MIB Viewer

utAlarmFilteringSeverity

OBJECT-TYPE
1.3.6.1.4.1.1949.2.3.2.2.3.1
Access
read-write
Status
current
Sub-identifiers
0
The leaf is used for filtering specified severity alarms. bit0 - cleared alarm bit1 - warning alarm bit2 - minor alarm bit3 - major alarm bit4 - critical alarm 1 - represent the alarm will be sent to NMS; 0 - this kind of alarms will be filtered by agent; other useless bits: fill in digitial 1 always. for examples, if operator wants to filter critical alarms. this leaf needs to be set to value 0x FF FF FF E1 low 8 bits are: 1110,0001 = E1 cauz if operator wants to filter critical alarms, meaning that others whose priority is lower than critical need to be filtered as well. attention: cleared alarm can't be filtered. DEFAULT:{-1}
Integer32