MIB Viewer

moduleStatus

OBJECT-TYPE
1.3.6.1.4.1.19947.1.3.6.1.8
Access
read-only
Status
current
Sub-identifiers
0
A bit string which shows the current module status. If a bit is set (1), the explanation is satisfied: moduleIsFineAdjustment (0), Module has reached state fine adjustment. moduleIsLiveInsertion (2), Module is in state live insertion. moduleNeedService (4), Hardware failure detected (consult iseg Spezialelektronik GmbH). moduleIsHardwareLimitVoltageGood (5), Hardware limit voltage in proper range, using for HV distributor modules with current mirror only. moduleIsInputError (6), Input error in connection with a module access. moduleIsNoSumError (8), All channels without any failure. moduleIsNoRamp (9), All channels stable, no is ramp active. moduleIsSafetyLoopGood (10), Safety loop is closed. moduleIsEventActive (11), Any event is active and mask is set. moduleIsGood (12), Module state is good. moduleIsSupplyGood (13), Power supply is good. moduleIsTemperatureGood (14), Module temperature is good. moduleIsKillEnable (15) Module state of kill enable.
BITS { moduleIsFineAdjustment (0), moduleIsLiveInsertion (2), moduleIsHighVoltageOn (3), moduleNeedService (4), moduleHardwareLimitVoltageIsGood (5), moduleIsInputError (6), moduleIsNoSumError (8), moduleIsNoRamp (9), moduleSafetyLoopIsGood (10), moduleIsEventActive (11), moduleIsGood (12), moduleSupplyIsGood (13), moduleTemperatureIsGood (14), moduleIsKillEnable (15) }