MIB Viewer

hwSiteDMULoad2LvdCapacity

OBJECT-TYPE
1.3.6.1.4.1.2011.6.164.1.31.2.1.12
Access
read-write
Status
current
Source
EMAP-MIB
Sub-identifiers
0
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue. Value range: 0 to 99, unit: %, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. NOTE: Only the lvd in capacity power off mode, this parameter can be configured successfully.
Integer32 (0..99)