outputUserConfig

OBJECT-TYPE
1.3.6.1.4.1.19947.1.3.2.1.37
Access
read-write
Status
current
Sub-identifiers
0
Definition of user-changeable items. A bit field packed into an integer which define the behavior of the output channel. Usable for WIENER LV devices only. The position of the bit fields in the integer value are: Bit 0: Voltage ramping at switch off: 0: Ramp down at switch off. 1: No ramp at switch off (immediate off) Bit 1, 2: Set different regulation modes, dependent on the cable inductance: 0: fast: short cables, up to 1 meter. 1: moderate: cables from 1 to 30 meter. 2: fast: identical to 0 (should not be used) 3: slow: cables longer than 30 meter. Bit 3: Internal sense line connection to the output (MPOD only): 0: The sense input at the sense connector is used for regulation. 1: The output voltage is used for regulation. Any signals at the sense connector are ignored. Bit 4: Enable External Inhibit input. 0: The external inhibit input is ignored. 1: The external inhibit input must be connected to a voltage source to allow switch on. Bit 5: Disable Global Inhibit inputs. 0: The global inhibit/interlock inputs of the system is active. 1: The global inhibit/interlock inputs of the system is ignored. Bit 6: Automatic Power On. 0: After switching the main system switch ON, the output is not switched on automatically. A separate outputSwitch command is required. 1: After switching the main system switch ON, the output is switched on automatically. If 'Disable Global Inhibit' (bit 5) is set, the output will be switched on regardless of the global inhibit/interlock signals. Community required for write access: guru.
Integer32 (0..127)