nnciAlarmQueueType

OBJECT-TYPE
1.3.6.1.4.1.123.2.4.1.1.9
Access
read-write
Status
mandatory
Sub-identifiers
0
This paramater is used to control the behaviour of the alarm queue in the overlfow case, i.e. when the alarm facility attempts to place the 65th alarm into the queue. If the queue type is set to Fixed, the 65th and 64th alarms will be discarded and the 'Too Many Alarms' alarm added as the last entry in the queue. If the queue type is set to Circular, the 65th alarm will overwrite the first alarm in the queue
INTEGER { fixedAlarmQueue(1), circularAlarmQueue(2) }