MIB Viewer

outputSwitch

OBJECT-TYPE
1.3.6.1.4.1.19947.1.3.2.1.9
Access
read-write
Status
current
Sub-identifiers
0
Read: An enumerated value which shows the current state of the output channel. Write: Change the state of the channel. If the channel is On, and the write value is Off, then the channel will switch Off. If the channel is Off, and the write value is On, and if no other signals (mainInhibit, outputInhibit, outputEmergencyOff or outputFailureMaxCurrent) are active, then the channel will switch on. If the write value is resetEmergencyOff, then the channel will leave the state EmergencyOff. A write of clearEvents is necessary before the voltage can ramp up again. If the write value is setEmergencyOff, then the channel will have the state EmergencyOff, which means that the High Voltage will switch off without a ramp and reset of the outputVoltage to null volt. If the write value is clearEvents, then all failure messages of the outputStatus will be reset (all channel events, all module events and the state emergencyOff).
INTEGER { off (0), on (1), resetEmergencyOff (2), setEmergencyOff (3), clearEvents (10), setVoltageRippleMeasurementOff(20), setVoltageMeasurementOn(21), setRippleMeasurementOn(22), setVoltageRippleMeasurementOn(23) }