outletSequenceDelay

OBJECT-TYPE
1.3.6.1.4.1.13742.6.3.5.3.1.32
Access
read-write
Status
current
Source
PDU2-MIB
Sub-identifiers
0
The time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets on operation is executed 2) Power to the PDU is cycledThis applies only when all outlets are being switched on or cycled. It is specified in seconds; 1 <= value <= 3600 seconds. The actual time interval used can never be less than the inrushGuardDelay defined in the unitConfigurationTable. Examples: 1) inrush Guard Delay is 2 seconds and outletSequenceDelay is 5 seconds. The time interval will be 5 seconds 2) inrush Guard Delay is 5 seconds and outletSequenceDelay is 2 seconds. The time interval will be 5 seconds
Unsigned32