeemdAlarm1ActiveWARNING: EMD Alarm-1 activated.
1.3.6.1.4.1.2468.1.2.1.2.37NodeemdAlarm2NormalINFORMATION: EMD Alarm-2 not active.
1.3.6.1.4.1.2468.1.2.1.2.38NodeemdAlarm2ActiveWARNING: EMD Alarm-2 activated.
1.3.6.1.4.1.2468.1.2.1.2.39NodeushaUpsInternalwarningWARNING: Internal warning.
1.3.6.1.4.1.2468.1.2.1.2.40NodeushaUpsReturnFromInternalwarningINFORMATION: Return from Internal warning.
1.3.6.1.4.1.2468.1.2.1.2.41NodeushaUpsEPOActiveWARNING: EPO Active.
1.3.6.1.4.1.2468.1.2.1.2.42NodeushaUpsReturnFromEPOActiveINFORMATION: Return from EPO Active.
1.3.6.1.4.1.2468.1.2.1.2.43NodeushaUpsModuleUnlockWARNING: Module Unlock.
1.3.6.1.4.1.2468.1.2.1.2.44NodeushaUpsReturnFromModuleUnlockINFORMATION: Return from Module Unlock.
1.3.6.1.4.1.2468.1.2.1.2.45NodeushaUpsMain1NeutrallossWARNING: Main 1 Neutral loss.
1.3.6.1.4.1.2468.1.2.1.2.46NodeushaUpsReturnFromMain1NeutrallossINFORMATION: Return from Main 1 Neutral loss.
1.3.6.1.4.1.2468.1.2.1.2.47NodeushaUpsMain1phaseerrorWARNING: Main 1 phase error.
1.3.6.1.4.1.2468.1.2.1.2.48NodeushaUpsReturnFromMain1phaseerrorINFORMATION: Return from Main 1 phase error.
1.3.6.1.4.1.2468.1.2.1.2.49NodeushaUpsSitefaultWARNING: Site fault.
1.3.6.1.4.1.2468.1.2.1.2.50NodeushaUpsReturnFromSitefaultINFORMATION: Return from Site fault.
1.3.6.1.4.1.2468.1.2.1.2.51NodeushaUpsBypassAbnormalWARNING: Bypass Abnormal.
1.3.6.1.4.1.2468.1.2.1.2.52NodeushaUpsReturnFromBypassAbnormalINFORMATION: Return from Bypass Abnormal.
1.3.6.1.4.1.2468.1.2.1.2.53NodeushaUpsBypassPhaseErrorWARNING: Bypass Phase Error.
1.3.6.1.4.1.2468.1.2.1.2.54NodeushaUpsReturnFromBypassPhaseErrorINFORMATION: Return from Bypass Phase Error.
1.3.6.1.4.1.2468.1.2.1.2.55NodeushaUpsBatteryOpenWARNING: Battery Open.
1.3.6.1.4.1.2468.1.2.1.2.56NodeushaUpsReturnFromBatteryOpenINFORMATION: Return from Battery Open.
1.3.6.1.4.1.2468.1.2.1.2.57NodeushaUpsBatteryOverChargeWARNING: Battery Over Charge.
1.3.6.1.4.1.2468.1.2.1.2.58NodeushaUpsReturnFromBatteryOverChargeINFORMATION: Return from Battery Over Charge.
1.3.6.1.4.1.2468.1.2.1.2.59NodeushaUpsBatteryReverseWARNING: Battery Reverse.
1.3.6.1.4.1.2468.1.2.1.2.60NodeushaUpsReturnFromBatteryReverseINFORMATION: Return from Battery Reverse.
1.3.6.1.4.1.2468.1.2.1.2.61NodeushaUpsOverloadforewarningWARNING: Overload forewarning.
1.3.6.1.4.1.2468.1.2.1.2.62NodeushaUpsReturnFromOverloadforewarningINFORMATION: Return from Overload forewarning.
1.3.6.1.4.1.2468.1.2.1.2.63NodeushaUpsOverloadWarningWARNING: Overload Warning.
1.3.6.1.4.1.2468.1.2.1.2.64NodeushaUpsReturnFromOverloadWarningINFORMATION: Return from Overload Warning.
1.3.6.1.4.1.2468.1.2.1.2.65NodeushaUpsFanLockWARNING: Fan Lock.
1.3.6.1.4.1.2468.1.2.1.2.66NodeushaUpsReturnFromFanLockINFORMATION: Return from Fan Lock.
1.3.6.1.4.1.2468.1.2.1.2.67NodeushaUpsMaintaincoverisopenWARNING: Maintain cover is open.
1.3.6.1.4.1.2468.1.2.1.2.68NodeushaUpsReturnFromMaintaincoverisopenINFORMATION: Return from Maintain cover is open.
1.3.6.1.4.1.2468.1.2.1.2.69NodeushaUpsChargerfaultWARNING: Charger fault.
1.3.6.1.4.1.2468.1.2.1.2.70NodeushaUpsReturnFromChargerfaultINFORMATION: Return from Charger fault.
1.3.6.1.4.1.2468.1.2.1.2.71NodeushaUpsModulelocationerrorWARNING: Module location error.
1.3.6.1.4.1.2468.1.2.1.2.72NodeushaUpsReturnFromModulelocationerrorINFORMATION: Return from Module location error.
1.3.6.1.4.1.2468.1.2.1.2.73NodeushaUpsTurnonabnormalWARNING: Turn on abnormal.
1.3.6.1.4.1.2468.1.2.1.2.74NodeushaUpsReturnFromTurnonabnormalINFORMATION: Return from Turn on abnormal.
1.3.6.1.4.1.2468.1.2.1.2.75NodeushaUpsRedundancylossWARNING: Redundancy loss.
1.3.6.1.4.1.2468.1.2.1.2.76NodeushaUpsReturnFromRedundancylossINFORMATION: Return from Redundancy loss.
1.3.6.1.4.1.2468.1.2.1.2.77NodeushaUpsHotSwapActivedWARNING: Hot Swap Actived.
1.3.6.1.4.1.2468.1.2.1.2.78NodeushaUpsReturnFromHotSwapActivedINFORMATION: Return from Hot Swap Actived.
1.3.6.1.4.1.2468.1.2.1.2.79NodeushaUpsBatteryInformWARNING: Battery Inform.
1.3.6.1.4.1.2468.1.2.1.2.80NodeushaUpsReturnFromBatteryInformINFORMATION: Return from Battery Inform.
1.3.6.1.4.1.2468.1.2.1.2.81NodeushaUpsInspectionInformWARNING: Inspection Inform.
1.3.6.1.4.1.2468.1.2.1.2.82NodeushaUpsReturnFromInspectionInformINFORMATION: Return from Inspection Inform.
1.3.6.1.4.1.2468.1.2.1.2.83NodeushaUpsGuaranteeInformWARNING: Guarantee Inform.
1.3.6.1.4.1.2468.1.2.1.2.84NodeushaUpsReturnFromGuaranteeInformINFORMATION: Return from Guarantee Inform.
1.3.6.1.4.1.2468.1.2.1.2.85NodeushaUpsTemperatureLowWARNING: Temperature Low.
1.3.6.1.4.1.2468.1.2.1.2.86NodeushaUpsReturnFromTemperatureLowINFORMATION: Return from Temperature Low.
1.3.6.1.4.1.2468.1.2.1.2.87NodeushaUpsTemperatureHighWARNING: Temperature High.
1.3.6.1.4.1.2468.1.2.1.2.88NodeushaUpsReturnFromTemperatureHighINFORMATION: Return from Temperature High.
1.3.6.1.4.1.2468.1.2.1.2.89NodeushaUpsBatteryOverTemperatureWARNING: Battery Over Temperature.
1.3.6.1.4.1.2468.1.2.1.2.90NodeushaUpsReturnFromBatteryOverTemperatureINFORMATION: Return from Battery Over Temperature.
1.3.6.1.4.1.2468.1.2.1.2.91NodeushaUpsFanMaintainInformWARNING: Fan Maintain Inform.
1.3.6.1.4.1.2468.1.2.1.2.92NodeushaUpsReturnFromFanMaintainInformINFORMATION: Return from Fan Maintain Inform.
1.3.6.1.4.1.2468.1.2.1.2.93NodeushaUpsBusCapacitanceMaintainInformWARNING: Bus Capacitance Maintain Inform.
1.3.6.1.4.1.2468.1.2.1.2.94NodeushaUpsReturnFromBusCapacitanceMaintainInformINFORMATION: Return from Bus Capacitance Maintain Inform.
1.3.6.1.4.1.2468.1.2.1.2.95NodeushaUpsSystemOverCapacityWARNING: System Over Capacity.
1.3.6.1.4.1.2468.1.2.1.2.96NodeushaUpsReturnFromSystemOverCapacityINFORMATION: Return from System Over Capacity.