MIB Viewer

hwSetBattsHighTempAction

OBJECT-TYPE
1.3.6.1.4.1.2011.6.164.1.4.1.4
Access
read-write
Status
current
Sub-identifiers
0
Battery high-temperature protection mode. It is an enumeration value, and can be configured. If the enumeration value is 1, it indicates the power-off protection mode; If the enumeration value is 2, it indicates the protection mode of lowering the output voltage of the rectifier module. unknown(255) it is do nothing
INTEGER { blvd(1), lowerDcOutput(2), unknown(255) }