MIB Viewer

outputTripActionTimeout

OBJECT-TYPE
1.3.6.1.4.1.19947.1.3.2.1.54
Access
read-write
Status
current
Sub-identifiers
0
Trip action if the communication between module and controller has been paused longer than outputTripTimeTimeout. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 14..15 of outputSupervisionBehavior.
OutputTripAction