MIB Viewer
MIB Viewer Desktop New

reliabilityId

OBJECT-TYPE
1.3.6.1.4.1.13742.6.10.1.2.1.2
Access
read-only
Status
current
Source
PDU2-MIB
Sub-identifiers
0
Unique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MAIN.CSUMERRLASTHOUR Number of checksum errors in sub (controller board) to main (CPU board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.SUB.CSUMERRLASTHOUR Number of checksum errors in main (CPU board) to sub (controller board) communication in the last hour on controller with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.TOUTLASTHOUR Number of communication timeouts to controller with serial number <serial> and bus address <addr> in the last hour. CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT Number of cycles the relay <num> on the controller board with serial number <serial> and bus address <addr> has made. A cycle is an off->on followed by an on->off event later. The count is increased on the off->on transition. CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR Number of failed switching operations on relay <num> on the controller board with serial number <serial> and bus address <addr> in the last hour. It depends on the specific controller board hardware and what error conditions are detected. CTRL.<serial>.<addr>.EMRSTCNT Number of energy-meter resets on the controller board with serial number <serial> and bus address <addr>. CTRL.<serial>.<addr>.RSTCNT Number of resets of the controller board with serial number <serial> and bus address <addr>.
DisplayString