MIB Viewer
MIB Viewer Desktop New

ats5gSwitchConfigTransferVoltageRange

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.33.3.1.14
Access
read-write
Status
mandatory
Sub-identifiers
0
This value specifies which voltage transfer range should be used to disqualify sources and raise alarms. The narrow transfer voltage must be less than the medium transfer voltage, which must be less than the wide transfer voltage. If the difference between ats5gSwitchConfigNominalVoltage and a source's measured VRMS is greater than the value specified by the selected transfer range, the ATS will disqualify that source. The ATS will be in a 'lost redundancy' state until the source recovers or the configuration is updated.
INTEGER { wide(1), medium(2), narrow(3) }