ats5gSwitchConfigNominalFrequency

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.33.3.1.22
Access
read-write
Status
mandatory
Sub-identifiers
0
This is the configurable line frequency in Hertz (Hz) that will be used to select sources. If the difference between ats5gSwitchConfigNominalFrequency and a source's measured frequency is greater than ats5gSwitchConfigFrequencyDeviation, the ATS will disqualify that source. The ATS will be in a 'lost redundancy' state until the source recovers or the configuration is updated.
INTEGER